AS/NZS 4777.2 + 5033

Solar PV Sizing Calculator

Solar system sizing and string design: panels, inverter, DC/AC ratio, cold Voc, hot Vmp against the MPPT window, string current, fusing, DC voltage drop and yield.

Inputs

Typical AU household: 15 to 25 kWh/day

Australia: 3.5 to 6.0 h/day (latitude dependent)

0° = North (optimal), 90° = East, 180° = South, 270° = West

Optimal ≈ latitude (e.g., 35° for Melbourne)

▶Advanced parameters

Typical modern: 370 to 440W

Soiling, cabling, temperature, mismatch (typical: 12 to 18%)

Modern inverters: 95 to 98%

0 = no limit, 5 kW = single-phase typical, 10 kW = three-phase

From a tilt and orientation table or modelling tool. Replaces the built-in orientation and tilt curves in sizing and yield. Blank uses the curves (indicative)

▶Inverter and DC/AC ratio (optional)

The inverter you are fitting. Replaces the automatic selection in the DC/AC and export checks

Blank uses 1.33 (indicative, CER small-scale scheme rule; check current CER and CEC guidelines)

▶DC string voltage check (optional)

Open-circuit voltage rises as cells get colder, so the coldest morning sets the maximum string voltage. Enter the module Voc and modules per string to check it.

From the module datasheet, e.g. 41.2

Modules connected in series

From the datasheet, negative. Blank uses -0.30

The site's record low morning temperature. Blank uses 0

From the inverter datasheet

Maximum PV array voltage allowed for the site. Blank uses 600 V (indicative, check AS/NZS 5033)

▶MPPT voltage window (optional)

On the hottest day the MPP voltage falls, and the string must stay above the tracker minimum. Uses the modules per string entered above.

From the module datasheet, e.g. 34.5

Datasheet Vmp or Pmax coefficient, negative. Blank uses -0.35 (indicative)

Site record high. Blank uses 45 (indicative)

From the datasheet. Blank uses 45 (indicative)

From the inverter datasheet

From the inverter datasheet

▶String current and fusing (optional)

From the module datasheet

Used for DC voltage drop. Blank uses module W / Vmp

Blank uses 1.25 (indicative, check AS/NZS 5033)

Blank uses 1

Blank uses 1. Checks the layout against the module count

From the inverter datasheet

From the module datasheet (reverse current rating)

Minimum fuse = factor x Isc. Blank uses 1.5 (indicative, check AS/NZS 5033)

▶DC cable voltage drop (optional)

String cable from the array to the inverter. Needs the module Vmp and modules per string.

Blank uses 4 mm² (indicative)

Resistivity from AS/NZS 3000 Appendix B, Equation B7

Blank uses 3 % (indicative, check AS/NZS 5033)

Results

System Size

5.6

kW

14 panels @ 400W

Number of panels14
Inverter size6 kVA
DC/AC ratio0.93
Orientation and tilt factor1.000
Daily yield20.8 kWh/day
Annual yield7,594 kWh/year
Specific yield1356 kWh/kWp/year
Self-consumption96.1%
Roof area required23.8 m²
Simple payback3.8 years

Checks

  • FailExport limit compliance: 5.70 kW (max 5)

    Distributor export limit; export control under AS/NZS 4777.1 and AS/NZS 4777.2 (clause not verified here)

  • PassDC/AC ratio within ceiling: 0.933 ratio (max 1.330)

    CER small-scale scheme rule: array up to 133% of inverter capacity (indicative, check current CER and CEC guidelines)

  • PassRoof area adequacy: 40 m² (min 23.80)

    1.7 m2 per module (indicative); check the array layout against AS/NZS 5033 and the module installation manual

Inverter size (6 kVA) exceeds export limit (5 kW). May require additional export control hardware.

String voltage not checked. Enter the module Voc and modules per string to check the cold-morning string voltage against the inverter and AS/NZS 5033 limits.

