Cable Sizing Calculator
Free Australian cable sizing calculator covering current rating, voltage drop, and earth fault loop impedance per AS/NZS 3008.1.1:2025. Mobile-first, no login.
Inputs
Converts kW or hp to amps. When given, voltage drop uses R cosφ + X sinφ instead of the worst-case impedance.
Conductor
Cable Type
Auto picks the smallest passing size and starts the earth at AS/NZS 3000 Table 5.1. Earth cables default to the parallel count.
▶Advanced options
AS/NZS 3000:2018 default limit is 5%
Arrangement
Resistance comes from AS/NZS 3008.1.1 Table 34 or 35 at the next tabulated temperature above the operating temperature, or at the insulation's maximum. Auto formation is flat touching in conduit and trefoil otherwise.
Adds an earth fault-loop max-length check
I²t = (fault current)² x clearing time, for the active and the earth.
Both > 0 adds a short-circuit withstand check
Results
Recommended Cable Size
2.5
mm² copper
Earth: 2.5 mm² (Table 5.1 minimum 2.5 mm²)
Current Carrying Capacity
23 A (>= 20 A)
Voltage Drop
4.7 % (<= 5 %)
Protection Device ≤ Cable Capacity
20 A (<= 23 A)
Show the working
| Step | Working | Result | Reference |
|---|---|---|---|
| Design current (Ib) | Ib = 20 A, single phase AC at 230 V, run 30 m, 1 cable(s) per phase, copper PVC (V-75) | 20 A | Input |
| Installation method factor | Table lookup: clipped direct to surface = 1.00 x the clipped-direct rating column | 1.00 | Rating column by installation method (indicative) |
| Ambient derating (air ref 40°C) | sqrt((75 - 40) / (75 - 40)) = 1.000 | 1.000 | AS/NZS 3008.1.1:2025 temperature derating |
| Grouping derating (touching) | Table lookup: 1 circuit(s), touching = 1.000 | 1.000 | AS/NZS 3008.1.1:2025 grouping table |
| Combined derating factor | 1.000 temp x 1.000 grouping = 1.000 | 1.000 | product of derating factors |
| Base current rating, 2.5mm² | Table lookup: 2.5 mm2 copper clipped direct = 23 A x 1.00 install x 1 parallel = 23.0 A | 23 A | AS/NZS 3008.1.1:2025 Table 3.18 (indicative) |
| Derated current capacity (Iz) | 23.0 A x 1.000 = 23 A vs Ib 20 A | 23 A | Iz = Itable × install × derating × parallel |
| Operating temperature (θ₀) | (20 / 23)^2 x (75 - 40) + 40 = 66.5 C (capped at 75 C; Iz is the derated capacity, as Cl 4.4 corrects the rated current by the rating factors) | 66.5 °C | AS/NZS 3008.1.1 Cl 4.4: θ₀ = (Ib/Iz)²·(θr−θa) + θa |
| Conductor resistance (75 C column) | θ₀ 66.5 C raised to the next tabulated temperature, 75 C; Rc from Table 35 (multicore), copper, 75 C column (column 4): 2.5 mm2 = 9.01 ohm/km | 9.0100 Ω/km | AS/NZS 3008.1.1:2009 Table 35, same values as 2017 |
| Conductor reactance (multi-core) | Xc from Table 30, multicore circular conductors, PVC (column 9): 2.5 mm2 = 0.102 ohm/km | 0.1020 Ω/km | AS/NZS 3008.1.1:2009 Table 30, same values as 2017 |
| Impedance (Z = √(R²+X²)) | sqrt(9.0100^2 + 0.1020^2) = 9.0106 ohm/km | 9.0106 Ω/km | Z = √(R² + X²) |
| Voltage drop (ΔV) | 2 x 20 A x 9.0106 ohm/km x 30 m / (1000 x 1) = 10.81 V | 10.81 V | ΔV = 2·Ib·Z·L/(1000·m) |
| Voltage drop percentage | 10.81 V / 230 V x 100 = 4.7% (limit 5%) | 4.7 % | AS/NZS 3000:2018 Cl. 3.6 (limit 5%) |
| Short-circuit withstand (K²S²) | (111.2 x 2.5)^2 = 7.73e+4 A2s (no prospective fault current given, so no let-through comparison) | 7.73e+4 A²s | K = 111.2 (AS/NZS 3008.1.1 Table 5.1) |
| Minimum earth size (Table 5.1) | Table lookup: 2.5 mm2 copper active gives 2.5 mm2 earth | 2.5 mm² | AS/NZS 3000:2018 Table 5.1 |
| Earth size (multi-core, fixed by the cable) | The earth core of a multi-core cable is fixed by its construction, so the earth is the Table 5.1 size of 2.5 mm2; no earth check is enabled | 2.5 mm² | Multi-core rule: earth core per Table 5.1; a failing earth check steps the active size up |
Standards referenced
- AS/NZS 3008.1.1:2025 Clause 4. Current-carrying capacity of cables, Australian conditions
- AS/NZS 3008.1.1:2025 Clause 5. Short-circuit temperature limits and adiabatic factor K
- AS/NZS 3008.1.1:2009 Table 35. a.c. resistance Rc, multicore cables, same values as 2017 (2025 Table 4.7(A))
- AS/NZS 3008.1.1:2009 Table 30. Reactance Xc at 50 Hz, same values as 2017 (2025 Table 4.1(B))
- AS/NZS 3000:2018 Clause 3.6. Voltage drop in consumer mains and sub-mains
- AS/NZS 3000:2018 Clause 8.3. Earth fault-loop impedance and automatic disconnection
- AS/NZS 3000:2018 Table 5.1. Minimum cross-sectional area of protective earthing conductors
Where a lookup value is marked indicative, it has not been transcribed from the current edition of the standard. Check results against your own copy before relying on them for design.
