AS/NZS 3000:2018 + 3001.1

EV Charger Cable Sizing

Cable and breaker sizing for EV charger installations. First AU/NZ dedicated tool, per AS/NZS 3000 and 3001.1.

Inputs

Advanced options

Default: 40°C (PVC 75°C cable)

AS/NZS 3000:2018 default is 5%

For circuits < 2.4 kW sharing

Results

Recommended Cable Size

6

mm²

Capacity: 40A

Charger Current32.2 A
Recommended Breaker40 A
RCD Type RequiredType A
Voltage Drop3.1% (7.13V)
Dedicated Circuit RequiredYes

Breaker Rating ≥ Charger Current

40 A (>= 32.2 A)

Cable Current Capacity

40 A (>= 32.2 A)

Voltage Drop

3.1 % (<= 5 %)

Dedicated Circuit Required

1 (>= 1 )

RCD Protection

1 (>= 1 )

Show the working
Step by step derivation of the result
StepWorkingResultReference
Charger current (Ib)7.4 kW x 1000 / (230 V x 1.000) = 32.2 A32.2 AI = P / (V × 1)
Recommended breaker sizeSmallest standard size >= 32.2 A from [10, 16, 20, 25, 32, 40, 50, 63, 80, 100] A = 40 A40 ANext standard size ≥ charger current (AS/NZS 3000:2018)
Temperature derating (Ct)sqrt((75 - 40) / (75 - 40)) = 1.0001.000AS/NZS 3008.1.1:2025 Table 28 (PVC 75°C)
Cable size selection, 6mm²Smallest size satisfying current capacity (40 A >= 32.2 A) and voltage drop (3.1% <= 5%) is 6 mm2 copper6 mm²AS/NZS 3008.1.1:2025 + AS/NZS 3000:2018 Cl. 3.6
Derated cable capacityTable lookup: 6 mm2 copper clipped direct = 40 A; 40 A x 1 (copper) x 1.000 (Ct) = 40 A40 ABase rating × Ct
Voltage drop (ΔV)32.2 A x 3.6900 mohm/m x 30 m x 2 (1-phase) / 1000 = 7.13 V, which is 3.1% of 230 V7.13 VΔV = (I × R × L × K) / 1000
RCD requirementLookup: charger type level2_single, supply 1-phase gives Type A (level 2 single-phase takes Type A)Type AAS/NZS 3001.1 (EV charging requires RCD protection)

Standards referenced

  • AS/NZS 3000:2018 Clause 2.5. Protection and isolation for electrical installations
  • AS/NZS 3000:2018 Clause 3.6. Voltage drop in consumer mains and sub-mains (5% limit)
  • AS/NZS 3008.1.1:2025 Clause 4. Current-carrying capacity of cables, Australian conditions
  • AS/NZS 3001.1. EV Supply Equipment, safety requirements and RCD protection

Lookup values used by these calculators are indicative and awaiting validation against the current standards. Confirm against your own licensed copy before relying on a result for design.

Important: These results are indicative only. EV charger installations must comply with AS/NZS 3000:2018 and AS/NZS 3001.1. Do not use for final design without independent verification from a licensed electrical contractor.

EV Charger Installation Guide for AS/NZS 3000:2018

Electric vehicle charger installations are one of the fastest-growing areas of electrical work in Australia. Every EV charger requires a dedicated circuit designed to handle continuous loading (100 percent demand factor), which means cable sizing, protection, and maximum demand calculations are more critical than for most household appliances. This calculator sizes the cable and circuit breaker for an EV charger installation based on charger rating, supply phase, cable run length, installation method, and ambient temperature.

The tool applies the requirements of AS/NZS 3000:2018 for general wiring rules and AS/NZS 3001.1 for transportable structures and vehicle charging. It checks current-carrying capacity per AS/NZS 3008.1.1, voltage drop against the 5% limit in Clause 3.6, and recommends RCD type based on the charger configuration.