Show the working
Step by step derivation of the result
StepWorkingResultReference
System efficiency factor(1 - 14 / 100) x (96 / 100) = 0.860 x 0.960 = 0.82560.8256(1 - systemLoss%) × inverterEff%
Required DC system size20 kWh/day / (4.5 h x 0.8256) = 5.383 kW5.383 kWEnergy balance: daily energy / (PSH x system efficiency)
Roof orientation factorcos(0 deg from north) = 1.0000; 0.85 + 0.175 x 1.0000 - 0.025 x 1.0000^2 = 1.000 (indicative)1.0000.85 + 0.175 cos(az) - 0.025 cos(az)^2, southern hemisphere, about 25 degree tilt (indicative curve, not from a standard)
Roof tilt factormax(0.7, 1 - (abs(35 - 35 optimal) / 90)^2 x 0.3) = 1.0001.000Quadratic penalty around a 35 degree optimum (indicative curve, not from a standard)
System size adjusted for roof geometry5.383 kW / (1.000 orientation x 1.000 tilt = 1.000) = 5.383 kW5.383 kWRequired size / orientation and tilt factor
Number of modules requiredceil(5.383 kW x 1000 / 400 W per module) = 14 modules, giving 14 x 400 W = 5.60 kW installed14 unitsRounded up from design calculation
Inverter rating (standard)Array 5.60 kW x 1.33 = 7.45 kVA ceiling; selected 6 kVA (ratio 1.07)6 kVAIndicative selection: first standard size from 1.0 to 1.33 x array (not a standard limit)
DC/AC ratio5.60 kWp / 6 kW selected inverter = 0.933, ceiling 1.33 (default, indicative)0.933Array kWp / inverter rated kW
Daily yield (AC)4.5 h x 5.60 kW x 0.8256 x 1.000 = 20.81 kWh/day20.81 kWh/dayPSH x installed kWp x system efficiency x orientation and tilt factor (indicative)
Annual yield (AC)20.81 kWh/day x 365 days = 7594 kWh/year7594 kWh/yearSimplified year-round estimate
Specific yield7594 kWh/year / 5.60 kWp = 1356.0 kWh/kWp/year1356.0 kWh/kWp/yearPerformance metric for system comparison
Roof area required14 panels x 1.7 m2 per panel = 23.8 m2, available 40 m223.8 m²Fixed 1.7 m2 per module (indicative)
Estimated self-consumptionmin(100, 20.0 kWh load / 20.81 kWh generation x 100) = 96.1 %96.1 %Simplified estimate based on load profile
Annual cost avoided (savings)(7300 kWh x $0.30) + (294 kWh x $0.05) = $2204.69 per year2204.69 $/yearAU tariffs: consumption $0.30/kWh, feed-in $0.05/kWh
Simple payback period5.60 kW x 1000 x $1.50/W = $8400; $8400 / $2204.69 per year = 3.8 years3.8 yearsSimplified estimate; ignores interest, tariff escalation, maintenance

Standards referenced

  • AS/NZS 3000:2018 Clause 7.3.2. Photovoltaic array systems to comply with AS/NZS 5033 (item d) and inverter systems with the AS/NZS 4777 series (item e)
  • AS/NZS 4777.2:2020. Inverter requirements for grid connection, including export control (standard not held in this repo; clause numbers not verified)
  • AS/NZS 5033:2021. PV array installation and safety: maximum array voltage, string current, overcurrent protection and cabling (standard not held in this repo; defaults here are indicative)
  • Clean Energy Regulator, Small-scale Renewable Energy Scheme. Array capacity up to 133% of inverter capacity for certificate eligibility (indicative; check the current CER and CEC rules)

Where a lookup value is marked indicative, it has not been transcribed from the current edition of the standard. Check results against your own copy before relying on them for design.

Important: These results are indicative only. Solar PV systems must be designed and installed by an accredited installer in accordance with AS/NZS 4777.1, AS/NZS 4777.2:2020 and AS/NZS 5033:2021, with the inverter and module datasheets. Values marked indicative are not taken from those standards.

Solar PV System Design Guide for AS/NZS 4777.2 and 5033

Sizing a grid-connected solar PV system involves balancing the customer's energy consumption, available roof space, inverter capacity, and local network export limits. A correctly sized system maximises self-consumption (using solar power on-site rather than exporting it at a lower feed-in tariff), minimises payback period, and complies with AS/NZS 4777.2:2020 for inverter energy systems and AS/NZS 5033:2021 for the DC array installation. This calculator takes the site's daily energy usage, location, roof orientation, and panel specifications to determine the optimal array size, inverter capacity, expected annual yield, and estimated payback period. It also checks the DC/AC ratio and the string design (cold Voc, hot and cold Vmp against the tracker window, string current, fusing and DC voltage drop) to flag problems before installation begins.

Key concepts

  • Peak sun hours (PSH) and location. PSH is the number of hours per day that solar irradiance averages 1 kW per square metre. It varies significantly across Australia: southern cities like Melbourne and Adelaide average 3.5 to 4.5 hours, while Darwin and Cairns average 5.0 to 6.0 hours. The calculator uses PSH to convert the array's rated capacity (kWp) into expected daily energy output (kWh). Choosing the wrong PSH value is one of the most common sizing errors.
  • DC to AC ratio (oversizing). The Clean Energy Regulator allows the DC array to be up to 1.33 times the inverter's rated AC output for small-scale certificates. That figure is a scheme rule, not an AS/NZS 4777.2 limit. This is called oversizing, and the cost is some clipping. Oversizing improves energy harvest in the morning and evening when irradiance is below peak, at the cost of minor clipping losses during the midday peak. It is standard practice in Australian residential systems because panels rarely reach their Standard Test Condition rating in real-world conditions.
  • String voltage and temperature effects. Panel open-circuit voltage (Voc) increases as ambient temperature drops. AS/NZS 5033:2021 requires that the maximum system voltage be calculated at the coldest expected temperature, not at STC (25 degrees Celsius). In southern Australia where winter mornings can reach 0 to 5 degrees Celsius, a string of panels that is within the inverter's MPPT range at 25 degrees may exceed the maximum input voltage at 0 degrees. The calculator applies the panel's temperature coefficient to compute worst-case Voc.
  • Export limits and DNSP rules. Most Australian DNSPs cap single-phase export at 5 kW and three-phase export at 10 kW at the point of connection. Systems larger than the export limit can still be installed but must use export limiting (zero export or dynamic export control) configured at the inverter. The calculator includes export limit configuration so you can size a larger array for self-consumption without violating network connection conditions.