Parameters
This calculator exposes more inputs than most, because it runs up to six separate checks and each one needs its own information. Every field is documented below with the range the form accepts and the factor it actually applies inside the calculation.
Circuit
- Phase configurationsingle phase, three phase, or DC
- Sets the voltage drop multiplier and the phase voltage used by the earth fault loop check. Three phase uses 1.732, the square root of 3, and a phase voltage of the nominal divided by 1.732. Single phase and DC use a factor of 2 and the nominal voltage itself. Selecting DC also drops reactance from the calculation entirely and disables the loop check. Changing this selector resets the nominal voltage.
- Nominal voltagevolts
- Set by the phase selector: 230 volts single phase, 400 volts line to line three phase. The voltage drop percentage is measured against this figure.
- Loadamps, kilowatts, kilovolt-amps or horsepower
- The load the circuit actually carries, not the protective device rating. In amps it is used directly as the design current, normally written as Ib. In kilowatts it is converted with I = P / (1.732 x V x pf) for three phase, or P / (V x pf) for single phase and DC, where DC always uses a power factor of 1. Kilovolt-amps leave the power factor out. Horsepower is converted at 746 watts per horsepower and then treated as kilowatts. The converted current is shown as its own step in the working and drives the current capacity check, the voltage drop and the operating temperature estimate.
- Load power factor0.1 to 1, blank by default, AC only
- Required when the load is entered in kilowatts or horsepower, because the conversion to amps needs it. Whenever it is given, voltage drop is calculated as resistance times cosine phi plus reactance times sine phi. Left blank, voltage drop falls back to the worst-case impedance magnitude, the square root of resistance squared plus reactance squared, which is conservative and reads slightly higher.
- Cable run lengthmetres, 1 to 2000
- The one-way route length. Do not double it for the return conductor; the phase multiplier already accounts for the return path. The same figure is compared against the maximum earth fault loop length when the loop check is enabled.
- Protection device ratingamps, 1 to 800
- The rating of the upstream circuit breaker or fuse, normally written as In. It is checked against the derated cable capacity so the cable is never protected by a device larger than it can carry, and when a device curve is selected it also sets the instantaneous trip current used by the loop check.
Cable construction and installation
- Installation methodeight options
- Applies a rating multiplier relative to clipped direct: free air spaced 1.18, perforated tray 1.10, free air touching 1.08, solid tray 1.00, clipped direct 1.00, enclosed in conduit in air 0.95, direct buried 0.92, and enclosed in conduit buried 0.88. Choosing either buried option also switches the whole derating calculation to the underground branch, which uses a 25 degree Celsius soil reference instead of a 40 degree Celsius air reference and reveals the burial depth and soil resistivity fields. Choosing either conduit option also recommends the smallest rigid PVC conduit for the cables, using the same fill method as the conduit fill calculator, and adds a conduit fill check.
- Conductor materialcopper or aluminium
- Aluminium multiplies the base current rating by 0.78 and reads its resistance from the aluminium columns of AS/NZS 3008.1.1 Table 35, or Table 34 for single-core, which run about 1.66 times copper. The tables list aluminium from 16 square millimetres; below that the resistance is scaled from copper and the result carries a warning. Both effects push the selected size upward, so an aluminium run typically lands one to two standard sizes above the copper equivalent.
- InsulationPVC 75, XLPE 90 or EPR 90
- Sets the rated conductor temperature, 75 degrees Celsius for PVC and 90 for XLPE and EPR. That temperature feeds the ambient derating formula and the operating temperature estimate, and caps the resistance column. It picks the reactance column in Table 30, PVC, XLPE or elastomer for EPR. It also selects the adiabatic constant used by the short-circuit check: 111.2 for copper with PVC, 143 for copper at 90 degrees, 73.6 for aluminium with PVC and 94 for aluminium at 90 degrees.
- Cable typemulti-core or single-core
- Single-core cables sit further apart than the cores of a multi-core cable, which raises inductive reactance. Multi-core reads resistance from AS/NZS 3008.1.1 Table 35 and reactance from the multicore columns of Table 30. Single-core reads Table 34 and the single-core columns of Table 30, trefoil or flat touching. Flat touching is assumed in conduit, as the Table 30 note allows, and trefoil otherwise; the Single-core Formation option overrides it. It also changes what goes into the conduit when a conduit method is chosen: one sheathed cable per parallel set for multi-core, or separate cores for single-core. On small conductors where reactance is negligible the two options give nearly identical sizes.
- Parallel cables per phasecount, 1 to 10
- The number of cables running in parallel for each phase. The rating is multiplied by the count and the voltage drop is divided by it. Selecting more than one also forces a minimum conductor size of 4 square millimetres per cable, because very small conductors in parallel do not share current reliably.
Manual sizes
- Active sizeAuto, or 1.5 to 300 square millimetres
- Auto returns the smallest standard size that passes every enabled check. Choosing a size evaluates that size instead: every check is reported as pass or fail at that size, and if any fails a warning names the failed checks and the size Auto would have picked.
- Earth sizeAuto, or 1.5 to 300 square millimetres per earth cable
- Auto uses the AS/NZS 3000:2018 Table 5.1 minimum for the active size. The earth checks are the earth short-circuit withstand, when a fault current and clearing time are entered, and the earth fault loop length, when a device curve is selected. What happens when one fails depends on the cable type. A multi-core cable's earth core is fixed by its construction, so the active size steps up instead, bringing the next cable's Table 5.1 earth with it. Single-core installations run the earth as a separate cable, so the earth steps up one standard size at a time while a check fails, never past the active size. Choosing a size uses it as given, adds a check that it meets the Table 5.1 minimum, and warns when it does not. On a multi-core cable a chosen earth is treated as a separate earth conductor run with the cable.
