Circuit Breaker Sizing
Select the correct breaker rating and curve for any circuit per AS/NZS 3000:2018.
Inputs
Load current from cable sizing calculation
After derating (temperature, grouping, etc.)
▶Advanced options
Leave blank for default (6 kA domestic)
Results
Recommended Breaker Rating
32
A
B-curve
B-curve selected for resistive loads (trips 3–5× In). Suitable for general-purpose and lighting circuits with minimal inrush.
Ib ≤ In
32 A
AS/NZS 3000 Cl 2.5.3
In ≤ Iz
32 A
AS/NZS 3000 Cl 2.5.3
Breaking Capacity
6 kA
AS/NZS 3000 Cl 2.5.5
Inrush Tolerance
1
AS/NZS 3000 Cl 2.5.4
Show the working
| Step | Working | Result | Reference |
|---|---|---|---|
| Identify design current (Ib) | Ib = 32 A (resistive load, 1-phase supply, non-continuous) | 32 A | AS/NZS 3000 Cl 2.5.3 |
| Identify cable CCC (Iz) | Iz = 40 A (derated cable capacity). Sizing rule: Ib <= In <= Iz, so 32 A <= In <= 40 A | 40 A | AS/NZS 3000 Cl 3.6.2 |
| Select standard rating | Smallest standard rating In with 32 A <= In <= 40 A gives In = 32 A (from 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A) | 32 A | AS/NZS 3000 Cl 2.5.3 |
| Select protective characteristic curve | Curve lookup: resistive load, starting multiple not specified gives B-curve. Magnetic trip band 3 to 5 x In = 96 to 160 A | B-curve | AS/NZS 3000 Cl 2.5.4 |
| Determine breaking capacity | Smallest standard capacity >= 6 kA prospective fault current gives 6 kA (from 6, 10, 15, 25 kA) | 6 kA | AS/NZS 3000 Cl 2.5.5 |
| RCD type recommendation | Table lookup: resistive load on 1-phase supply gives Type_A | Type_A | AS/NZS 3000 Cl 2.6.2 |
Lookup values used by these calculators are indicative and awaiting validation against the current standards. Confirm against your own licensed copy before relying on a result for design.
Parameters
Every field on the form maps to one input on the calculation engine. This is what each one means, what it is measured in, the range it accepts, and where it actually changes the answer.
- Design current, Ib (amperes)
- The current the circuit is expected to carry in normal service, after diversity has been applied. Take it from the load schedule or from the cable sizing calculation.
- Typical range. About 5 A for a small lighting circuit up to 125 A for a submain. The field accepts 1 to 500 A.
- Gotcha. Ib is the load current, not the cable rating. If you enter a design current above the cable capacity the calculator stops, reports the cable as undersized, and returns no breaker rating at all.
- Cable current-carrying capacity, Iz (amperes)
- The continuous current the cable can carry as installed. That is the AS/NZS 3008.1.1 table value after every derating factor has been applied: ambient temperature, grouping, thermal insulation, and installation method.
- Typical range. Around 20 to 25 A for 2.5 mm squared thermoplastic cable enclosed in a wall, and 34 to 40 A for 6 mm squared. The field accepts 1 to 500 A.
- Gotcha. Use the derated figure, not the raw table value. Entering the underated value inflates Iz and lets the calculator pick a breaker the cable cannot actually support.
- Load type (resistive, lighting, motor, mixed, capacitive)
- Selects the trip curve. Resistive and lighting return curve B. Motor returns curve C, or curve D when the starting multiple is above 8. Mixed and capacitive both return curve C.
- Gotcha. Load type changes the curve letter and the justification wording only. It does not change the selected rating or the breaking capacity.
- Motor starting multiple (multiples of rated current)
- The ratio of motor starting current to breaker rated current. Direct-on-line induction motors typically sit at 6 to 8 times. This field only appears when load type is set to motor.
- Typical range. The field accepts 1 to 15. Above 8 the curve moves from C to D. Above 10 the calculator raises a warning to confirm that direct-on-line starting is viable at all, or whether a soft starter is needed.