Common scenarios

  • Sizing a residential system for a family in Adelaide. A household using 25 kWh per day in Adelaide (PSH approximately 4.2) needs a minimum array of about 6 kW to offset their consumption. After applying a 30% oversize allowance for system losses (soiling, temperature derating, inverter efficiency, cable losses), the recommended array is approximately 7.8 kWp. The electrician enters the consumption, location, and roof details, and the calculator determines the panel count, inverter size, and expected payback period based on current consumption and feed-in tariff rates.
  • Checking string voltage for a commercial rooftop in Melbourne. A commercial installation uses 15 panels per string, each with a Voc of 41.2 V and a temperature coefficient of -0.27% per degree Celsius. At STC the string Voc is 618 V, but at a winter morning cell temperature of 2 degrees Celsius it rises to about 656 V. Enter those figures in the string voltage check with the inverter's maximum DC input, typically 1000 V for a commercial inverter, and the calculator shows whether the string fits, or how many modules to drop if it does not.
  • Evaluating payback for a system with low self-consumption. A homeowner who works during the day and uses most electricity in the evening will have a self-consumption ratio of only 20 to 30% without a battery. Most of the solar generation is exported at 5 to 8 cents per kWh rather than offsetting grid consumption at 30 to 35 cents per kWh. The calculator shows how this low self-consumption ratio extends the payback period compared to a household with daytime loads, helping the customer make an informed decision about system size and whether to add battery storage.

System sizing components

  • Daily energy consumption (kWh): All on-site loads to be offset by solar generation.
  • Peak sun hours (PSH): Australia typically 3.5 to 6.0 hours per day depending on location and season.
  • Roof area and orientation: North-facing is optimal in the southern hemisphere; east and west orientations reduce output by 10 to 20%.
  • Roof tilt: Optimal angle is approximately equal to the site latitude (for example, 35 degrees for Melbourne).
  • System losses: Soiling 2 to 3%, cabling 2 to 3%, temperature 5 to 7%, inverter 4 to 5%.

Key compliance requirements

  • Export limiting: Single-phase typically 5 kW, three-phase 10 kW, set by the distributor.
  • DC/AC ratio: Array up to 1.33 times the inverter rating for small-scale certificates (Clean Energy Regulator rule, indicative).
  • DC string voltage: The cold-morning string Voc must stay under the inverter maximum DC input and the AS/NZS 5033 maximum array voltage for the site.
  • MPPT window: The hot-day string Vmp must stay above the tracker minimum and the cold-morning Vmp below the tracker maximum, from the inverter datasheet.
  • String current and fusing: Strings in parallel must not exceed the tracker input current, and with three or more strings in parallel string fuses are normally needed. The multipliers used are indicative; check AS/NZS 5033.
  • Standards route: AS/NZS 3000:2018 Clause 7.3.2 requires PV array systems to comply with AS/NZS 5033 and inverter systems with the AS/NZS 4777 series.
  • Anti-islanding: All grid-connected inverters require automatic disconnection on grid failure.

Performance metrics

  • Specific yield: 1,000 to 1,400 kWh/kWp/year typical in Australia.
  • Self-consumption: Percentage of generation used on-site. Higher self-consumption delivers better return on investment without batteries.
  • Payback period: Estimated using approximately $0.30/kWh consumption tariff and approximately $0.05/kWh feed-in tariff (typical current Australian tariffs).
Disclaimer: Solar PV systems must be designed and installed by a certified solar installer in accordance with AS/NZS 4777.2:2020 and AS/NZS 5033:2021. Tariff rates and DNSP connection conditions vary by state and distributor.

Parameters

Every field this calculator accepts, what it means, the range it accepts, and how it feeds the result. The four numeric fields under Advanced parameters are optional to change but always used. Every optional field left blank leaves the result exactly as it would be without it, apart from the defaults named below.