- Earth cablescount, 1 to 10, defaults to the parallel cable count
- The number of earth conductors in parallel. The Table 5.1 earth for the total active area is shared across them and rounded up to a standard size, and the earth impedance in the loop check is divided by this count. With two parallel 50 square millimetre actives, the total of 100 takes the 120 row and a 35 square millimetre earth, so one earth cable gives 35 and two give 17.5 each, rounded up to 25. No earth cable is allowed below the Table 5.1 earth for one of the actives on its own, so two parallel 240 square millimetre actives (480 in total, the 500 row, a 120 earth) with two earth cables need 95 each, not 60 rounded up to 70.
Derating
- Maximum voltage droppercent, 1 to 10, default 5
- The compliance target for the voltage drop check. AS/NZS 3000:2018 Clause 3.6 uses 5 percent across the whole installation, so tighten this when the run being sized is only one part of the chain.
- Ambient temperaturedegrees Celsius, 10 to 75
- Air temperature for in-air installation methods, soil temperature for buried ones. The factor is the square root of the rated temperature minus the ambient, divided by the rated temperature minus the reference. The reference is 40 degrees in air and 25 degrees in soil. At the reference temperature the factor is exactly 1, so a PVC cable in 40 degree air gets no ambient penalty at all. Entering an ambient above the rated conductor temperature drives the factor to zero and no size will pass.
- Number of circuits in groupcount, 1 to 20
- How many loaded circuits share the same enclosure, tray or trench. The factor steps down: 1 gives 1.00, 2 gives 0.80, 3 gives 0.70, 4 to 6 gives 0.57, 7 to 9 gives 0.50, and 10 or more gives 0.44. This is often the largest single penalty in the whole calculation, so count the circuits honestly.
- Arrangementtouching or spaced
- Spaced cables shed heat better and recover 30 percent of the grouping penalty. With three circuits, touching gives 0.70 and spaced gives 0.79. It has no effect at all when the grouping count is 1, since there is no penalty to recover.
- Burial depthmetres, 0.3 to 3, buried methods only
- The factor is 1.00 at the 0.5 metre reference and falls by 0.06 for every metre deeper, with a floor of 0.85. Shallower than 0.5 metres gives no bonus. Deeper soil dissipates heat more slowly, which is why the penalty exists.
- Soil thermal resistivitykelvin metres per watt, 0.5 to 3, buried methods only
- The factor is 1.00 at the 1.2 reference and changes by 0.1 per unit either side, clamped between 0.7 and 1.2. Wet clay conducts heat away well and sits low; dry sand sits high and penalises the cable. If you have no soil thermal test, 1.2 is the usual default.
Optional deeper checks
- Protective device curveblank, B, C or D
- Leaving it blank disables the earth fault loop check entirely. Selecting a curve enables it and sets the instantaneous trip current as a multiple of the device rating: B is 4 times, C is 7.5 times and D is 12.5 times. The loop check is skipped on DC and skipped if the device rating is zero.
- Loop methodestimate, calculate or measured
- Estimate assumes 80 percent of the source voltage is available to drive the fault and needs no extra input. Calculate derives the source impedance from a prospective earth fault current you supply. Measured uses a loop impedance you have actually tested at the board. Estimate is the right default when you have nothing measured.
- Prospective earth fault currentkiloamps, 0 to 100, calculate method only
- The fault current available at the origin of the circuit. Used only when the loop method is set to calculate. Leave at zero if you are not using that method.
- Measured loop impedanceohms, 0 to 10, measured method only
- The loop impedance measured at the origin of the circuit with a loop tester. Used only when the loop method is set to measured.
- Prospective fault currentkiloamps, 0 to 100
- The prospective short-circuit current at the cable. This field and the clearing time below must both be greater than zero for the short-circuit withstand checks to run, one on the active and one on the earth. A failing earth check steps the active up on multi-core cable and the earth up on single-core. Leave both at zero to skip them.
- Fault clearing timeseconds, 0 to 5, clearing time method only
- How long the protective device takes to clear that short circuit. Together with the fault current it gives the let-through energy the conductor has to survive.
- Short-circuit let-throughclearing time, MCB class 3 or custom
- Where the let-through energy, I squared t, comes from. Clearing time, the default, multiplies the fault current squared by the clearing time and takes no credit for current limiting. MCB class 3 uses the maximum I squared t that EN 60898-1:2019 Annex ZA (Tables ZA.1 and ZA.2) permits an energy limiting class 3 MCB at its rated breaking capacity, the worst case for that breaker, so no clearing time is needed. Custom takes the figure you read off the device maker's let-through curve at your prospective fault current. With either device option the phase fault figure is checked against the active and the earth fault figure against the earth, and the active has to survive the larger of the two, as AS/NZS 3000:2018 Clause 2.5.4.2 Note 2 asks for current limiting devices. All device figures are indicative manufacturer data.
- MCB curve and breaking capacitytype B or C; 3, 4.5, 6 or 10 kA; class 3 only
- The curve and the rated short-circuit capacity printed on the breaker select the row and table. The rating column comes from the protection device rating: up to 16 A, 20 to 32 A, 40 A, or 50 to 63 A, with a rating between columns taking the next column up. Type D, ratings above 63 A and 15 kA breakers are outside the tables, so use Custom for them. When a fault current is entered it is also checked against the breaking capacity, per AS/NZS 3000:2018 Clause 2.5.4.2(a).