Key concepts

  • Continuous load rating. EV chargers are classified as continuous loads because they can draw full rated current for hours at a time. This means the cable and protective device must be rated for 100 percent of the charger current with no diversity reduction. A 32 A charger requires a cable and breaker rated for at least 32 A continuously.
  • RCD type selection. In Australia, AS/NZS 3000:2018 covers EV charging in Appendix P, which is informative guidance rather than a normative requirement. Appendix P4.1 recommends each connecting point be protected by its own RCD of at least Type A rated at not more than 30 mA, and that where the charging station uses an IEC 62196 socket outlet or vehicle connector, protection against DC fault current is also provided, either a Type B RCD or a Type A RCD plus equipment that disconnects the supply on DC fault current above 6 mA, unless the charging station already provides it. In New Zealand, Clause 7.9 is normative, and Clause 7.9.4 requires a Type B RCD complying with IEC/TR 62432 for all EV supplies in non-residential installations. The clause states the RCD type, not a milliamp rating. amendment of the Standard before relying on a Type A RCD alone.
  • Voltage drop. Long cable runs from the switchboard to the garage or carport are common in residential installations. The 5% voltage drop limit (11.5 V on a 230 V circuit) can force a cable size upgrade from 6 mm squared to 10 mm squared on runs longer than approximately 25 metres for a 32 A load.
  • Maximum demand impact. Adding an EV charger increases the property maximum demand by the full charger rating (for example, 7.4 kW for a 32 A single-phase unit). Older homes with 63 A or 80 A mains may need a main switch or supply cable upgrade before the charger can be installed.

Common scenarios

  1. Residential garage, 32 A single-phase. A homeowner wants a 7.4 kW wall-mounted Mode 3 charger installed in a detached garage, 30 metres from the switchboard. The cable run passes through the roof space (40 degrees Celsius ambient). At 32 A continuous, 6 mm squared copper is adequate for current but exceeds the 5% voltage drop limit at 30 m. The calculator recommends upgrading to 10 mm squared, with a 40 A Type A RCD and 32 A curve B MCB.
  2. Commercial car park, three-phase 22 kW. A workplace installs a 32 A three-phase charger on a 35 metre run from the distribution board. Three-phase voltage drop is lower than single-phase for the same current, so 6 mm squared four-core cable is typically sufficient. The circuit requires a Type B RCD (or Type A if the charger has internal DC detection) and a 40 A four-pole MCB.
  3. Older home, mains capacity check. A 1990s house with a 63 A single-phase main switch already has 45 A of existing maximum demand. Adding a 32 A EV charger takes the total to 77 A, exceeding the 63 A main switch. The calculator flags this, and the electrician must arrange a mains upgrade with the distribution network service provider before installing the charger.
Disclaimer: This calculator is a guide only. EV charger installations must comply with AS/NZS 3000:2018, AS/NZS 3001.1, and any applicable network operator requirements. Always verify with a qualified electrical engineer.

Parameters

Every field this calculator accepts, what it means, the range it accepts, and how it feeds the result. Three fields sit under Advanced options; two of them change the answer and one only triggers a warning.