Daily energy consumption (kilowatt hours per day, 1 to 200)
Average daily site consumption. Take a recent bill and divide the quarterly kilowatt hours by about 90. A typical Australian household sits between 15 and 25. This is the single figure that sets the array size: the tool sizes the system to generate this amount per day, so it targets full annual offset, not a self consumption optimised system. Below 5 or above 100 raises a warning to check the units.
Peak sun hours (hours per day, 2 to 8)
Daily hours at an irradiance of 1 kilowatt per square metre, as a yearly average for the site. Roughly 3.5 to 4.5 for Hobart, Melbourne and Adelaide, 4.5 to 5.0 for Sydney and Perth, and 5.0 to 6.0 for Brisbane, Cairns and Darwin. Outside 2 to 8 the tool warns that the value is outside the Australian range. Use a yearly average, not a summer figure, or the system will be undersized for winter.
Available roof area (square metres, 5 to 500)
Usable area on the chosen roof plane. It does not constrain the array size: the tool sizes the array from consumption and then compares the area needed against this figure, reporting a fail and a warning if it does not fit. Deduct setbacks, walkways, vents and any shaded zone before entering it.
Roof orientation (degrees, 0 to 360, where 0 is north)
Azimuth of the roof plane measured from north. The performance factor is 0.85 plus 0.175 times the cosine of the angle from north, minus 0.025 times that cosine squared. That gives 1.00 at north, 0.961 at 45 degrees, 0.85 at due east or west and 0.65 at south, falling steadily from north to south and never reaching zero. It is an indicative curve for a roof of about 25 degrees at mid-latitude Australia, not a figure from a standard. At 30 degrees or more off north the tool suggests entering an orientation and tilt factor from a table or a modelling tool, and above 90 and below 270 it warns that the orientation is unfavourable.
Roof tilt (degrees from horizontal, 0 to 90)
Pitch of the roof plane. The tool assumes an optimum of 35 degrees and applies a quadratic penalty for deviation, floored at 0.7. A 20 degree roof scores 0.992, a 10 degree roof 0.977, a flat roof 0.955. Tilt is therefore a much weaker driver than orientation in this model.
Panel wattage (watts per module, 200 to 500)
Nameplate output of one module at standard test conditions. Modern modules are 370 to 440 watts; outside that range the tool raises a warning. It sets the module count and therefore the installed capacity after rounding up to a whole module. Note that the roof area calculation uses a fixed 1.7 square metres per module regardless of what you enter here.
System loss (percent, 5 to 30 in the form, 0 to 50 accepted)
Everything except inverter conversion: soiling, cable loss, temperature derate, mismatch, and any shading allowance. Typical 12 to 18 percent, default 14. Do not include inverter losses here, they are entered separately and the two multiply together.
Inverter efficiency (percent, 90 to 99 in the form)
European or weighted conversion efficiency from the inverter datasheet. Modern units are 95 to 98 percent. Below 92 percent the tool raises a warning. Combined with system loss it gives the overall system efficiency: for 14 percent loss and 96 percent inverter, 0.86 times 0.96 equals 0.8256.
Export limit (kilowatts, 0 to 30)
The distributor export cap at the point of connection. Commonly 5 kilowatts single phase and 10 kilowatts three phase, but it varies by network and by feeder. Enter 0 to switch the check off entirely. The check compares 0.95 times the selected inverter rating against this figure, so a system that is sized larger than the cap will fail here even though it is perfectly legal with export limiting configured at the inverter.
DC string voltage check (optional: module Voc, modules per string, temperature coefficient, lowest cell temperature, inverter maximum input, system voltage limit)
Works out the string open-circuit voltage at the coldest expected cell temperature, as N times Voc at STC times (1 plus the temperature coefficient over 100 times the lowest temperature minus 25). It checks the result against the inverter maximum DC input and against the system voltage limit, which defaults to 600 volts. If the coefficient or the temperature is left blank it uses minus 0.30 percent per degree and 0 degrees, and says so in the working. The 600 volt default is indicative; check AS/NZS 5033 and the site. If the string is too long it tells you the most modules the string can take.
Orientation and tilt factor (optional, percent, above 0 to 120)
The output of this roof plane relative to the peak sun hours you entered, taken from a tilt and orientation table or a modelling tool. When entered it replaces the built-in orientation and tilt curves in both the array sizing and the yield, and the working shows the curve value it replaced. Leave it blank to use the curves, which are indicative. The tool warns whenever the curve is used 30 degrees or more off north.
Inverter rated output (optional, kilowatts)
The AC rating of the inverter you are actually fitting. It replaces the automatic selection everywhere, including the export check and the DC/AC ratio: array kilowatts peak divided by this rating.
Maximum DC/AC ratio (optional, 0.5 to 3, default 1.33)
The ceiling for the DC/AC ratio check, which always runs: array kilowatts peak over the entered inverter rating, or over the automatically selected inverter if none is entered. The default 1.33 is the Clean Energy Regulator small-scale certificate rule (array up to 133 percent of inverter capacity), not a figure from AS/NZS 4777.2; it is indicative, so check the current rules. Above the ceiling the tool gives the most modules that fit. With an entered inverter, a ratio below 1 warns that the inverter is larger than the array.
MPPT voltage window (optional: module Vmp, Vmp coefficient, hottest ambient, NOCT, MPPT minimum and maximum)
Runs when the module Vmp and modules per string are entered. The hottest cell temperature is the ambient plus (NOCT minus 20) over 800 times 1000, so 45 degrees ambient and a 45 degree NOCT give 76.25 degrees. The string Vmp at that temperature is checked against the MPPT minimum, and the string Vmp at the lowest cell temperature against the MPPT maximum. Blank fields use minus 0.35 percent per degree, 45 degrees ambient and 45 degrees NOCT, all indicative. A failure gives the shortest or longest string that fits.
String current and fusing (optional: module Isc and Imp, Isc factor, strings per MPPT, MPPTs, MPPT input current, module series fuse rating, fuse minimum factor)
Runs when the module Isc is entered. The design string current is Isc times 1.25 by default and the MPPT current is that times the strings in parallel, checked against the inverter input current per MPPT. The reverse current into a faulted string is the other strings in parallel times the design current; if that exceeds the module maximum series fuse rating, string fuses are needed, and the fuse must sit between 1.5 times Isc and that rating. Without the module rating, three or more strings in parallel are assumed to need fuses. The 1.25 and 1.5 factors are indicative; check AS/NZS 5033. The MPPT count multiplies out a string layout that is compared with the module count.
DC cable voltage drop (optional: one way route length, conductor size, material, target)
Runs when the route length is entered, with the module Vmp and modules per string. Loop resistance is 2 times the length times the resistivity over the size, using 22.5 by 10 to the minus 3 ohm square millimetres per metre for copper and 36 by 10 to the minus 3 for aluminium from AS/NZS 3000 Appendix B Equation B7. The current is the module Imp, or the module rating over Vmp if Imp is blank. The drop is a percentage of the string Vmp at STC and is checked against 3 percent by default, which is an indicative design target, not a figure from a standard held here. Blank size uses 4 square millimetres.

