Cable Sizing Calculator
Free Australian cable sizing calculator covering current rating, voltage drop, and earth fault loop impedance per AS/NZS 3008.1.1:2025. Mobile-first, no login.
Inputs
▶Advanced options
AS/NZS 3000:2018 default limit is 5%
Results
Recommended Cable Size
2.5
mm² copper
Earth: 2.5 mm²
Current Carrying Capacity
23 A (>= 20 A)
Voltage Drop
4.6 % (<= 5 %)
Protection Device ≤ Cable Capacity
20 A (<= 23 A)
Cable Sizing Guide
Cable sizing in Australia is governed by AS/NZS 3008.1.1:2025 (Australian conditions) and AS/NZS 3000:2018 (Wiring Rules). The 4th edition was published in December 2025 and introduces updated current rating tables, revised derating factors, and expanded coverage for modern installation methods including solar PV DC circuits.
The three checks every cable must pass
- 1
Current carrying capacity : The cable must carry the full load current continuously without exceeding its rated temperature.
- 2
Voltage drop : Voltage drop from source to load must not exceed 5% of the nominal supply voltage (AS/NZS 3000 Clause 3.6).
- 3
Earth fault loop impedance : Total earth fault loop impedance must be low enough that the protection device disconnects within the required time.
On site? Get the same calcs on your phone.
SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.
Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.
Related calculators