Solar PV Voltage Rise to AS/NZS 4777.1:2024
How to calculate solar PV voltage rise at the point of connection per AS/NZS 4777.1:2024. Formula, cable impedance, and two worked examples.

When a solar PV system injects power into the grid, current flows from the inverter through the installation cables toward the network. This current flowing through the cable impedance raises the voltage at the inverter end above the grid voltage. AS/NZS 4777.1:2024 limits this voltage rise to 2 percent of nominal at the point of common coupling. This guide explains the formula, how it differs from voltage drop, and walks through two worked examples. The Solar PV Sizing Calculator checks voltage rise as part of the system design.
What is voltage rise and why it matters
In a normal installation, load current flows from the grid toward the equipment, causing voltage to drop along the cable. In a solar installation, the inverter generates current that flows in the opposite direction, from the installation back toward the grid. This reverse current flow raises the voltage at the inverter terminals above the grid voltage.
Excessive voltage rise causes problems. Equipment connected to the same circuit sees higher-than-nominal voltage. The inverter may trip on overvoltage protection, reducing energy yield. Neighbours on the same distribution transformer may experience voltage fluctuations as the solar system ramps up and down with cloud cover.
The AS/NZS 4777.1:2024 limit
AS/NZS 4777.1:2024 limits voltage rise caused by the inverter energy system to 2 percent of the nominal voltage at the point of common coupling (PCC). For a 230 V single-phase supply, the limit is 4.6 V. For a 400 V three-phase supply, the limit is 8 V line-to-line.
Some distribution network service providers (DNSPs) allow up to 3 percent on longer distribution feeders, but always check the local connection agreement.
Where voltage rise occurs
Voltage rise accumulates along the cable path from the inverter output to the PCC. In a typical residential installation, this path includes the cable from the inverter to the solar isolator, from the isolator to the switchboard, and from the switchboard to the meter (the PCC). Each segment contributes impedance and voltage rise.
Difference between voltage drop and voltage rise
- Voltage drop: load current flows from grid toward equipment. Voltage decreases. Checked against AS/NZS 3000 Clause 3.6 (5 percent limit).
- Voltage rise: generation current flows from inverter toward grid. Voltage increases. Checked against AS/NZS 4777.1 (2 percent limit).
The formulas are the same; only the direction differs. The Voltage Drop Calculator can be used for both by entering the inverter output current as the design current.
The voltage rise formula
For a single-phase system:
where I is the inverter output current in amps, L is the one-way cable route length in metres divided by 1000, R and X are the cable per-metre resistance and reactance, and cos phi is the inverter power factor (typically 1.0 for modern inverters). The factor of 2 accounts for both the active and the neutral conductor carrying the export current, per AS/NZS 3008.1.1 Equation 4.5(3). For three-phase, replace the 2 with 1.732, because no current flows in the neutral of a balanced three-phase circuit.
Cable resistance and reactance
Use the same R and X tables from AS/NZS 3008.1.1 as for voltage drop calculations. For typical residential solar cables (4 to 6 mm squared copper PVC), reactance is negligible and the bracket reduces to R times cos theta. The phase multiplier still applies, so single phase remains 2 times I times L times R and three phase remains the square root of 3 times I times L times R. For longer commercial runs on larger cables, include reactance.
Impact on sensitive equipment
When voltage rise pushes the installation voltage above nominal, all equipment on the same circuit sees the elevated voltage. Most equipment tolerates plus or minus 10 percent (207 to 253 V for 230 V), but sustained operation near the upper limit accelerates wear on motors, reduces LED driver lifespan, and may cause electronic equipment to shut down on overvoltage protection.
Mitigation strategies
- Increase cable size: lower R reduces voltage rise proportionally.
- Shorten the cable run: shorter route means less total impedance.
- Reactive power control (Q control): modern inverters can absorb reactive power to reduce voltage at the PCC. AS/NZS 4777.2:2020 mandates volt-VAR and volt-watt response modes.
- Export limiting: cap the inverter output to a level that keeps voltage rise within limits.