Assumptions and limits

This is a first pass sizing tool for a single roof plane. Here is exactly what it assumes and where it stops.

What it assumes

  • A single roof plane and a flat energy target. The required array is the daily consumption divided by peak sun hours times system efficiency, then divided again by the combined orientation and tilt factor, then rounded up to whole modules. Splitting an array across two orientations, or across two inverters, is not supported.
  • Orientation and tilt are indicative curves, not irradiance modelling. An indicative southern hemisphere azimuth curve (1.00 north, 0.85 east or west, 0.65 south, for a roof of about 25 degrees) and a quadratic penalty around a 35 degree optimum for tilt. The two do not interact, so a steep west roof is scored the same way as a shallow one. Enter an orientation and tilt factor from a table to replace both. There is no shading analysis, no horizon profile, no ground reflectance, no seasonal split and no hourly simulation. A site with a real shading obstruction will not be represented at all.
  • Compensating for a poor roof by making the array bigger. When the geometry factor drops, the tool divides the required size by it, so an east or west roof at 0.85 asks for about 18 percent more array and a south roof at 0.65 about 54 percent more. That is a modelling choice, not what a designer would necessarily do. In practice you would often accept the lower yield rather than pay for the extra array.
  • Yield is a flat annual extrapolation. Daily yield is peak sun hours times installed capacity times system efficiency times the same orientation and tilt factor the sizing used, and annual yield is that times 365. Before October 2026 the yield left the factor out, so any roof off north reported more energy than the array it had just sized could make. No monthly profile, no temperature variation through the year, no panel degradation over life, no clipping loss when the array exceeds the inverter.
  • Self consumption is a crude ratio. It is the daily load divided by the daily generation, capped at 100 percent. It has no knowledge of when during the day the load occurs, so a system sized to just match the load reports a self consumption near 100 percent, which no real site achieves without storage. Treat this figure, and the payback that depends on it, as order of magnitude only.
  • Payback uses fixed assumptions. Installed cost of 1.50 dollars per watt, consumption tariff of 30 cents per kilowatt hour and feed in tariff of 5 cents. There is no rebate or small scale technology certificate, no interest, no tariff escalation, no maintenance and no inverter replacement at year 10 to 12.
  • Roof area required is a fixed 1.7 square metres per module. It ignores the module dimensions you implied by the wattage, and it ignores setbacks, walkways, penetrations and rail layout. Real usable roof needs are typically higher.
  • Inverter selection is a lookup, not an engineering choice. The tool takes the first standard rating from 3, 5, 6, 8, 10, 15, 20, 25 and 30 kilovolt amperes that is at or above the array size and at or below 1.33 times the array size, and if none fits it uses 1.1 times the array rounded up. That 1.33 is a selection rule, not a limit from AS/NZS 4777.2, and it keeps the DC/AC ratio at or below 1. Enter the inverter you are fitting to replace the selection in the DC/AC and export checks.
  • String design is one string type on identical trackers. Every string has the same module count and every MPPT the same number of strings. Temperatures come from a single hottest ambient and NOCT, at 1000 watts per square metre, with no wind or mounting correction. The Isc factor, the fuse window factor, the voltage drop target and the 600 volt default limit are indicative defaults, not values taken from AS/NZS 5033, which is not held here.

What it does not do

  • No DC cable current rating, no fuse or isolator product selection, no array isolation or switching arrangement, and no earthing and bonding of the array. The DC voltage drop covers the string cable only, not a combiner to inverter main cable.
  • No alternating current cable sizing and no voltage rise back to the point of supply. Use the voltage rise calculator for that, and expect voltage rise, not array sizing, to be the binding constraint on many jobs.
  • No inverter grid protection settings, no volt watt or volt var response curves, no anti islanding verification, and no dynamic or flexible export arrangements.
  • No distributor application requirements, no battery storage sizing, and no time of use or demand tariff modelling.

Every result should be checked against the current editions of AS/NZS 4777.1, AS/NZS 4777.2 and AS/NZS 5033, and against the local distributor connection rules, then signed off by the person responsible for the installation.

