AS/NZS 3000:2018

RCD Selection Calculator

Select the right RCD type and sensitivity, including NZ Type A mandate, per AS/NZS 3000:2018.

Inputs

Results

Recommended RCD Type

AC

30 mA

2P RCD @ 20 A

Sensitivity adequate for location

30 mA (<= 100)

RCD type adequate for load

1 (>= 1)

Disconnection time

300 ms (<= 300)

RCD rating ≥ circuit current

20 A (<= 20)

RCD TypeAC
Sensitivity30 mA
RCD Rating20 A
Number of Poles2P
Max Disconnection Time300 ms
Type A RequiredNo
Additional ProtectionNot required

Recommended Products (Informational)

AC-type 30mA RCD (e.g., Clipsal, Schneider Electric, Legrand, Eaton)

Show the working
Step by step derivation of the result
StepWorkingResultReference
Identify circuit typeLookup keys: circuitType = socket_outlet, country = AUsocket_outletAS/NZS 3000 Cl 2.6.2
Identify location/installation environmentLookup key: location = indoorindoorAS/NZS 3000 Cl 2.6.4
Identify phase type and rated currentsingle-phase circuit, In = 20 Asingle, 20 A AAS/NZS 3000 Cl 2.6.1
Determine RCD sensitivityTable lookup: location = indoor + circuitType = socket_outlet gives 30 mA (allowed values 10, 30, 100, 300 mA)30 mAAS/NZS 3000 Cl 2.6.4
Determine RCD type (AC/A/F/B)Table lookup: circuitType = socket_outlet, hasVSD = false, hasNonLinearLoads = false gives Type ACACAS/NZS 3000 Cl 2.6.2
Maximum disconnection timeTable lookup: location = indoor gives 300 ms (0.300 s) maximum disconnection time300 msAS/NZS 3000 Cl 2.6.2
Determine number of polessingle-phase gives 2 poles (L + N)2PAS/NZS 3000 Cl 2.6.1
Select RCD ratingSmallest standard rating >= 20 A gives 20 A (from 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A), leaving 0.0 A of headroom20 AAS/NZS 3000 Cl 2.6.1

Standards referenced

  • AS/NZS 3000:2018 Clause 2.6.1. Residual current device selection and rating
  • AS/NZS 3000:2018 Clause 2.6.2. RCD type and sensitivity requirements by circuit type
  • AS/NZS 3000:2018 Clause 2.6.3. Additional protective measures
  • AS/NZS 3000:2018 Clause 2.6.4. Special requirements for wet areas and high-risk locations
  • AS/NZS 3000:2018 Amendment 1. Type A RCD mandate for NZ socket outlet circuits

Lookup values used by these calculators are indicative and awaiting validation against the current standards. Confirm against your own licensed copy before relying on a result for design.

DRAFT: Pending CPEng review for compliance accuracy

Important: These recommendations are indicative only. RCD selection and installation must be verified by a qualified electrical engineer in accordance with AS/NZS 3000:2018. Consult manufacturer datasheets and obtain professional electrical design before purchasing.

Parameters

Seven inputs drive the recommendation. This is what each one means, what it is measured in, and exactly which part of the output it controls.