Charger type (level 2 single phase, level 2 three phase, direct current fast)
Selecting a type presets the rating in the form to 7.4, 22 or 50 kilowatts. In the calculation itself it has exactly one effect: a direct current fast charger forces the recommended residual current device to Type B. It does not change the current, the cable, or the breaker.
Charger rating (kilowatts, 0.1 to 350)
The design current is derived straight from this figure, so enter the alternating current input rating from the equipment nameplate, not the vehicle side output. For a direct current fast charger the advertised kilowatt figure is direct current output and the alternating current input is different again, so for those units take the input current from the manufacturer data instead of trusting this field.
Supply phase and supply voltage (single phase 230 volts or three phase 400 volts)
Single phase divides the rating by the voltage; three phase divides by the voltage times the square root of 3. Only 230 and 400 volts are accepted, and the form sets the voltage automatically when you change the phase. Three phase also forces the residual current device recommendation to Type B.
Cable length (metres, 1 to 1,000, one way)
Route length from the switchboard to the charger, measured one way. The return path is already in the voltage drop multiplier, so do not double it. Measure the real route including the drop down the wall and any detour around the building, since the voltage drop check is usually what decides the cable size on domestic jobs.
Conductor material (copper or aluminium)
Aluminium multiplies both the current rating and the conductor resistance by 0.78. Lowering the rating is correct in direction. Lowering the resistance is not: aluminium resists more than copper, not less. See the limits below before using an aluminium result.
Installation method (clipped direct, enclosed in conduit, buried direct)
Recorded with the calculation and shown in saved history, but it does not change any output in this engine. The current ratings used are clipped direct figures throughout. If the run is in conduit in a wall or buried, apply the relevant derating yourself or size the run in the cable sizing calculator, which does model installation method.
Ambient temperature (degrees Celsius, 0 to 70, default 40)
The only derating the engine applies. The factor is the square root of 75 minus ambient, over 75 minus 40, which is the polyvinyl chloride 75 degree form. At 40 degrees the factor is exactly 1.000, at 45 degrees it is 0.926, at 50 degrees 0.845. A run through a roof space in an Australian summer should be entered at 45 to 50 degrees, not 40.
Maximum voltage drop (percent, 0.1 to 10, default 5)
The limit the selected cable must satisfy. The AS/NZS 3000 Clause 3.6 figure of 5 percent applies to the whole installation from the point of supply to the equipment, so if the consumer mains and submain have already used part of that budget, enter only what is left for this final subcircuit, commonly 2 to 3 percent.
Existing load (amperes, 0 to 100)
Only used to raise a warning when the charger is 2.4 kilowatts or less and could share a circuit. It does not perform a maximum demand calculation and it does not check the mains or main switch capacity. For anything above 2.4 kilowatts it has no effect at all beyond one compliance line.

Assumptions and limits

This sizes a cable and picks a breaker for one dedicated charger circuit. Here is exactly what it assumes and where it stops.

What it assumes

  • Design current is the plain rating divided by voltage. No continuous load uplift, no 125 percent factor, no diversity, no allowance for a charger that draws slightly above nameplate. A 7.4 kilowatt unit at 230 volts gives 32.2 amperes and nothing more is added.
  • Cable selection walks the standard sizes and stops at the first that fits. It must satisfy the derated current capacity and the voltage drop limit. Base ratings are the engine placeholder copper clipped direct figures at 40 degrees Celsius, not transcribed from a licensed copy of AS/NZS 3008.1.1.
  • Only ambient temperature derating is applied. No grouping factor for other circuits in the same enclosure, no thermal insulation factor, no burial depth or soil resistivity, no installation method column. The polyvinyl chloride 75 degree form is used regardless of whether the cable is actually cross linked polyethylene.
  • Voltage drop uses resistance only. No reactance and no power factor, at an assumed conductor temperature of 75 degrees Celsius.
  • The three phase voltage drop multiplier is 1, not the square root of 3. The percentage is also taken against the 400 volt line voltage. The conventional form is the square root of 3 times current times resistance times length, so three phase drop reported here is roughly 1.7 times optimistic. Re check any three phase run in the voltage drop or cable sizing calculator before you commit to a size.
  • Aluminium resistance is scaled the wrong way. The same 0.78 factor is applied to both the rating and the resistance, so aluminium voltage drop comes out lower than copper when it should be roughly 1.6 times higher. Do not size an aluminium run from this tool without checking the resistance against manufacturer data.
  • The residual current device rule is deliberately simple. Type B for a direct current fast charger or any three phase supply, Type A otherwise. That is a rule of thumb in code, not a reading of AS/NZS 3000 Appendix P, which is informative in Australia, or of the normative New Zealand Clause 7.9. Many chargers include their own direct current fault detection which changes the answer. Read the standard and the equipment datasheet.