Worked examples

Five complete runs with every intermediate figure shown, so you can check the tool against your own arithmetic. Examples 4 and 5 add the string design.

Example 1. Adelaide house, single phase, north facing roof

A household using 20 kilowatt hours a day, 4.5 peak sun hours, 40 square metres of north facing roof at 35 degrees pitch, 400 watt modules, a 5 kilowatt export cap.

Daily consumption20 kWh/day
Peak sun hours4.5 h/day
Roof area, orientation, tilt40 m², 0°, 35°
Module rating400 W
System loss, inverter efficiency14 %, 96 %
Export limit5 kW

Working

  1. System efficiency: (1 - 0.14) x 0.96 = 0.8256.
  2. Required array: 20 / (4.5 x 0.8256) = 5.383 kW.
  3. Orientation factor at 0 degrees = 1.000. Tilt factor at 35 degrees = 1.000. Combined 1.000, so the adjusted size stays at 5.383 kW.
  4. Modules: 5,383 / 400 = 13.46, rounded up to 14. Installed 14 x 400 W = 5.60 kW.
  5. Inverter ceiling: 5.60 x 1.33 = 7.45 kVA. First standard rating at or above 5.60 and at or below 7.45 is 6 kVA. DC/AC ratio 5.60 / 6 = 0.933.
  6. Daily yield: 4.5 x 5.60 x 0.8256 = 20.81 kWh. Annual 20.81 x 365 = 7,594 kWh. Specific yield 7,594 / 5.60 = 1,356 kWh per kWp.
  7. Roof area needed: 14 x 1.7 = 23.8 m².
  8. Self consumption: 20 / 20.81 = 96.1 percent, so 7,300 kWh consumed and 294 kWh exported.
  9. Savings: 7,300 x 0.30 + 294 x 0.05 = 2,204.69 dollars. Cost 5.60 x 1,000 x 1.50 = 8,400 dollars. Payback 3.8 years.
  10. Export check: 6 x 0.95 = 5.7 kW against the 5 kW cap.

Result. 5.60 kilowatts, 14 modules, 6 kilovolt ampere inverter, 7,594 kilowatt hours a year, 3.8 year simple payback. DC/AC ratio 0.933 against 1.33 passes, roof area 23.8 against 40 square metres passes, export 5.7 against 5 kilowatts fails, which in practice means export limiting configured at the inverter. The string voltage check does not run here, because the module Voc and modules per string were left blank.

Example 2. Three phase site on a north east roof

A small commercial site using 35 kilowatt hours a day at 5.0 peak sun hours, with 90 square metres of roof facing 45 degrees east of north at a 20 degree pitch, 440 watt modules, a 97 percent inverter and a 10 kilowatt export cap. This example shows the orientation penalty on a roof 45 degrees off north.

Daily consumption35 kWh/day
Peak sun hours5.0 h/day
Roof area, orientation, tilt90 m², 45°, 20°
Module rating440 W
System loss, inverter efficiency14 %, 97 %
Export limit10 kW

Working

  1. System efficiency: 0.86 x 0.97 = 0.8342.
  2. Required array: 35 / (5.0 x 0.8342) = 8.391 kW.
  3. Orientation factor: cos 45 degrees = 0.7071, so 0.85 + 0.175 x 0.7071 - 0.025 x 0.5 = 0.961. Tilt factor at 20 degrees: 1 - (15 / 90) squared x 0.3 = 0.992. Combined 0.953.
  4. Adjusted array: 8.391 / 0.953 = 8.803 kW.
  5. Modules: 8,803 / 440 = 20.006, rounded up to 21. Installed 21 x 440 W = 9.24 kW. It only just tips over 20 modules.
  6. Inverter ceiling 9.24 x 1.33 = 12.29 kVA, so 10 kVA is selected. DC/AC ratio 9.24 / 10 = 0.924.
  7. Daily yield: 5.0 x 9.24 x 0.8342 x 0.953 = 36.74 kWh. Annual 13,409 kWh. Specific yield 1,451.2 kWh per kWp, the same 0.953 factor applied to every kilowatt.
  8. Roof area needed: 21 x 1.7 = 35.7 m² against 90 available.
  9. Self consumption: 35 / 36.74 = 95.3 percent, so 12,775 kWh consumed and 634 kWh exported.
  10. Savings: 12,775 x 0.30 + 634 x 0.05 = 3,864.21 dollars. Cost 9.24 x 1,000 x 1.50 = 13,860 dollars. Payback 3.6 years.
  11. Export check: 10 x 0.95 = 9.5 kW against the 10 kW cap.

Result. 9.24 kilowatts, 21 modules, 10 kilovolt ampere inverter, 13,409 kilowatt hours a year, 3.6 year payback. DC/AC ratio 0.924, roof area 35.7 square metres and export 9.5 kilowatts allpass. The 45 degree azimuth costs under 4 percent here, so it adds one module, not a doubled array. If a tilt and orientation table gave 93 percent for this roof (an assumed figure for illustration), entering it gives 8.391 / 0.93 = 9.022 kilowatts, still 21 modules, and 35.84 kilowatt hours a day.

