Every field this calculator accepts, what it means, the range it accepts, and how it feeds the result. The four numeric fields under Advanced parameters are optional to change but always used. Every optional field left blank leaves the result exactly as it would be without it, apart from the defaults named below.
- Daily energy consumption (kilowatt hours per day, 1 to 200)
- Average daily site consumption. Take a recent bill and divide the quarterly kilowatt hours by about 90. A typical Australian household sits between 15 and 25. This is the single figure that sets the array size: the tool sizes the system to generate this amount per day, so it targets full annual offset, not a self consumption optimised system. Below 5 or above 100 raises a warning to check the units.
- Peak sun hours (hours per day, 2 to 8)
- Daily hours at an irradiance of 1 kilowatt per square metre, as a yearly average for the site. Roughly 3.5 to 4.5 for Hobart, Melbourne and Adelaide, 4.5 to 5.0 for Sydney and Perth, and 5.0 to 6.0 for Brisbane, Cairns and Darwin. Outside 2 to 8 the tool warns that the value is outside the Australian range. Use a yearly average, not a summer figure, or the system will be undersized for winter.
- Available roof area (square metres, 5 to 500)
- Usable area on the chosen roof plane. It does not constrain the array size: the tool sizes the array from consumption and then compares the area needed against this figure, reporting a fail and a warning if it does not fit. Deduct setbacks, walkways, vents and any shaded zone before entering it.
- Roof orientation (degrees, 0 to 360, where 0 is north)
- Azimuth of the roof plane measured from north. The performance factor is 0.85 plus 0.175 times the cosine of the angle from north, minus 0.025 times that cosine squared. That gives 1.00 at north, 0.961 at 45 degrees, 0.85 at due east or west and 0.65 at south, falling steadily from north to south and never reaching zero. It is an indicative curve for a roof of about 25 degrees at mid-latitude Australia, not a figure from a standard. At 30 degrees or more off north the tool suggests entering an orientation and tilt factor from a table or a modelling tool, and above 90 and below 270 it warns that the orientation is unfavourable.
- Roof tilt (degrees from horizontal, 0 to 90)
- Pitch of the roof plane. The tool assumes an optimum of 35 degrees and applies a quadratic penalty for deviation, floored at 0.7. A 20 degree roof scores 0.992, a 10 degree roof 0.977, a flat roof 0.955. Tilt is therefore a much weaker driver than orientation in this model.
- Panel wattage (watts per module, 200 to 500)
- Nameplate output of one module at standard test conditions. Modern modules are 370 to 440 watts; outside that range the tool raises a warning. It sets the module count and therefore the installed capacity after rounding up to a whole module. Note that the roof area calculation uses a fixed 1.7 square metres per module regardless of what you enter here.
- System loss (percent, 5 to 30 in the form, 0 to 50 accepted)
- Everything except inverter conversion: soiling, cable loss, temperature derate, mismatch, and any shading allowance. Typical 12 to 18 percent, default 14. Do not include inverter losses here, they are entered separately and the two multiply together.
- Inverter efficiency (percent, 90 to 99 in the form)
- European or weighted conversion efficiency from the inverter datasheet. Modern units are 95 to 98 percent. Below 92 percent the tool raises a warning. Combined with system loss it gives the overall system efficiency: for 14 percent loss and 96 percent inverter, 0.86 times 0.96 equals 0.8256.
- Export limit (kilowatts, 0 to 30)
- The distributor export cap at the point of connection. Commonly 5 kilowatts single phase and 10 kilowatts three phase, but it varies by network and by feeder. Enter 0 to switch the check off entirely. The check compares 0.95 times the selected inverter rating against this figure, so a system that is sized larger than the cap will fail here even though it is perfectly legal with export limiting configured at the inverter.
- DC string voltage check (optional: module Voc, modules per string, temperature coefficient, lowest cell temperature, inverter maximum input, system voltage limit)
- Works out the string open-circuit voltage at the coldest expected cell temperature, as N times Voc at STC times (1 plus the temperature coefficient over 100 times the lowest temperature minus 25). It checks the result against the inverter maximum DC input and against the system voltage limit, which defaults to 600 volts. If the coefficient or the temperature is left blank it uses minus 0.30 percent per degree and 0 degrees, and says so in the working. The 600 volt default is indicative; check AS/NZS 5033 and the site. If the string is too long it tells you the most modules the string can take.
- Orientation and tilt factor (optional, percent, above 0 to 120)
- The output of this roof plane relative to the peak sun hours you entered, taken from a tilt and orientation table or a modelling tool. When entered it replaces the built-in orientation and tilt curves in both the array sizing and the yield, and the working shows the curve value it replaced. Leave it blank to use the curves, which are indicative. The tool warns whenever the curve is used 30 degrees or more off north.
- Inverter rated output (optional, kilowatts)
- The AC rating of the inverter you are actually fitting. It replaces the automatic selection everywhere, including the export check and the DC/AC ratio: array kilowatts peak divided by this rating.
- Maximum DC/AC ratio (optional, 0.5 to 3, default 1.33)
- The ceiling for the DC/AC ratio check, which always runs: array kilowatts peak over the entered inverter rating, or over the automatically selected inverter if none is entered. The default 1.33 is the Clean Energy Regulator small-scale certificate rule (array up to 133 percent of inverter capacity), not a figure from AS/NZS 4777.2; it is indicative, so check the current rules. Above the ceiling the tool gives the most modules that fit. With an entered inverter, a ratio below 1 warns that the inverter is larger than the array.
- MPPT voltage window (optional: module Vmp, Vmp coefficient, hottest ambient, NOCT, MPPT minimum and maximum)
- Runs when the module Vmp and modules per string are entered. The hottest cell temperature is the ambient plus (NOCT minus 20) over 800 times 1000, so 45 degrees ambient and a 45 degree NOCT give 76.25 degrees. The string Vmp at that temperature is checked against the MPPT minimum, and the string Vmp at the lowest cell temperature against the MPPT maximum. Blank fields use minus 0.35 percent per degree, 45 degrees ambient and 45 degrees NOCT, all indicative. A failure gives the shortest or longest string that fits.
- String current and fusing (optional: module Isc and Imp, Isc factor, strings per MPPT, MPPTs, MPPT input current, module series fuse rating, fuse minimum factor)
- Runs when the module Isc is entered. The design string current is Isc times 1.25 by default and the MPPT current is that times the strings in parallel, checked against the inverter input current per MPPT. The reverse current into a faulted string is the other strings in parallel times the design current; if that exceeds the module maximum series fuse rating, string fuses are needed, and the fuse must sit between 1.5 times Isc and that rating. Without the module rating, three or more strings in parallel are assumed to need fuses. The 1.25 and 1.5 factors are indicative; check AS/NZS 5033. The MPPT count multiplies out a string layout that is compared with the module count.
- DC cable voltage drop (optional: one way route length, conductor size, material, target)
- Runs when the route length is entered, with the module Vmp and modules per string. Loop resistance is 2 times the length times the resistivity over the size, using 22.5 by 10 to the minus 3 ohm square millimetres per metre for copper and 36 by 10 to the minus 3 for aluminium from AS/NZS 3000 Appendix B Equation B7. The current is the module Imp, or the module rating over Vmp if Imp is blank. The drop is a percentage of the string Vmp at STC and is checked against 3 percent by default, which is an indicative design target, not a figure from a standard held here. Blank size uses 4 square millimetres.