- Gotcha. For every other load type the value is not passed to the engine, so changing it has no effect.
- Continuous load (checkbox)
- Marks loads that run for more than three hours at a time, such as EV chargers, resistive heating, and process equipment.
- Gotcha. Ticking this box adds a note to the result and nothing else. The calculator does not apply a 125 percent or any other continuous-duty factor to the rating. If your design rule requires one, apply it to Ib before you enter it.
- Supply phase (single phase or three phase)
- Records whether the circuit is single phase or three phase and, when RCD protection is ticked, feeds the RCD type rule of thumb.
- Gotcha. The selected rating, curve, and breaking capacity are identical for both settings. Phase balance, neutral loading, and three-phase derating are not modelled.
- Prospective fault current (kiloamperes, optional, under advanced options)
- The maximum prospective short-circuit current available at the point where the device is installed.
- Typical range. About 3 to 6 kA at a domestic switchboard, 10 kA at a light commercial board, and 15 to 50 kA close to a distribution transformer. Leave the field blank and the calculator assumes 6 kA.
- Gotcha. The calculator returns the smallest standard breaking capacity from 6, 10, 15, and 25 kA that is at or above your figure. Enter more than 25 kA and it still returns 25 kA, but the breaking capacity check then fails. That failure is the signal to move to a moulded-case device.
- RCD protection required (checkbox, under advanced options)
- When ticked, the calculator adds an RCD type suggestion. Motor and capacitive loads return Type B, other three-phase circuits return Type AC, and everything else returns Type A.
- Gotcha. This is a coarse rule of thumb. It does not consider EV chargers, solar inverters, or the New Zealand Type A requirement, and it does not return a sensitivity in milliamperes. Use the RCD selection calculator for that decision.
Assumptions and limits
What the tool assumes
- Only the standard rating ladder of 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, and 125 A is considered. Fuses, adjustable moulded-case trip units, and non-standard ratings are not offered.
- It returns the smallest rating that satisfies Ib <= In <= Iz and stops there. If no standard rating fits inside that window it returns nothing and issues a warning rather than rounding either way.
- Breaking capacity is chosen from a four-value list of 6, 10, 15, and 25 kA.
- The trip curve is a lookup from load type. The calculator does not compare a device let-through characteristic against a motor starting curve or a transformer inrush curve.
- The trip bands quoted with each curve, roughly 3 to 5 times rated current for B, 5 to 10 for C, and 10 to 20 for D, are the generic bands. Individual manufacturer curves vary within and across those bands.
What this calculator does not do
- No overload coordination check against 1.45 times Iz, which is the second half of the AS/NZS 3000 Clause 2.5.3 rule.
- No adiabatic short-circuit check. It does not confirm that the cable withstands the let-through energy of the selected device.
- No earth fault loop impedance or disconnection time check against AS/NZS 3000 Table 8.1, so it cannot tell you whether the device clears a fault within 0.4 or 5 seconds.
- No discrimination, cascading, or backup protection check against the upstream device.
- No temperature correction of the device itself. Miniature circuit breaker thermal elements are calibrated at a reference ambient of 30 degrees Celsius and lose capacity in a hot switchboard.
- The RCD suggestion is a rule of thumb, not an assessment against AS/NZS 3000 Clause 2.6.
Do not treat any output here as a verified selection. Check the result against the current edition of AS/NZS 3000 and AS/NZS 60898.1, against the manufacturer published time-current curves and breaking capacity, and have the design signed off by the person responsible for the installation. Nothing on this page has been validated or certified by a chartered professional engineer.
Worked examples
Four complete runs through the same method, using the calculator formulas exactly as implemented.
Example 1: single-phase resistive final subcircuit
A domestic circuit supplying resistive load on 2.5 mm squared cable enclosed in a wall. Design current 16 A, derated cable capacity 23 A, prospective fault current at the board 4 kA, RCD protection required.
| Design current Ib | 16 A |
|---|---|
| Cable capacity Iz | 23 A |
| Load type | Resistive, single phase, not continuous |
| Prospective fault current | 4 kA |
- Walk the rating ladder. 6 A and 10 A are below Ib, so they fail Ib <= In. 16 A satisfies both 16 <= 16 and 16 <= 23, so 16 A is selected.
