HomeCalculatorsMaximum Demand

Maximum Demand Calculator

AS/NZS 3000:2018 Tables C1 & C2 (Australian conditions)

✓ 2018 Standard📊 Phase 1

Inputs

Lighting & Power

Heating & Cooling

Cooking Appliances

Water Heating

Other Loads

Results

Maximum Demand

14.60kW
63.48A

Recommended Main Switch

80 A

Next standard size ≥ 63.48 A

Main Switch Rating

80 A (>= 63.47826086956522 A)

CategoryRaw (kW)DiversityAfter (kW)
Lighting3.000.832.50
Power Point Circuits4.000.632.50
Heating/Cooling0.001.000.00
Cooking Appliances6.001.006.00
Water Heater3.601.003.60
Other Fixed Appliances0.001.000.00
Motors0.001.000.00
Total14.60
Important: These results are indicative only. Diversity factors are pending CPEng verification against AS/NZS 3000:2018 Tables C1/C2. Do not use for final design without independent verification by a qualified electrical engineer.

Maximum Demand — AS/NZS 3000:2018

Maximum demand is the greatest average power drawn over a defined period, used to size main switches and determine meter/supply capacity. In Australia, maximum demand is calculated using diversity factors from AS/NZS 3000:2018 Tables C1 (residential) and C2 (commercial). Diversity factors account for the fact that not all loads operate simultaneously at full capacity.

Residential Maximum Demand (Table C1)

For residential installations, the demand calculator considers:

  • Lighting circuits: First circuit = 1 kW, additional = 0.75 kW each (⚠️ PLACEHOLDER)
  • Power point circuits: First = 1 kW, additional = 0.5 kW each (⚠️ PLACEHOLDER)
  • Heating & Cooling: Only the larger load is at 100%, the other at 50%
  • Cooking appliances: 1st = 100%, 2nd first 1 kW = 100% then 80%, 3rd+ = 60% (⚠️ PLACEHOLDER)
  • Water heating: Treated as continuous load (100%)
  • Fixed appliances: Each at 100%
  • Motors: Largest at 100%, others at 80% (⚠️ PLACEHOLDER)
  • EV charger: Treated as continuous load (100%)

Commercial Maximum Demand (Table C2)

For commercial installations, a simplified approach is used:

  • Lighting: 75% diversity factor (⚠️ PLACEHOLDER)
  • Socket outlets: 0.5 kW per circuit at 50% diversity (⚠️ PLACEHOLDER)
  • Fixed appliances: 100%
  • Motors: 85% average diversity (⚠️ PLACEHOLDER)

Main Switch Selection

The main switch rating must be ≥ the calculated maximum demand current. The calculator selects the next standard switch size (40A, 63A, 80A, 100A, 125A, 160A, 200A, 250A, 315A, 400A, 630A).

Important Notes

⚠️ Disclaimer: This calculator uses placeholder diversity factors pending CPEng verification against AS/NZS 3000:2018. For final design, these results must be verified by a qualified electrical engineer and checked against the current edition of AS/NZS 3000:2018 and the applicable electricity distributor's connection requirements.