What it does not do

  • It does not check that the breaker is at or below the cable capacity, does not select a tripping curve, and does not do discrimination with upstream devices.
  • It does not calculate earth fault loop impedance or maximum disconnection time, and it does not size the protective earthing conductor.
  • It does not do a maximum demand calculation, so it will not tell you whether the mains, main switch or supply can carry the extra load. That is often the real constraint on an older home.
  • It does not cover load management or dynamic current limiting, multiple chargers on a shared supply, isolation and switching arrangements, ingress protection, mechanical protection, or the socket outlet arrangements used for Mode 2 charging.
  • It does not produce a certificate of compliance or anything a distributor will accept as an application.

Check every result against the current editions of AS/NZS 3000, AS/NZS 3001.1 and AS/NZS 3008.1.1, and have the design signed off by the person responsible for the installation. Nothing here is validated or certified, and the underlying figures have not been reviewed by a chartered professional engineer.

Worked examples

Three complete runs with every intermediate figure shown, so you can check the tool against your own arithmetic.

Example 1. 7.4 kilowatt single phase wall charger, 30 metres

A Mode 3 wall unit in an attached garage, 30 metres of copper from the switchboard, clipped direct, 40 degrees Celsius ambient, the full 5 percent voltage drop budget available.

Charger rating, phase7.4 kW, single phase 230 V
Cable length, material30 m, copper
Ambient temperature40 °C
Maximum voltage drop5 %

Working

  1. Design current: 7,400 / (230 x 1) = 32.2 A.
  2. Breaker: next standard size at or above 32.2 A is 40 A.
  3. Temperature factor: square root of (75 - 40) / (75 - 40) = 1.000.
  4. Try 1.5 mm² at 17 A, 2.5 mm² at 23 A and 4 mm² at 31 A. All are below 32.2 A, so all are rejected on current.
  5. Try 6 mm²: 40 A x 1.000 = 40 A, which is at or above 32.2 A.
  6. Voltage drop on 6 mm², resistance 3.69 milliohms per metre, multiplier 2: 32.2 x 3.69 x 30 x 2 / 1,000 = 7.13 V.
  7. As a percentage: 7.13 / 230 = 3.1 percent, within the 5 percent limit, so 6 mm² is selected.

Result. 6 square millimetre copper, 40 ampere breaker, Type A residual current device, dedicated circuit required. Current capacity, voltage drop and the dedicated circuit checks all pass. Worth noting: the 40 ampere breaker sits on a cable rated at exactly 40 amperes, with no margin, and the engine does not check that relationship. Most installers would fit a 32 ampere device for a 32 ampere charger, which also gives the cable some headroom.

Example 2. 22 kilowatt three phase charger, 35 metres

A workplace charger on a three phase supply, 35 metres of copper from the distribution board, 40 degrees Celsius ambient.

Charger rating, phase22 kW, three phase 400 V
Cable length, material35 m, copper
Ambient temperature40 °C
Maximum voltage drop5 %

Working

  1. Design current: 22,000 / (400 x 1.732) = 31.8 A.
  2. Breaker: next standard size at or above 31.8 A is 32 A.
  3. Temperature factor 1.000. First size with a rating at or above 31.8 A is 6 mm² at 40 A.
  4. Voltage drop, three phase multiplier 1: 31.8 x 3.69 x 35 x 1 / 1,000 = 4.11 V.
  5. As a percentage against 400 V: 4.11 / 400 = 1.0 percent.

Result. 6 square millimetre copper, 32 ampere breaker, Type B residual current device because the supply is three phase, dedicated circuit required. All checks pass. Apply the caveat from the limits: with the conventional square root of 3 factor the drop would be about 7.11 volts, or 1.8 percent rather than 1.0 percent. Still comfortably inside the limit here, but on a longer run that difference decides the cable size.