- Custom device and I squared tMCB, MCCB or generic; A²s
- The device type labels the working. Enter the phase fault let-through and, if it differs, the earth fault let-through, both read from the manufacturer's curve at the prospective phase and earth fault currents. A blank earth figure uses the phase figure. For NHP TemBreak PRO MCCBs the curves are in Annex C of the user manuals; for Schneider Acti 9 MCBs they are in document CA908025E, Short-circuit current limiting.
Assumptions and limits
The selection method here follows the structure of a real AS/NZS 3008.1.1 cable calculation: derate the rating, check voltage drop, check the loop, check short-circuit withstand, and take the smallest size that survives all of it. The method is complete. The numbers behind it are not yet authoritative, and that distinction matters.
What the calculator assumes
- Resistance and reactance are the standard's values; the ratings are not. Conductor resistance and reactance are transcribed from AS/NZS 3008.1.1:2009 Tables 34, 35 and 30, the same values as the 2017 edition, and locked by regression tests. The 2025 edition renumbers them as Tables 4.5(A), 4.7(A) and 4.1. The base current ratings, the installation method factors, the grouping, depth and soil resistivity factors, and the adiabatic constants are still indicative working figures, not taken from a licensed copy of the 2025 edition, so check them against your copy before relying on a result. Expect the selected size to be broadly sensible and the individual amperages to differ from the standard.
- One rating table for every construction. The standard selects a different rating column for each installation method and cable construction. This calculator starts from a single base table and applies the installation method as a flat multiplier instead. That is a structural simplification, not just a data one.
- Resistance follows the operating temperature. Clause 4.4 estimates the conductor temperature from the load current, the derated capacity, the rated temperature and the ambient, then raises it to the next tabulated column, 45, 60, 75, 90 or 110 degrees Celsius. A lightly loaded cable therefore reads a lower resistance than one near its rating. Choose Maximum rated temperature to read the insulation's rated column instead. The earth conductor is read from the same column as the actives.
- Aluminium current rating is a flat 0.78 of copper (indicative). Aluminium resistance is read from Tables 34 and 35, which list it from 16 square millimetres. Below 16 square millimetres the copper value is scaled by the table's aluminium to copper ratio at 16 square millimetres and a warning says so.
- Voltage drop uses worst-case impedance unless a power factor is entered. Entering a load power factor, which kilowatt and horsepower loads require, switches to resistance times cosine phi plus reactance times sine phi. There is no separate worst-case option once a power factor is given.
- Load conversion uses line current only. Kilowatts and horsepower assume the entered figure is electrical input power. A motor nameplate in kilowatts is shaft output, so divide by the efficiency first or enter the nameplate full load current in amps.
- The neutral is reported as the same size as the active. There is no reduced-neutral logic and no allowance for triplen harmonic current in the neutral of a three phase circuit feeding non-linear loads, which in a heavily loaded office or data installation can exceed the phase current.
- The minimum earth is the copper column of AS/NZS 3000:2018 Table 5.1, transcribed from the standard and locked by regression tests, so a 16 square millimetre active gets a 6 square millimetre earth. Three parts of the earth sizing are indicative. Aluminium cables have an aluminium earth: the copper earth from the aluminium active column of Table 5.1, converted to the smallest aluminium conductor with a lower impedance and a higher fault rating, the sizes jCalc publishes (16 for 16 to 35, 25 for 50 and 70, up to 240 for 630, and 40 percent above that). Parallel cables look up the total active area, taking the next row up when it falls between rows, as Clause 5.3.3.1.2 requires. The standard is silent on splitting that earth across parallel earth cables, so the calculator shares it across them but keeps each one at or above the Table 5.1 earth for a single active. Rows 400, 500 and 630 give 120 square millimetres and above 630 the earth is 25 percent of the active area, both straight from the table. An earth above 300 square millimetres per cable is flagged, since 300 is the largest cable modelled.
- Multi-core earth cores are assumed to be the Table 5.1 size. Real cables follow it closely, but check the manufacturer's construction. When an earth check fails on multi-core cable, the active steps up, which can oversize the actives considerably; entering a separate earth conductor in the Earth size field is often the cheaper fix. For single-core, the separate earth is stepped up instead and never past the active size; if it still fails there, that active size fails and the next one is tried.
- With the clearing time method, the earth short-circuit check uses the same prospective fault current and clearing time as the active check, and the same adiabatic constant. A real earth fault current is usually lower than the phase fault current, so this is conservative. With custom let-through you can enter a separate earth fault figure.
- The conduit size comes from AS/NZS 3000:2018 Tables C10 to C12, as jCalc does, for the conduit type you pick (heavy duty rigid UPVC by default). Every cable of the circuit goes in one conduit, with a neutral the same size as the active for single-core three phase and two phase circuits. Single-core cables use Table C10; when the earth is smaller than the actives the tables do not cover the mix, so every cable is counted at the larger size, which is conservative. Multi-core single phase and DC cables use Table C11 (two-core and earth) and three phase uses Table C12 (four-core and earth); two phase three-core and earth is not tabulated, so the Table C12 count is used as the conservative choice. Where the tables print both PVC and XLPE rows, the PVC row is used. Outside the tables (for example two-core and earth above 25 square millimetres, or metallic conduit) the calculator falls back to the indicative space factor on indicative diameters, which are only tabulated to 50 square millimetres for multi-core, so above that no conduit is recommended and a warning says so. The tables assume a short run with bends minimised.
- The loop check uses the instantaneous trip band midpoint, 4, 7.5 or 12.5 times the device rating, and for the estimate method an 80 percent source voltage allowance. It does not use the maximum Zs values in AS/NZS 3000 Table 8.1, it does not model fuse time-current curves, and it takes no account of RCD protection, which changes the disconnection argument entirely.
