Every field this calculator accepts, what it means, the range it accepts, and how it feeds the result. The last two live under Advanced options but are always used.
- Phase configuration (single phase or three phase)
- Sets two separate factors. The current calculation divides by 1 for single phase and by the square root of 3 for three phase. The voltage rise calculation multiplies by 2 for single phase, because the current flows out along the active and back along the neutral, and by the square root of 3 for three phase, giving a line to line rise. Changing this selector in the form also resets nominal voltage to 230 or 400 and the maximum allowed voltage to 253 or 440.
- Inverter rating (kilowatts, 0.5 to 100)
- The alternating current output rating of the inverter, not the array size. Use the continuous rated output from the datasheet, because that is the worst case export the cable ever carries. If you export limit the inverter, the current at the limit is what actually flows, so entering the limited figure gives the rise you will really see, while the full rating gives the design worst case.
- Cable size (square millimetres, 1.5 to 300)
- Cross sectional area of one active conductor. Only the sixteen standard sizes are accepted: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240 and 300. Anything else returns zeros and a warning rather than an interpolated answer. Resistance is looked up from this size, so it is the main lever you have on the result.
- Cable length (metres, 1 to 500, one way)
- Route length from the inverter to the meter or point of supply, measured one way. Do not double it for the return path: the return is already in the phase multiplier. Measure the real route including drops down walls and runs around the roof space, not the straight line distance. Above 1,000 metres the input is rejected as unreasonable.
- Conductor material (copper or aluminium)
- Copper uses the resistance table directly. Aluminium divides the copper resistance by 0.78, giving a factor of about 1.28. See the limits below: that factor is lower than the real resistivity ratio, so aluminium results understate the rise.
- Nominal voltage (volts, set by the phase selector)
- The reference used both to convert the inverter kilowatts into amperes and as the denominator for the percentage rise. It follows the phase selector at 230 or 400 volts. It is not the measured voltage on site, which is entered separately.
- Existing voltage at meter (volts, form range 200 to 280)
- The supply voltage measured at the point of supply, ideally at the middle of a sunny day when the feeder is lightly loaded and sitting high. The calculated rise is added to this to get the voltage at the inverter terminals. Gotcha: the field range and the module validation are both built around single phase values, the field caps at 280 volts and the validator rejects anything above 300, so a three phase line voltage near 400 volts sits outside the intended range even though the arithmetic still runs. For three phase work, read the rise in volts and percent and compare the absolute voltage yourself.
- Maximum allowed voltage (volts, default 253 single phase or 440 three phase)
- The absolute ceiling the inverter terminal voltage is checked against, taken from AS 61000.3.100 for the default values. Some distributors set their own figure in the connection offer, so override it when the offer says something different. It must not be less than the existing voltage at the meter.