Example 3. Same charger, 60 metre run through a hot roof space

The same 7.4 kilowatt single phase charger, but in a detached garage 60 metres away with the cable run through a roof space at 45 degrees Celsius. This is the case where voltage drop, not current, decides the answer.

Charger rating, phase7.4 kW, single phase 230 V
Cable length, material60 m, copper
Ambient temperature45 °C
Maximum voltage drop5 %

Working

  1. Design current 32.2 A, breaker 40 A, as before.
  2. Temperature factor: square root of (75 - 45) / (75 - 40) = 0.926.
  3. 6 mm²: 40 x 0.926 = 37.0 A, which clears 32.2 A on current.
  4. But its voltage drop is 32.2 x 3.69 x 60 x 2 / 1,000 = 14.26 V, or 6.2 percent, over the 5 percent limit, so 6 mm² is rejected.
  5. 10 mm²: 54 x 0.926 = 50.0 A on current, and 32.2 x 2.19 x 60 x 2 / 1,000 = 8.46 V, or 3.7 percent.

Result. 10 square millimetre copper, 40 ampere breaker, Type A residual current device. All checks pass at 10 square millimetres. Doubling the run length from 30 to 60 metres, plus 5 degrees of extra ambient, is enough to move the answer up a size, and it is the voltage drop that does it, not the current.

Common questions

What cable size do I need for a 32 A EV charger?+

A 32 A single-phase EV charger typically requires a minimum 6 mm squared copper cable for runs up to about 25 metres. For longer runs, voltage drop may require 10 mm squared. The Cable Sizing Calculator checks current carrying capacity, voltage drop, and earth fault loop impedance for the specific installation.

What RCD type is required for an EV charger?+

It depends on the country. In Australia, AS/NZS 3000:2018 covers EV charging in Appendix P, which is informative guidance rather than a normative requirement. Appendix P4.1 recommends each connecting point be protected by its own RCD of at least Type A with a rated residual operating current not exceeding 30 mA. Where the charging station uses a socket outlet or vehicle connector to the IEC 62196 series, protection against DC fault current should also be provided, either a Type B RCD, or a Type A RCD plus equipment that disconnects the supply on DC fault current above 6 mA, unless the charging station already provides it. In New Zealand, Clause 7.9 is normative. Clause 7.9.4 requires that all supplies for charging electric vehicles in non-residential installations be protected by a Type B RCD complying with IEC/TR 62432, and it does not attach a milliamp figure to that requirement. Check Clause 7.9.3 for the mode-specific requirements and the current amendment before relying on a Type A RCD alone. This calculator installations. Check the manufacturer datasheet and the current amendment of the Standard before selecting the device.

Can I install an EV charger on an existing circuit?+

No. EV chargers are classified as continuous loads (100 percent demand factor) and must be on a dedicated circuit with its own protective device. The circuit must not be shared with other loads. The main switch and supply cable must also be checked for the additional maximum demand.

What is the difference between Mode 2 and Mode 3 EV charging?+

Mode 2 uses a portable cable with an inline control box plugged into a standardised socket outlet. AS/NZS 3000 Appendix P defines Mode 2 as using socket outlets not exceeding 32 A, and allows connecting point socket outlets rated up to 20 A complying with AS/NZS 3112, AS/NZS 3123 or IEC 60309. Most portable units sold in Australia come with a 10 A plug for a standard socket outlet, but 15 A and 20 A arrangements are also Mode 2. Mode 3 uses a dedicated wall-mounted charging station (up to 32 A single-phase or 22 kW three-phase) with a permanent cable connection. Mode 3 is faster and safer for daily use.

How does an EV charger affect maximum demand?+

An EV charger is treated as a continuous load at 100 percent demand factor. A 32 A single-phase charger adds 7.4 kW to the maximum demand. This may require upgrading the main switch or supply cable, especially in older homes with 63 A or 80 A mains.

SparkyToolkit · iOS

On site? Get the same calcs on your phone.

SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.

Download on theApp Store

Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.

Related calculators