Circuit type (eight options)
Lighting, socket outlet, fixed appliance, motor, EV charger, hot water, pool or spa, and medical. This is the primary input: it drives both the sensitivity and the device type.
How it is used. Medical always returns Type B. Pool or spa returns 30 mA. Socket outlet returns 30 mA, or 10 mA in a wet area or bathroom. Indoor lighting returns 100 mA. Everything else returns 30 mA.
Phase type (single phase or three phase)
Single phase returns a 2-pole device covering active and neutral. Three phase returns a 4-pole device covering three actives and neutral.
Gotcha. Pole count is all this input controls. It does not change the sensitivity, the type, or the disconnection time, and there is no option for a 3-pole device on a three-wire circuit with no neutral.
Circuit rated current (amperes)
The rated current of the circuit the RCD sits in, normally the rating of the protective device in front of it.
Typical range. 10 to 63 A for final subcircuits, higher for submains. The field accepts 1 to 200 A.
Gotcha. The calculator rounds up to the next standard RCD frame size from 16, 20, 25, 32, 40, 50, 63, 80, 100, and 125 A. Anything under 16 A therefore returns a 16 A device, and anything above 125 A returns 125 A. Above 63 A the result carries a warning to check the device short-circuit rating.
Location (indoor dry, outdoor, wet area, bathroom)
The environment the circuit serves. It sharpens the sensitivity and sets the maximum disconnection time reported with the result.
How it is used. Bathroom and wet area report 100 milliseconds, outdoor reports 200 milliseconds, indoor reports 300 milliseconds. A wet area or bathroom combined with a socket outlet or hot water circuit drops the sensitivity from 30 mA to 10 mA. Outdoor also flags that portable RCD protection should be considered for maintenance work.
Country (Australia or New Zealand)
Selecting New Zealand on a socket outlet circuit forces the recommendation up to Type A, reflecting the New Zealand requirement that Type AC is no longer acceptable for socket outlet protection.
Gotcha. The country setting has no effect on any circuit type other than socket outlets, and it does not change sensitivity or disconnection time.
Variable speed drive (checkbox)
Tick this when the load includes a variable speed drive, frequency converter, or soft starter, which can produce residual current that is not a clean sine wave.
How it is used. On a motor circuit it returns Type F, or Type B when non-linear loads is also ticked. On an EV charger circuit it returns Type A. On any other circuit type it returns Type F.
Non-linear loads (checkbox)
Tick this for harmonic-heavy loads such as large rectifier fronts, banks of switch-mode supplies, or drives without input filtering.
Gotcha. On its own this box upgrades motor and EV charger circuits to Type B on its own, without needing the variable speed drive box. On every other circuit type it only adds a note about monitoring harmonic distortion. It changes the device type only when it is combined with the variable speed drive box on a motor circuit, where it lifts the recommendation from Type F to Type B.

Assumptions and limits

What the tool assumes

  • The recommendation is a decision tree over those seven inputs. It is not a clause-by-clause application of AS/NZS 3000 Section 2.6, and the engine itself carries a draft status note that appears with every result.
  • The disconnection times of 100, 200, and 300 milliseconds are values the tool assigns by location. AS/NZS 3000 and AS/NZS 61008 set RCD performance by device rating and residual current, not by whether the room is wet, so treat those figures as a design target rather than a quoted requirement.
  • Sensitivity is chosen from location and circuit type only. There is no calculation of standing earth leakage from connected equipment, which is the usual cause of nuisance tripping on circuits with many electronic loads.

Known quirks you will see in the output

  • An indoor lighting circuit returns 100 mA. For Australian domestic work, Clause 2.6.3.2.2 requires 30 mA on final subcircuits including lighting, so take 30 mA as the default and treat the 100 mA result as out of step with current practice.
  • Ordinary Australian socket outlet and lighting circuits return Type AC. Current practice, and the New Zealand requirement, is Type A as the minimum for new work. Read a Type AC result as the floor, not the recommendation.
  • On a New Zealand socket outlet circuit the headline recommendation correctly moves up to Type A, but the check named RCD type adequate for load still tests the type from before that upgrade and reports a failure. Read it as confirmation that the Type A requirement was applied, not as a defect in the recommendation.
  • The suggested products are generic manufacturer names attached to the type and sensitivity. They are not a product selection and they are not checked for availability or rating.

What this calculator does not do

  • No discrimination check between a 30 mA final RCD and a 100 or 300 mA upstream device, and no time-delayed or selective type S option.
  • No short-circuit rating or backup protection check on the RCD itself, and no choice between a separate RCD plus circuit breaker and a combined RCBO.
  • No coverage of the special-location rules that override the general ones: medical body-protected and cardiac-protected areas to AS/NZS 3003, construction and demolition sites to AS/NZS 3012, swimming pool and spa zones, marinas, or caravan parks.
  • No assessment of solar photovoltaic or battery systems, where the inverter topology decides whether Type B is mandatory.