- The short-circuit check compares the adiabatic constant squared times area squared against the let-through energy. By default that is current squared times time: the full prospective current flowing for the whole clearing time, with no credit for current limiting by the protective device, which for a modern current-limiting breaker is a significant conservatism. Choose MCB class 3 or Custom to use the device's let-through instead, as jCalc does.
- Device let-through figures are indicative manufacturer data, not values from AS/NZS 3008 or AS/NZS 3000. The MCB class 3 option uses the ceiling EN 60898-1:2019 Annex ZA allows, read at the breaker's breaking capacity whatever the actual fault level, which is the worst case for any class 3 breaker of that rating. Real current limiting MCBs usually let through much less, so a size that fails only on the class 3 figure may pass on the actual device's curve. jCalc uses typical Schneider iC60 and C120 values here; we could not obtain those curves as published numbers, so we use the product standard ceiling instead, which is more conservative. Confirm the breaker is marked class 3 (the 3 in a square on its front), that the class tables cover it, and check the result against the actual device's let-through curve. AS/NZS 60898.1 has not been checked for the same annex. No MCCB or fuse let-through values are built in, because no published tables could be found; enter them from the manufacturer's curves with Custom.
- Voltage drop percent is rounded to one decimal before it is compared, so a true 5.04 percent displays as 5.0 percent and reads as a pass. Treat anything within a tenth of a percent of the limit as needing a second look.
- Selection returns the smallest standard size that satisfies every enabled check, unless an active size is chosen by hand. If no size satisfies them all, the largest size is shown along with a warning that there is no solution. The per-size selection table marks the earth, current rating, voltage drop, fault and loop result separately for every size, so you can see exactly which check each size failed on.
What this should not be used for
- The design of record for any installation. Verify the selected size against the current edition of AS/NZS 3008.1.1 using licensed tables before it goes on a drawing.
- High voltage cable, which is covered by AS/NZS 3008.1.1 Part 2 and its own rating and screening rules.
- Solar photovoltaic DC string circuits, where voltage rise rather than drop governs. Use the voltage rise calculator.
- Busbar, busway or bare conductor systems, which are not cables and do not use these rating tables.
- Fire-rated, mineral-insulated or circuit-integrity cable, which carries its own manufacturer ratings and its own installation rules.
- Hazardous area installations, which add AS/NZS 60079 requirements on top of everything here.
- Any circuit protected by an RCD where you are relying on the loop check for disconnection, since RCD operation is not modelled.
Results should be checked against the current edition of AS/NZS 3008.1.1 and AS/NZS 3000, and the final design signed off by the responsible person for the installation. Nothing on this page is a certification.
Worked examples
Four complete selections showing every factor applied in order, covering single phase copper, three phase aluminium buried with full derating, a case where the short-circuit check on the earth core rather than current rating decides the answer, and a kilowatt load where the earth fault loop check sets the size.
Example 1: single phase 20 amp final subcircuit, clipped direct
A 230 volt single phase circuit drawing 20 amps runs 30 metres, clipped direct, in copper with PVC insulation, on its own with no grouping and 40 degree ambient. Protected by a 20 amp device.
| Phase configuration | Single phase, 230 V |
|---|---|
| Load current | 20 A |
| Run length | 30 m |
| Protection device rating | 20 A |
| Installation method | Clipped direct |
| Conductor / insulation | Copper, PVC 75 °C |
| Cable type | Multi-core |
| Ambient temperature | 40 °C |
| Circuits in group | 1 |
| Maximum voltage drop | 5 % |
Step 1, derating. Ambient is at the 40 degree reference, so the temperature factor is 1.000. Grouping of one gives 1.000. Clipped direct gives an installation factor of 1.00. The combined derating factor is 1.000, which is the easy case.
Step 2, current capacity. A 1.5 square millimetre conductor rates 17 amps, which is below the 20 amp design current, so it fails. A 2.5 square millimetre conductor rates 23 amps, which passes.
Step 3, operating temperature. 20 divided by 23, squared, times the 35 degree rise from 40 to 75, plus 40, gives 66.5 degrees Celsius. The next tabulated temperature up is 75 degrees, so resistance is read from the 75 degree column.
Step 4, voltage drop at 2.5 square millimetres. Table 35 gives 9.01 ohms per kilometre at 75 degrees, and Table 30 gives a multicore PVC reactance of 0.102. The impedance is the square root of 9.01 squared plus 0.102 squared, which is 9.0106. Drop equals 2 times 20 times 9.0106 times 30, divided by 1000, which is 10.81 volts, or 4.7 percent of 230.
Step 5, protection check. The 20 amp device is less than the 23 amp derated capacity, so it passes.
PASS at 2.5 square millimetres, with a 2.5 square millimetre earth, which is the Table 5.1 row for a 2.5 square millimetre copper active. Current capacity 23 amps against 20 amps, voltage drop 4.7 percent against 5 percent. Note how tight the voltage drop is: this circuit has almost no headroom left, and any extension of the run will push it over. Short-circuit withstand at this size is 77284 ampere-squared seconds, reported for reference since no fault current was entered.
Example 2: three phase aluminium submain, direct buried
A 400 volt three phase submain carries 100 amps over 60 metres, direct buried at 0.7 metres in soil of 1.5 kelvin metres per watt at 25 degrees Celsius, sharing the trench with one other circuit. Aluminium conductors with XLPE insulation, protected by a 100 amp device.
| Phase configuration | Three phase, 400 V |
|---|---|
| Load current | 100 A |
| Run length | 60 m |
| Protection device rating | 100 A |
| Installation method | Direct buried |
| Conductor / insulation | Aluminium, XLPE 90 °C |
| Cable type | Multi-core |
| Soil temperature | 25 °C |
| Circuits in group | 2, touching |
| Burial depth | 0.7 m |
| Soil thermal resistivity | 1.5 K·m/W |
| Maximum voltage drop | 5 % |
Step 1, derating. Soil at the 25 degree reference gives a temperature factor of 1.000. Two circuits touching gives 0.800. Burial at 0.7 metres is 0.2 metres past the reference, so 1 minus 0.2 times 0.06 gives 0.988. Soil resistivity of 1.5 is 0.3 above the reference, so 1 minus 0.3 times 0.1 gives 0.970. Multiplied together: 0.767.