- Resistive load returns curve B.
- Breaking capacity: 6 kA is the smallest standard value at or above 4 kA.
- Single phase, resistive, RCD ticked returns Type A.
Result. 16 A curve B, 6 kA breaking capacity, Type A RCD. All four compliance checks pass: Ib <= In (16 <= 16), In <= Iz (16 <= 23), breaking capacity 6 kA at or above 4 kA, and inrush tolerance satisfied.
Example 2: three-phase direct-on-line motor
A 22 kW motor at a motor control centre. Full load current 40 A, cable derated to 57 A, starting current 7 times rated current, prospective fault current 18 kA, no RCD.
| Design current Ib | 40 A |
|---|---|
| Cable capacity Iz | 57 A |
| Load type | Motor, three phase, starting multiple 7 |
| Prospective fault current | 18 kA |
- Ratings 6 through 32 A all fail Ib <= In. 40 A satisfies 40 <= 40 and 40 <= 57, so 40 A is selected.
- Starting multiple 7 is not above 8, so the motor branch returns curve C rather than curve D.
- Breaking capacity: 6, 10, and 15 kA are all below 18 kA, so the calculator steps up to 25 kA.
- RCD not required, so the RCD type is reported as not applicable.
Result. 40 A curve C, 25 kA breaking capacity. All four checks pass, and the result carries a note that three-phase derating factors are not implemented.
Example 3: continuous EV charger circuit
A 32 A single-phase wall charger on 6 mm squared cable derated to 34 A, running for several hours at full load. Prospective fault current 6 kA, RCD protection required.
| Design current Ib | 32 A |
|---|---|
| Cable capacity Iz | 34 A |
| Load type | Mixed, single phase, continuous load ticked |
| Prospective fault current | 6 kA |
- 32 A is the first rating that satisfies 32 <= 32 and 32 <= 34, so it is selected. The window is only 2 A wide.
- Mixed load returns curve C.
- Breaking capacity: 6 kA meets the 6 kA fault level exactly, so the check passes on the boundary.
- Single phase, mixed load, RCD ticked returns Type A.
Result. 32 A curve C, 6 kA breaking capacity, Type A RCD. All four checks pass, with a note that the breaker must be rated for 100 percent continuous current. Remember that the calculator has not applied a continuous-duty factor for you, and in practice an EV charger circuit needs a Type A or Type B RCD confirmed against the charger datasheet.
Example 4: when no standard rating fits
A heat pump drawing 34 A on a cable derated to 38 A. This is the case people hit most often and then assume the calculator is broken.
- 32 A fails Ib <= In, because 34 A is above 32 A.
- 40 A fails In <= Iz, because 40 A is above 38 A.
- No standard rating sits inside the 34 A to 38 A window.
Result. No rating returned. The calculator reports 0 A with the warning that no standard breaker rating fits between 34 A and 38 A, and it produces no compliance checks. The fix is on the cable side: go up a size so Iz reaches at least 40 A, improve the installation method, or reduce the design current.
Circuit Breaker Selection for AS/NZS 3000:2018
Circuit breaker sizing is one of the most fundamental tasks in electrical design. Every circuit in an installation needs a protective device that will disconnect the supply fast enough to prevent cable damage during an overload or short circuit, while staying closed under normal operating conditions. This calculator helps you select the correct breaker rating, trip curve, and breaking capacity for a given circuit based on the design current, cable current-carrying capacity, and prospective fault current at the point of installation.
Whether you are wiring a residential switchboard, sizing protection for a commercial distribution board, or specifying MCBs for an industrial motor control centre, this tool applies the coordination rules from AS/NZS 3000:2018 Clause 2.5 and the device standards in AS/NZS 60898.1 (MCBs) and AS/NZS 60947.2 (MCCBs).