Example 3. Small system that clears the export cap

A smaller household using 15 kilowatt hours a day at 4.0 peak sun hours, on 30 square metres of north facing roof at 25 degrees. This is the case where every check that the engine can pass, does.

Daily consumption15 kWh/day
Peak sun hours4.0 h/day
Roof area, orientation, tilt30 m², 0°, 25°
Module rating400 W
Export limit5 kW

Working

  1. System efficiency 0.8256. Required array: 15 / (4.0 x 0.8256) = 4.542 kW.
  2. Orientation 1.000, tilt at 25 degrees: 1 - (10 / 90) squared x 0.3 = 0.996. Adjusted 4.559 kW.
  3. Modules: 4,559 / 400 = 11.4, rounded up to 12. Installed 4.80 kW.
  4. Inverter ceiling 4.80 x 1.33 = 6.38 kVA, so 5 kVA is selected. DC/AC ratio 4.80 / 5 = 0.96.
  5. Daily yield: 4.0 x 4.80 x 0.8256 x 0.996 = 15.79 kWh. Annual 5,764 kWh. Specific yield 1,200.9 kWh per kWp.
  6. Roof area needed: 12 x 1.7 = 20.4 m² against 30 available.
  7. Self consumption 15 / 15.79 = 95.0 percent. Savings 5,475 x 0.30 + 289 x 0.05 = 1,656.97 dollars. Cost 7,200 dollars. Payback 4.3 years.
  8. Export check: 5 x 0.95 = 4.75 kW against the 5 kW cap.

Result. 4.80 kilowatts, 12 modules, 5 kilovolt ampere inverter, 5,764 kilowatt hours a year, 4.3 year payback. Export, DC/AC ratio and roof area all pass. The lower peak sun hours drop the specific yield from about 1,356 to 1,201 kilowatt hours per kilowatt peak. Almost all of that is the location; the 25 degree pitch costs only 0.4 percent.

Example 4. String design for the Example 1 house

The Example 1 house (14 modules, 5.60 kilowatts) on a 5 kilowatt inverter with two trackers, one string of 7 modules on each. Module Voc 41.2 volts, Vmp 34.5 volts, Isc 12.3 amps, Imp 11.6 amps. Inverter maximum DC input 600 volts, tracker range 90 to 560 volts, 16 amps per tracker. String cable 25 metres one way. The temperature coefficients, NOCT, temperatures, cable size and factors are left blank, so the indicative defaults apply.

Modules per string, strings per MPPT, MPPTs7, 1, 2
Module Voc, Vmp41.2 V, 34.5 V
Module Isc, Imp12.3 A, 11.6 A
Inverter rating5 kW
Inverter DC maximum, MPPT range600 V, 90 to 560 V
MPPT maximum input current16 A
String cable25 m, 4 mm² copper (default)

Working

  1. Cold Voc at 0 degrees, minus 0.30 percent per degree: 41.2 x (1 + 0.003 x 25) = 44.29 V per module, x 7 = 310.0 V, under 600 V.
  2. Hottest cell temperature: 45 + (45 - 20) / 800 x 1000 = 76.25 degrees.
  3. Hot Vmp at minus 0.35 percent per degree: 34.5 x (1 - 0.0035 x 51.25) = 28.312 V, x 7 = 198.2 V, above the 90 V tracker minimum.
  4. Cold Vmp: 34.5 x (1 + 0.0035 x 25) = 37.519 V, x 7 = 262.6 V, under the 560 V tracker maximum.
  5. Design string current: 1.25 x 12.3 = 15.38 A on one string, under the 16 A tracker input.
  6. Fusing: one string per tracker, so (1 - 1) x 15.38 = 0 A reverse current. No string fuses.
  7. Layout: 2 x 1 x 7 = 14 modules, matching the sizing.
  8. DC/AC ratio: 5.60 / 5 = 1.12, under 1.33. Export now 5 x 0.95 = 4.75 kW against the 5 kW cap.
  9. Cable: loop resistance 2 x 25 x 0.0225 / 4 = 0.2813 ohm. Drop 11.6 x 0.2813 = 3.26 V, over 7 x 34.5 = 241.5 V gives 1.35 percent. Loss 11.6 squared x 0.2813 = 37.8 W per string.

Result. Every check passes: cold Voc 310.0 V, hot Vmp 198.2 V, cold Vmp 262.6 V, tracker current 15.38 A, DC/AC 1.12, export 4.75 kW, voltage drop 1.35 percent. Fitting the 5 kilowatt inverter instead of the automatic 6 kilovolt ampere choice is also what clears the export check that failed in Example 1.

Example 5. Commercial array with three strings per tracker

A site using 120 kilowatt hours a day at 5.0 peak sun hours, north facing at 35 degrees, 440 watt modules, a 97 percent inverter and a 30 kilowatt export cap. The sizing gives 66 modules, 29.04 kilowatts, laid out as two trackers of three strings of 11. A 25 kilowatt inverter, 1000 volt maximum, tracker range 200 to 850 volts and 40 amps per tracker. Every datasheet and site value is entered.