Use the result as a starting point for the conversation, then check it against the current edition of AS/NZS 3000, against the load manufacturer installation instructions, particularly for EV chargers and inverters, and against the local supply authority or jurisdiction rules. Have the selection signed off by the person responsible for the installation. Nothing on this page has been validated or certified by a chartered professional engineer.

Worked examples

Three complete runs through the decision tree, including the checks the calculator reports.

Example 1: Australian domestic socket outlet circuit

A 20 A general power circuit in the living areas of a house. Single phase, indoor dry location, Australia, no drive, no non-linear loads.

  1. Sensitivity: socket outlet outside a wet area returns 30 mA.
  2. Type: no drive, no non-linear load, not medical and not pool, so the tree returns Type AC.
  3. Poles: single phase returns 2 poles.
  4. Rating: the smallest standard frame at or above 20 A is 20 A.
  5. Disconnection time: indoor returns 300 milliseconds.

Result. Type AC, 30 mA, 2-pole, 20 A frame. All four checks pass: sensitivity 30 mA within the 100 mA limit, type check satisfied, disconnection 300 milliseconds within 300, and rating 20 A within the 20 A frame. In practice specify Type A rather than Type AC for new work.

Example 2: New Zealand bathroom socket outlet

A 16 A socket outlet circuit serving a bathroom in a New Zealand dwelling. Single phase, no drive, no non-linear loads.

  1. Sensitivity: bathroom combined with socket outlet returns 10 mA rather than 30 mA.
  2. Type: the base tree returns Type AC, then the New Zealand socket outlet rule lifts the recommendation to Type A.
  3. Poles: single phase returns 2 poles.
  4. Rating: 16 A is already a standard frame size.
  5. Disconnection time: bathroom returns 100 milliseconds.

Result. Type A, 10 mA, 2-pole, 16 A frame, 100 milliseconds. Sensitivity, disconnection time, and rating checks pass. The type check fails because it is testing the pre-upgrade Type AC against the New Zealand requirement. That failure is the tool telling you the mandate applied, and the Type A headline is the answer to use.

Example 3: three-phase motor on a drive, outdoors

A 40 A three-phase pump motor fed from a variable speed drive in an outdoor plant enclosure, with harmonic-heavy loads on the same board. Australia.

  1. Sensitivity: a motor circuit, and an outdoor location, both point to 30 mA.
  2. Type: motor plus drive would return Type F, but non-linear loads is also ticked, so it lifts to Type B.
  3. Poles: three phase returns 4 poles.
  4. Rating: 40 A is already a standard frame size.
  5. Disconnection time: outdoor returns 200 milliseconds.
  6. Outdoor location also flags portable RCD protection for maintenance work.

Result. Type B, 30 mA, 4-pole, 40 A frame, 200 milliseconds, with portable RCD protection recommended. All four checks pass. A Type B device is expensive and physically large, so confirm against the drive manufacturer documentation whether Type B is genuinely required or whether an internally protected drive allows a Type F upstream.

RCD Selection for AS/NZS 3000:2018

A residual current device (RCD) continuously compares the current flowing out on the active with the current returning on the neutral. Under healthy conditions the two are equal; when some current leaks to earth, through a person, a damaged cable, or a wet appliance, the balance is lost and the RCD disconnects within milliseconds. The standard sensitivity for personal protection is 30 mA, fast enough to prevent ventricular fibrillation in most circumstances.

When AS/NZS 3000 requires an RCD

In Australian domestic and residential installations, Clause 2.6.3.2.2 requires 30 mA RCD protection on all final subcircuits, including fixed-wired appliances such as hot water systems and air conditioners. The only exceptions are extra-low voltage subcircuits, separated supply subcircuits, and repairs. In non-domestic installations, Clause 2.6.3.2.3.3 requires 30 mA RCDs on final subcircuits rated up to 32 A supplying socket outlets, lighting, directly connected hand-held equipment, and directly connected equipment that presents an increased risk of electric shock. Special locations, bathrooms, swimming pools, construction sites, and medical areas, carry additional requirements that override the general rules.