Key concepts
- Coordination rule (Ib <= In <= Iz). The breaker rated current (In) must sit between the circuit design current (Ib) and the cable current-carrying capacity (Iz). If In is below Ib the breaker nuisance-trips under normal load. If In exceeds Iz the cable overheats before the breaker trips.
- Trip curves (B, C, D). The curve letter defines the instantaneous magnetic trip threshold relative to rated current. Curve B trips magnetically between 3 and 5 times In, suiting resistive and lighting loads. Curve C trips between 5 and 10 times In, appropriate for small motors and fluorescent lighting with moderate inrush. Curve D trips between 10 and 14 times In, required for direct-on-line motor starting, welding equipment, and transformer energisation where inrush can exceed 10 times rated current.
- Breaking capacity (Icu / Icn). The maximum prospective fault current the device can safely interrupt. Common residential MCBs are rated at 6 kA. Light commercial installations typically require 10 kA. Industrial switchboards near large transformers can see fault levels of 25 to 50 kA, requiring MCCBs or high-rupture-capacity MCBs.
- Disconnection times. AS/NZS 3000 Clause 1.5.5.3(d) and Clause 5.7.2 require final subcircuits supplying socket outlets rated up to 63 A, hand-held Class I equipment, or portable equipment to disconnect within 0.4 seconds under fault, and other circuits including submains and circuits supplying fixed or stationary equipment within 5 seconds. Table 8.1 lists the maximum earth fault loop impedance that achieves these times for common MCB and fuse ratings. The breaker must be fast enough at the available fault current to meet these limits.
Common scenarios
- Residential final subcircuit. A 20 A lighting circuit on 2.5 mm squared TPS cable (Iz approximately 23 A in enclosed conduit at 40 degrees Celsius). Design current is 16 A. A 20 A curve B MCB with 6 kA breaking capacity satisfies the coordination rule and suits the resistive/lighting load profile.
- Commercial air conditioning circuit. A 7.5 kW three-phase split system drawing approximately 14 A at 400 V. The compressor motor has a locked rotor current of around 70 A (5 times FLC). A 16 A curve C MCB handles the starting inrush without nuisance-tripping, while a curve B at the same rating would trip on every compressor start.
- Industrial DOL motor starter. A 22 kW motor with a starting current of 280 A (approximately 7 times FLC of 40 A). The prospective fault current at the MCC is 18 kA. A 50 A curve D MCB (or MCCB with adjustable magnetic trip) prevents nuisance-tripping during the 2 to 3 second starting period, and the 25 kA breaking capacity exceeds the available fault level.
Common questions
How do I select the correct circuit breaker rating?+
The circuit breaker rated current must be greater than or equal to the circuit design current Ib and less than or equal to the cable current carrying capacity Iz. The standard ratings are 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Select the smallest standard rating that is at or above Ib.
What is the difference between curve B, C, and D circuit breakers?+
Curve B trips at 3 to 5 times rated current (general use, resistive loads). Curve C trips at 5 to 10 times rated current (motors with moderate inrush, fluorescent lighting). Curve D trips at 10 to 14 times rated current (high inrush loads like DOL motor starting, transformers, welding equipment).
When should I use a curve D circuit breaker?+
Curve D is required for circuits with high inrush current, primarily direct-on-line motor starting where locked rotor current is 5 to 7 times FLC. Curve C would nuisance-trip on the motor starting inrush. Curve D allows the inrush to pass for several seconds before tripping.
What is the breaking capacity of a circuit breaker?+
Breaking capacity (also called interrupting rating or Icu) is the maximum fault current the breaker can safely interrupt without damage. It must be equal to or greater than the prospective short circuit current at the point of installation. Common values are 6 kA for residential, 10 kA for light commercial, and 25 to 50 kA for industrial.
Can I use a circuit breaker as a switch?+
Yes, circuit breakers rated for switching duty can be used as isolating switches. Most modern MCBs are rated for switching duty per AS/NZS 60898. However, a circuit breaker should not be used as a routine on/off switch for high-frequency switching applications; a dedicated switch or contactor is more appropriate.
On site? Get the same calcs on your phone.
SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.
Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.
Related calculators