Step 2, base rating. Direct buried applies a 0.92 installation factor and aluminium a 0.78 material factor. For a 70 square millimetre conductor the base table figure of 185 amps becomes 185 times 0.78 times 0.92, which is 132.8 amps.
Step 3, derated capacity. 132.8 times 0.767 equals 101.8 amps, which clears the 100 amp design current. The next size down, 50 square millimetres, gives only 79.8 amps and fails.
Step 4, operating temperature. Clause 4.4 uses the derated capacity, since the rating factors apply. 100 divided by 101.8, squared, times the 65 degree rise from 25 to 90, plus 25, gives 87.7 degrees Celsius. The cable runs close to its rating, so resistance is read from the 90 degree column.
Step 5, voltage drop at 70 square millimetres. Table 35 gives 70 square millimetre aluminium 0.569 ohms per kilometre at 90 degrees, and Table 30 gives a multicore XLPE reactance of 0.0741. The impedance is the square root of 0.569 squared plus 0.0741 squared, which is 0.5738. Drop equals 1.732 times 100 times 0.5738 times 60, divided by 1000, which is 5.96 volts, or 1.5 percent of 400.
Step 6, protection check. The 100 amp device is below the 101.8 amp capacity, so it passes, though only just.
Step 7, earth. The aluminium active column of Table 5.1 gives a 10 square millimetre copper earth for a 70 square millimetre aluminium active. The smallest aluminium earth with a lower impedance and a higher fault rating than 10 copper is 25 square millimetres, the size jCalc publishes (indicative, the standard prints copper earths only). No fault current or device curve was entered, so no earth check runs and the earth stays at that minimum.
PASS at 70 square millimetres, with a 25 square millimetre earth. This example shows the shape of a derated calculation clearly: the combined derating factor of 0.767 and the aluminium and burial factors together turn a nominal 185 amp conductor into a 101.8 amp one. Voltage drop at 1.5 percent is not remotely the binding constraint here. Current capacity is, and the margin over the 100 amp device is under 2 amps.
Example 3: when short-circuit withstand decides the size
A 230 volt single phase circuit drawing 32 amps runs 45 metres in conduit in air, multi-core copper with PVC insulation, protected by a 32 amp type C breaker. The board has a documented prospective fault level of 6 kiloamps and the device clears in 0.1 seconds. Both the earth fault loop check and the short-circuit check are enabled.
| Phase configuration | Single phase, 230 V |
|---|---|
| Load current | 32 A |
| Run length | 45 m |
| Protection device rating | 32 A |
| Installation method | Enclosed in conduit in air |
| Conductor / insulation | Copper, PVC 75 °C |
| Cable type | Multi-core |
| Ambient temperature | 40 °C |
| Circuits in group | 1 |
| Device curve | C |
| Loop method | Estimate |
| Prospective fault current | 6 kA |
| Fault clearing time | 0.1 s |
Step 1, derating. Ambient and grouping both give 1.000. Conduit in air applies a 0.95 installation factor.
Step 2, current capacity. A 4 square millimetre conductor gives 31 times 0.95, which is 29.5 amps and fails against 32 amps. A 6 square millimetre conductor gives 40 times 0.95, which is 38 amps and passes.
Step 3, voltage drop at 6 square millimetres. The operating temperature is 32 divided by 38, squared, times 35, plus 40, which is 64.8 degrees, so the 75 degree column applies. Table 35 gives 3.75 ohms per kilometre and Table 30 a reactance of 0.0967, an impedance of 3.7512. Drop equals 2 times 32 times 3.7512 times 45, divided by 1000, which is 10.80 volts, or 4.7 percent. Passes.
Step 4, short-circuit withstand at 6 square millimetres. Let-through energy is 6000 squared times 0.1, which is 3,600,000 ampere-squared seconds. The conductor withstand is the adiabatic constant of 111.2 times 6, squared, which is only 445,156. The active fails by a factor of eight, so 6 square millimetres fails whatever the earth does.
Step 5, active withstand. 10 square millimetres gives 111.2 times 10, squared, which is 1,236,544. 16 square millimetres gives 3,165,553, still short of 3,600,000. 25 square millimetres gives 111.2 times 25, squared, which is 7,728,400 and clears it.
Step 6, the earth core. This is multi-core cable, so the earth is the core built into it, sized by Table 5.1, and it has to survive the same let-through. A 25 square millimetre cable has a 6 square millimetre earth core, which withstands 445,156 and fails. The calculator cannot grow that core, so it steps the active up instead. 35 square millimetres brings a 10 square millimetre core at 1,236,544, which fails. 50 square millimetres brings a 16 square millimetre core at 3,165,553, which fails. 70 square millimetres brings a 25 square millimetre core at 7,728,400, which passes.
Step 7, rechecking 70 square millimetres. Capacity 185 times 0.95 equals 175.8 amps. The operating temperature is 32 divided by 175.8, squared, times 35, plus 40, which is 41.2 degrees Celsius, so resistance comes from the 45 degree column. Table 35 gives 0.295 ohms per kilometre and Table 30 a reactance of 0.077, an impedance of 0.3049, so the drop is 2 times 32 times 0.3049 times 45, divided by 1000, which is 0.88 volts or 0.4 percent. A type C breaker trips instantaneously at 7.5 times 32, which is 240 amps. The 25 square millimetre earth core, read from the same 45 degree column, is 0.799 ohms per kilometre with a reactance of 0.0853, an impedance of 0.8035, so the loop total is 1.1084 ohms per kilometre and the maximum length is 0.8 times 230 times 1000, divided by 240 times 1.1084, which is 691.7 metres against the 45 metre run.