The four RCD types

The right type depends on the kind of residual current a load can produce. Modern electronics rectify the mains, so the leakage is no longer a clean sine wave, and a basic Type AC can be blinded by it.

  • Type AC: detects AC sinusoidal residual current only. No longer the minimum for socket outlets in New Zealand.
  • Type A: AC plus pulsating DC residual current from rectified loads (LED drivers, switchmode supplies, induction cooktops). The New Zealand minimum and the recommended default for new Australian work.
  • Type F: Type A behaviour plus the composite frequencies produced by single-phase variable frequency drives, common on pool pumps and some HVAC.
  • Type B: all of the above plus smooth DC residual current above 6 mA. Required where a load can develop a true DC earth fault, principally EV chargers and grid-connected solar.

Common scenarios

  • Kitchen and bathroom socket outlets: 30 mA Type A.
  • EV charger (Mode 3): Type B, unless the charger has integrated DC fault detection and the manufacturer permits a Type A upstream.
  • Grid-connected solar inverter: Type B on the AC side for non-isolated (transformerless) inverters.
  • Pool pump on a VFD: Type F (or Type B if a smooth DC component is possible).
  • General lighting and power: 30 mA Type A on each final subcircuit; an RCBO isolates only the faulted circuit.
Disclaimer: Always check the local jurisdiction’s requirements and the appliance manufacturer’s datasheet. EV charger and solar PV circuits typically require Type B. Verify against AS/NZS 3000:2018 before final design.

Common questions

What is the difference between Type AC, A, F, and B RCDs?+

Type AC trips on AC residual currents only. Type A adds pulsating DC residual currents (e.g. from rectified loads with capacitors); this is the New Zealand minimum. Type F adds composite waveforms typical of variable frequency drives. Type B adds smooth DC residual currents (above 10 mA), which is required for many EV chargers and grid-connected solar inverters where the DC side can develop a true earth fault.

Does AS/NZS 3000 require RCDs on every circuit?+

In Australian domestic and residential installations, effectively yes. Clause 2.6.3.2.2 of AS/NZS 3000:2018 requires 30 mA RCD protection for all final subcircuits, which includes fixed and directly connected appliances. Non-domestic installations follow Clause 2.6.3.2.3.3, which requires 30 mA on final subcircuits rated up to 32 A supplying socket outlets, lighting, directly connected hand-held equipment, and directly connected equipment that presents an increased risk of electric shock. The calculator recommends a sensitivity for every circuit type, including fixed appliances.

When do I need a Type B RCD?+

Type B is required when the load can produce smooth DC residual current that would saturate or mask a Type A or F RCD. The most common cases are EV chargers without internal Type B detection (Mode 3 chargers above 16 A typically include Type B internally; smaller ones may not), grid-connected inverters with non-isolated topology, and some VFD installations. Confirm with the manufacturer datasheet; if a Type B is needed and you fit a Type A, the RCD may not detect a real DC fault.

Why has New Zealand mandated Type A RCDs?+

New Zealand AS/NZS 3000 amendments require Type A as the minimum because modern domestic loads (LED drivers, switchmode supplies, induction cooktops) produce pulsating DC residual currents that a Type AC cannot reliably detect. Type AC RCDs in New Zealand new installations are no longer compliant for socket outlet protection. Australia has not mandated this nationally yet, but Type A is recommended for all new work and is required for solar PV and EV charger circuits.

Are RCDs and RCBOs the same thing?+

No. An RCD detects residual (earth-leakage) current only and trips when leakage exceeds the rated sensitivity (e.g. 30 mA). An RCBO is an RCD combined with a miniature circuit breaker in a single device, providing both residual current protection and overload or short-circuit protection. RCBOs are generally preferred over a separate RCD plus MCB because they isolate only the affected circuit on a fault rather than tripping the whole switchboard subsection.

SparkyToolkit · iOS

On site? Get the same calcs on your phone.

SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.

Download on theApp Store

Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.

Related calculators