Modules per string, strings per MPPT, MPPTs11, 3, 2
Module Voc, coefficient48.5 V, -0.27 %/°C
Module Vmp, coefficient, NOCT40.6 V, -0.30 %/°C, 44 °C
Module Isc, Imp, series fuse rating11.5 A, 10.84 A, 20 A
Coldest cell, hottest ambient-2 °C, 40 °C
Inverter25 kW, 1000 V, 200 to 850 V, 40 A per MPPT
String cable40 m, 6 mm² copper

Working

  1. Sizing: 120 / (5.0 x 0.8342) = 28.770 kW, 66 modules, 29.04 kW. DC/AC 29.04 / 25 = 1.162.
  2. Cold Voc: 48.5 x (1 + 0.0027 x 27) = 52.04 V, x 11 = 572.4 V, under the default 600 V limit and the 1000 V inverter maximum.
  3. Hottest cell: 40 + (44 - 20) x 1.25 = 70 degrees. Hot Vmp: 40.6 x (1 - 0.003 x 45) = 35.119 V, x 11 = 386.3 V, above 200 V.
  4. Cold Vmp: 40.6 x (1 + 0.003 x 27) = 43.889 V, x 11 = 482.8 V, under 850 V.
  5. Design string current 1.25 x 11.5 = 14.375 A. Three strings: 43.13 A against 40 A per tracker. Most strings that fit: 40 / 14.375 = 2.78, so 2.
  6. Fusing: (3 - 1) x 14.375 = 28.75 A reverse current, above the 20 A module rating, so string fuses are needed. Window 1.5 x 11.5 = 17.25 A to 20 A.
  7. Cable: 2 x 40 x 0.0225 / 6 = 0.3 ohm. Drop 10.84 x 0.3 = 3.25 V over 11 x 40.6 = 446.6 V gives 0.73 percent. Loss 35.3 W per string.
  8. Export 25 x 0.95 = 23.75 kW against 30 kW. Roof 66 x 1.7 = 112.2 m² against 250.

Result. Voltages, fusing window, DC/AC ratio, voltage drop, export and roof area all pass, with a fuse rated from 17.25 to 20 amps on each string. The tracker current fails at 43.13 amps against 40, so this inverter takes at most two strings per tracker: use a model with more or higher current trackers, or re-split the 66 modules.

Common questions

How do I size a solar PV system for an Australian home?+

Start from your daily energy use in kWh (look at a recent power bill, divide kWh per quarter by 90). Divide that by the local peak sun hours (3.5 to 4 in southern states, 5 to 6 in Queensland and the Northern Territory) to get the minimum array size in kW. Then divide by the system efficiency (14 percent losses and a 96 percent inverter give 0.8256) and by the roof orientation and tilt factor. The calculator does this once you enter consumption, peak sun hours and the roof details, then rounds up to whole modules.

What is the maximum panel to inverter ratio in Australia?+

The common 1.33 figure is not an AS/NZS 4777.2 limit. It is the Clean Energy Regulator rule for small-scale technology certificates, which allows the panel array to be up to 133 percent of the inverter capacity. Oversizing improves morning and evening yield, because real panels rarely reach Standard Test Condition output. Enter the inverter you are fitting and the calculator works out the DC/AC ratio and checks it against 1.33 by default; check the current CER and Clean Energy Council rules before relying on it.

What does AS/NZS 5033 require for DC string voltage?+

AS/NZS 5033 sets a maximum PV array voltage, commonly applied as 600 V DC on domestic premises; check the current edition for your site. String voltage is calculated at the coldest expected cell temperature (typically 0 to 5 degrees Celsius in southern Australia) using the module temperature coefficient, since cold weather lifts the open-circuit voltage. Enter the module Voc and modules per string and the calculator works out the cold-morning string Voc and checks it against the inverter maximum DC input and the system voltage limit. Add the module Vmp and the inverter MPPT range and it also checks that the string stays inside the tracker window on the hottest day and the coldest morning.

How do I calculate solar payback period in Australia?+

Estimate annual savings by adding (self-consumption percentage times annual yield times consumption tariff) plus (export percentage times annual yield times feed-in tariff). Typical values: consumption tariff around 30 to 35 cents per kWh, feed-in tariff 5 to 8 cents per kWh, self-consumption 30 to 50 percent without batteries. Divide system cost by annual savings to get payback in years; typical residential payback is currently 4 to 7 years.

What is the export limit for residential solar in Australia?+

Most distributors cap single-phase export at 5 kW and three-phase export at 10 kW (per AS/NZS 4777.2 and individual DNSP rules). Larger systems can be installed but must be configured with export limiting (zero export or controlled export) at the inverter. The calculator includes export limit configuration so you can size a larger array than your export allowance permits.

Keep ElecCalc free

Saved you time today? Shout the next coffee.

ElecCalc is free, with no login and no paywall, built by a working sparky in Adelaide. A few dollars covers the hosting and keeps the calculators checked against the standards.

Support ElecCalc
SparkyToolkit · iOS

On site? Get the same calcs on your phone.

SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.

Download on theApp Store

Building something else? DataQuoll serves Australian emergency incidents, river gauges and trade RDO calendars as an API.

Related calculators