Step 8, conduit. The method is in conduit, but AS/NZS 3000 Table C11 lists two-core and earth cables only up to 25 square millimetres, and the indicative multi-core diameters stop at 50 square millimetres, so no conduit size is recommended and a warning asks for the manufacturer's diameter.
PASS at 70 square millimetres, with its 25 square millimetre earth core. Current rating alone would have accepted 6 square millimetres, the active's own withstand 25 square millimetres, and it is the earth core that drags the cable up to 70. That is a big jump, and there are two cheaper ways out. Run single-core cable, where the earth is a separate conductor: the calculator then keeps a 25 square millimetre active, steps the earth from 6 to 25 square millimetres, reads Table 34 and the flat touching reactance for cables in conduit (0.799 and 0.121 ohms per kilometre at 45 degrees), gives a drop of 2.33 volts and a loop limit of 474.4 metres, and fits the two live cores and the earth in a 40 millimetre heavy duty rigid UPVC conduit (AS/NZS 3000 Table C10 allows three 25 square millimetre single-core cables at 40 millimetres and one at 32). Or keep multi-core and enter a separate 25 square millimetre earth in the Earth size field. Note also the conservatism: the check assumes the full 6 kiloamps flows for the whole 0.1 seconds, through the earth as well as the active, whereas a current-limiting breaker would cut it well short.
Example 4: a kilowatt load where the loop check sets the size
A 30 kilowatt three phase load at a power factor of 0.85 runs 80 metres from the board, clipped direct, in multi-core copper with PVC insulation, protected by a 50 amp type C breaker. The loop check is enabled with the estimate method; no fault current is entered.
| Phase configuration | Three phase, 400 V |
|---|---|
| Load | 30 kW |
| Load power factor | 0.85 |
| Run length | 80 m |
| Protection device rating | 50 A |
| Installation method | Clipped direct |
| Conductor / insulation | Copper, PVC 75 °C |
| Cable type | Multi-core |
| Ambient temperature | 40 °C |
| Circuits in group | 1 |
| Device curve | C |
| Loop method | Estimate |
Step 1, design current. I equals 30,000 watts divided by 1.732 times 400 times 0.85, which is 30,000 divided by 588.9, or 50.94 amps.
Step 2, current capacity. All derating factors are 1.000. A 6 square millimetre conductor rates 40 amps and fails. A 10 square millimetre conductor rates 54 amps and passes, and the 50 amp breaker sits under it.
Step 3, loop at 10 square millimetres. Table 5.1 gives a 10 square millimetre cable a 4 square millimetre earth core. The operating temperature is 50.94 divided by 54, squared, times 35, plus 40, which is 71.1 degrees, so the 75 degree column applies. The breaker trips at 7.5 times 50, which is 375 amps, and the phase voltage is 400 divided by 1.732, which is 230.9 volts. The active is 2.23 ohms per kilometre with a reactance of 0.0906, an impedance of 2.2318, and the earth core 5.61 with 0.102, an impedance of 5.6109, totalling 7.8428 ohms per kilometre. Maximum length is 0.8 times 230.9 times 1000, divided by 375 times 7.8428, which is 62.8 metres. The run is 80 metres, so it fails, and because the earth core is fixed the active steps up.
Step 4, operating temperature at 16 square millimetres. 50.94 divided by 73, squared, times the 35 degree rise from 40 to 75, plus 40, gives 57.0 degrees Celsius. The next tabulated temperature up is 60 degrees, so Table 35 gives 1.33 ohms per kilometre for the active and 3.56 for the 6 square millimetre earth core.
Step 5, loop at 16 square millimetres. With reactances of 0.0861 and 0.0967, the active impedance is 1.3328 and the earth core 3.5613, totalling 4.8941 ohms per kilometre, so the maximum length is 0.8 times 230.9 times 1000, divided by 375 times 4.8941, which is 100.7 metres. That covers the run.
Step 6, voltage drop with the power factor. The sine of the power factor angle is the square root of 1 minus 0.85 squared, which is 0.5268. Resistance 1.33 times 0.85 plus reactance 0.0861 times 0.5268 gives 1.1759 ohms per kilometre. Drop equals 1.732 times 50.94 times 1.1759 times 80, divided by 1000, which is 8.30 volts, or 2.1 percent of 400.
PASS at 16 square millimetres, with its 6 square millimetre earth core. Current rating wanted only 10; the earth fault loop moved it up a size. In single-core the 10 square millimetre active would stand, with its separate earth stepped from 4 to 6 square millimetres: Table 34 at 75 degrees and the trefoil reactance give a loop limit of 82.3 metres and a drop of 13.82 volts, 3.5 percent.
Example 5: MCB let-through decides the earth core
A 230 volt single phase 32 amp circuit runs 10 metres clipped direct in multi-core copper with PVC insulation. It is protected by a 32 amp type C MCB marked 10 kA and energy limiting class 3, and the board's prospective fault level is 8 kiloamps. The short-circuit check uses the MCB let-through instead of a clearing time.
| Phase configuration | Single phase, 230 V |
|---|---|
| Load current | 32 A |
| Run length | 10 m |
| Protection device rating | 32 A |
| Installation method | Clipped direct |
| Conductor / insulation | Copper, PVC 75 °C |
| Cable type | Multi-core |
| Short-circuit let-through | MCB energy limiting class 3 |
| MCB curve, breaking capacity | Type C, 10 kA |
| Prospective fault current | 8 kA |
Step 1, current and drop. A 6 square millimetre conductor rates 40 amps against 32, and the drop over 10 metres is 2 times 32 times 3.7512 times 10, divided by 1000, which is 2.40 volts or 1.0 percent. Without a short-circuit check the answer would be 6 square millimetres.