Worked example: 6.5 kW residential, 50 m run
A 5 kW single-phase inverter (6.5 kW array) is connected to the switchboard 30 metres from the inverter, and the meter is 20 metres from the switchboard. Total route: 50 metres. Cable: 6 mm squared copper PVC. Power factor: 1.0.
Inverter current at rated output: 5000 / 230 = 21.7 A. R for 6 mm squared at 75 degrees (AS/NZS 3008.1.1 Table 35): 3.75 milliohms per metre. Both the active and the neutral carry the export current, so the formula uses 2R.
8.14 V is 3.5 percent of 230 V. Over the 2 percent limit. Fail. Upsize the cable or shorten the run until the calculated rise is under 4.6 V, then re-check.
Worked example: 30 kW commercial, 200 m run
A 30 kW three-phase inverter is connected 200 metres away via 16 mm squared copper XLPE four-core. Power factor: 1.0.
Inverter current per phase: 30,000 / (1.732 times 400) = 43.3 A. R for 16 mm squared at 90 degrees (AS/NZS 3008.1.1 Table 35): 1.47 milliohms per metre.
22.05 V is 5.5 percent of 400 V. Exceeds the 2 percent limit (8 V). 35 mm squared (0.669 milliohms per metre at 90 degrees) still gives 10.03 V. The cable must be upsized to 50 mm squared (0.494, giving 7.41 V or 1.9 percent) or the run shortened.
Common mistakes
- Using the 5 percent voltage drop limit for voltage rise. The voltage rise limit under AS/NZS 4777.1 is 2 percent, not 5 percent.
- Forgetting the meter-to-switchboard cable. The full path from inverter to PCC includes every cable segment.
- Ignoring network impedance. On weak rural networks, upstream impedance is a significant contributor.
Where the calculator fits in
The ElecCalc Solar PV Sizing Calculator includes voltage rise checking. The Cable Sizing Calculator provides R and X values for any cable size.
Common questions
What is the maximum voltage rise allowed by AS/NZS 4777.1 at the point of connection?+
AS/NZS 4777.1:2024 limits voltage rise caused by the inverter energy system to 2 percent of the nominal voltage at the point of common coupling (PCC) for most installations. Some distributors allow up to 3 percent on distribution feeders. For 230 V single-phase the 2 percent limit is 4.6 V.
How do I calculate voltage rise from a solar array to the grid?+
Voltage rise is calculated using the same formula as voltage drop but in the reverse direction. The injected current from the inverter flows through the cable impedance toward the grid, raising the voltage at the inverter end above the grid voltage. The formula is: voltage rise = 2 times I times (R_total times cos phi plus X_total times sin phi) for single-phase, or 1.732 times I times (R_total times cos phi plus X_total times sin phi) for three-phase. The factor of 2 in the single-phase case accounts for both the active and the neutral conductor carrying the export current.
Is voltage rise the same as voltage drop?+
No. Voltage drop occurs when load current flows from the supply toward the load, reducing voltage at the far end. Voltage rise occurs when generation current flows toward the grid, increasing voltage at the inverter end. The formulas are similar but the current direction and its effect on voltage are opposite.
What happens if voltage rise exceeds the limit?+
If voltage rise at the PCC exceeds the AS/NZS 4777.1 limit, the inverter must reduce its output (curtailment) or the distributor may refuse to approve the connection. Options to reduce voltage rise include increasing cable size, reducing cable length, or using reactive power control at the inverter.
Can I reduce voltage rise with reactive power control?+
Yes. Modern grid-connected inverters can absorb reactive power to reduce voltage at the PCC. By absorbing reactive power the inverter reduces the voltage rise caused by active power injection. AS/NZS 4777.2:2020 specifies the volt-VAR and volt-watt response modes that inverters must support.
Saved you time today? Shout the next coffee.
ElecCalc is free, with no login and no paywall, built by a working sparky in Adelaide. A few dollars covers the hosting and keeps the calculators checked against the standards.
On site? Get the same calcs on your phone.
SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.
Building something else? DataQuoll serves Australian emergency incidents, river gauges and trade RDO calendars as an API.
Use the calculator
Related guides