Step 2, let-through. EN 60898-1:2019 Table ZA.2 is for type C. Its 10,000 amp row and its 20, 25 and 32 amp column give a class 3 maximum of 100,000 ampere-squared seconds. The 8 kiloamp prospective fault is below the 10 kiloamp breaking capacity, so the breaker is rated for it and the check passes.
Step 3, the active. 111.2 times 6, squared, is 445,156, well above 100,000. Passes.
Step 4, the earth core. A 6 square millimetre cable has a 2.5 square millimetre earth core under Table 5.1. 111.2 times 2.5, squared, is 77,284, below 100,000, so it fails and the active steps up. A 10 square millimetre cable brings a 4 square millimetre core: 111.2 times 4, squared, is 197,847. Passes.
Step 5, rechecking 10 square millimetres. It rates 54 amps, runs at 52.3 degrees so the 60 degree column gives 2.12 ohms per kilometre, an impedance of 2.1219 with the 0.0906 reactance, and a drop of 1.36 volts, 0.6 percent.
PASS at 10 square millimetres, with its 4 square millimetre earth core, on the class 3 ceiling. That ceiling is the most any class 3 breaker of this rating may let through at 10 kiloamps. If the maker's curve for the actual breaker at 8 kiloamps reads below 77,284 ampere-squared seconds, enter that figure with Custom and the 6 square millimetre cable passes. Read it from the curve, do not assume it.
Cable Sizing Guide
Cable sizing in Australia is governed by AS/NZS 3008.1.1:2025 (Australian conditions) and AS/NZS 3000:2018 (Wiring Rules). The 4th edition was published in December 2025 and introduces updated current rating tables, revised derating factors, and expanded coverage for modern installation methods including solar PV DC circuits.
The three checks every cable must pass
- 1
Current carrying capacity : The cable must carry the full load current continuously without exceeding its rated temperature.
- 2
Voltage drop : Voltage drop from source to load must not exceed 5% of the nominal supply voltage (AS/NZS 3000 Clause 3.6).
- 3
Earth fault loop impedance : Total earth fault loop impedance must be low enough that the protection device disconnects within the required time.
Common questions
How do I size a cable for an Australian installation?+
Australian cable sizing follows AS/NZS 3008.1.1:2025 and AS/NZS 3000:2018. Every cable must pass three checks. (1) Current carrying capacity: the cable must safely carry the full load current after derating for ambient temperature, grouping, and installation method. (2) Voltage drop: total drop from source to load must not exceed 5% of nominal voltage (AS/NZS 3000 Clause 3.6). (3) Earth fault loop impedance: the loop must be low enough for protection to clear faults within the Clause 5.7.2 disconnection times, using the maximum Zs values in AS/NZS 3000 Table 8.1. The calculator runs all three in parallel and returns the smallest size that passes.
What is the maximum voltage drop allowed in AS/NZS 3000?+
AS/NZS 3000:2018 Clause 3.6 sets the limit at 5% of the nominal supply voltage from the point of supply to the most remote point of the installation. For 230 V single-phase that is 11.5 V; for 400 V three-phase line-to-line that is 20 V. Some industries and supply authorities require tighter limits (3% is common for sensitive equipment). Set the target percentage in the calculator and it back-solves to the cable size that just passes.
How is current carrying capacity determined?+
Current carrying capacity (Iz) starts from the base current rating in AS/NZS 3008.1.1:2025 tables for the chosen cable construction (PVC, XLPE, copper, aluminium) and installation method. Three derating factors then apply: ambient temperature (default 40 °C in Australia), grouping (number of circuits in the same enclosure), and depth of burial for direct-buried cables. Iz = Itable × Ka × Kg × Kd. The calculator does this automatically based on the inputs you provide.
What changed in AS/NZS 3008.1.1:2025 compared to 2017?+
The 4th edition (December 2025) updates the current rating tables with newer cable constructions, revises grouping derating for closely-packed installations, expands installation methods to include solar PV DC string circuits and EV charging infrastructure, and adjusts ambient temperature reference values to better reflect Australian conditions. Some 2017 cable sizes will calculate slightly differently in 2025. The rating, resistance and derating figures in this calculator are indicative working values rather than transcriptions of the 2025 tables, so check a result against your copy of the standard.
Does the calculator handle parallel cables and multiple circuits per conduit?+
Yes. Set the grouping factor in the inputs to reflect the number of loaded circuits in the same enclosure or on the same tray. The calculator applies the AS/NZS 3008.1.1 grouping derating automatically. For parallel cables, enter the full design current and the number of cables per phase: the rating is multiplied by that count, the voltage drop is divided by it, and the Table 5.1 earth is worked out from the total active area and shared across the earth cables you specify, with no earth smaller than the Table 5.1 earth for one of the parallel actives.
Can I use this for cables longer than 100 m?+
Yes. The calculator handles any length. For very long runs, voltage drop is usually the binding constraint rather than current carrying capacity. The calculator will return a cable size large enough to keep the drop under your selected limit, which may be much larger than current rating alone would require.
Saved you time today? Shout the next coffee.
ElecCalc is free, with no login and no paywall, built by a working sparky in Adelaide. A few dollars covers the hosting and keeps the calculators checked against the standards.
On site? Get the same calcs on your phone.
SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.
Building something else? DataQuoll serves Australian emergency incidents, river gauges and trade RDO calendars as an API.
Related calculators