AS/NZS 3000 Section 5

Earthing System Calculator

Free earthing system calculator for AS/NZS 3000 Section 5. Soil resistivity, electrode design, max earth resistance, touch and step voltage. No login.

Inputs

Typical range: 10 to 10000 Ω·m (measured on-site)

Depth for rod; length for strip/plate/ring

Center depth (typically 1 to 3 m)

Electrical parameters

Prospective earth fault current (from distribution)

Protective device disconnection time (typ. 0.1 to 0.4 s)

Results

Earth Resistance

77.87

Ω

Touch voltage limit (≤50V typical)

38934.79990323499 V (<= 50)

Earth resistance limit (TN-C-S)

77.86959980646998 Ω (<= 10)

Step voltage limit

20000 V (<= 75)

Earth conductor size (adequate)

4 mm² (>= 4)

Single Electrode Resistance81.968 Ω
Grid Resistance (parallel)81.968 Ω
Practical Resistance77.870 Ω
Touch Voltage (Prospective)38934.8 V
Touch Voltage Limit50 V
Step Voltage20000.0 V
Step Voltage Limit75 V
Min Earth Conductor4 mm²

Touch voltage approaching limit: 38934.8V (limit: 50V)

Earth resistance approaching limit: 77.87Ω (limit: 10Ω)

Important: These results are indicative only. Earthing system design must be verified by a qualified electrical engineer in accordance with AS/NZS 3000:2018 Section 5. Earth resistance testing must be performed on-site with appropriate instrumentation.

Earthing System Design for AS/NZS 3000 Section 5

The earthing system bonds non-current-carrying metalwork to earth so that fault current returns through a low-impedance path and protective devices clear quickly. This calculator estimates ground resistance for common electrode types in the soil resistivity you specify, and flags touch and step voltage risks during a fault. All calculations follow AS/NZS 3000 Section 5 and the supporting equations from AS/NZS 3000 Appendix B.

How to calculate maximum earth resistance per AS/NZS 3000

AS/NZS 3000 does not specify a single maximum earth resistance value. Instead it requires the earth fault loop impedance (Zs) be low enough that the protective device disconnects within the time set in Table 5.1, typically 0.4 seconds for socket outlets up to 32 A, 5 seconds for fixed appliances and distribution circuits. The calculator works backwards from these limits to determine the maximum acceptable earth resistance for your circuit.

For most Multiple Earthed Neutral (MEN) installations the effective ceiling on the consumer earth electrode resistance works out to roughly 10 to 30 Ω, but the exact figure depends on the upstream supply impedance, the protective device type and rating, and whether the circuit feeds a socket outlet or a fixed load.

Earth fault loop impedance vs earth resistance

Earth resistance (Re) is the resistance of just the electrode-to-soil path. Earth fault loop impedance (Zs) is the resistance of the entire loop: phase conductor → load → fault → earth conductor → MEN link → transformer secondary → phase conductor again. Zs is what determines whether the protective device sees enough fault current to trip in time. The calculator computes both, plus the prospective fault current Ifault.

Soil resistivity testing: Wenner method walkthrough

The Wenner four-pin method is the industry-standard soil resistivity test. Drive four equally-spaced auxiliary electrodes into the ground in a straight line, inject a known AC current between the outer pair, and measure the voltage drop between the inner pair. The apparent soil resistivity (ρ) at depth ≈ a is:

ρ = 2π × a × R

where a is the electrode spacing in metres and R is the resistance reading in ohms. Repeat at spacings of 1, 2, 4, and 8 m to characterise resistivity at progressively deeper layers. Use the harmonic mean of these readings as your design value.

Earth electrode types and when to use each

  • Driven rod (1.2 to 2.4 m copper-clad steel): the default for residential and light commercial. Cheap, fast to install, effective in soils up to ≈ 200 Ω·m. Multiple rods in parallel for high-resistivity sites.
  • Plate (600 × 600 mm copper or galv. steel): when ground is too rocky to drive rods. Buried at 600 mm depth minimum. Lower contact area than a rod for the same depth.
  • Mesh / grid: at substations and large industrial sites. Provides equipotential bonding across a large area, critical for limiting touch and step voltages during a fault.
  • Ring earth (buried bare conductor around the building): common for lightning protection and high- resistivity sites. Often combined with rods at corners.

Touch and step voltage: what AS/NZS 3000 Section 5 actually requires

When fault current flows through the earth electrode, the soil around it sits at an elevated potential. Touch voltage is what a person feels between an exposed metal part (e.g. a switchboard frame) and the ground 1 m away, limited to 50 V AC under fault for installations accessible to ordinary persons. Step voltage is what a person feels between their two feet (1 m apart) standing on the ground near the electrode. The calculator flags either if it exceeds the safe limit for the disconnection time of the upstream protective device.

Disclaimer: Soil resistivity should be measured on site (Wenner or driven-rod method). MEN, TT, and TN-S system selection and bonding requirements must be verified by a qualified electrical engineer against AS/NZS 3000:2018 before final design.

Common questions

What is the maximum earth resistance allowed by AS/NZS 3000?+

AS/NZS 3000 does not set a single fixed maximum earth resistance. Instead it requires that the earth fault loop impedance be low enough that the protective device disconnects within the time required by Table 5.1 (typically 0.4 s for socket outlets ≤32 A, 5 s for fixed appliances). For most residential MEN systems this works out to an earth electrode resistance under about 30 Ω, but the actual ceiling depends on the supply system, protective device, and circuit configuration.

How do I test soil resistivity on site?+

The most common method is the Wenner four-electrode test. Drive four equally-spaced rods into the ground in a straight line, inject a known current between the outer two, and measure the voltage between the inner two. Soil resistivity (ρ) in Ω·m equals 2π × a × R, where a is the electrode spacing in metres and R is the measured resistance in ohms. Repeat at multiple spacings (1 m, 2 m, 4 m, 8 m) to characterise resistivity at different depths. Australian sandy and rocky soils typically range from 100 to 1000 Ω·m; clay and damp soils 10 to 100 Ω·m.

What is the difference between earth fault loop impedance and earth resistance?+

Earth resistance (Re) is the resistance of just the earth electrode-to-mass-of-earth path, measured in ohms. Earth fault loop impedance (Zs) is the total impedance of the entire fault loop, including phase conductor, earth conductor, transformer winding, supply earth, and the earth electrode all in series. Zs is what determines whether a fault current is high enough to trip the protective device. AS/NZS 3000 disconnection times are based on Zs, not Re alone.

Which earth electrode type should I use?+

Driven rods (1.2 to 2.4 m copper-clad steel) are the default for most residential and light commercial sites: cheap, fast to install, and effective in soils up to about 200 Ω·m. Plates are useful when ground is too rocky to drive rods. Earthing meshes (grids of buried bare conductors) are used at substations and large industrial sites where the touch and step voltage requirements demand a large equipotential area. Ring earths surround buildings; they are common for lightning protection and in installations with high soil resistivity.

How do touch and step voltage hazards arise?+

During an earth fault, current flowing through the soil creates a voltage gradient around the earth electrode. Touch voltage is the difference between an exposed conductive part (e.g. a metal switchboard frame) and a person's feet 1 m away, typically limited to 50 V AC under fault. Step voltage is the difference between two points on the ground 1 m apart, where a person's feet might be, typically limited to higher levels but still hazardous. AS/NZS 3000 Section 5 requires the earthing system be designed so neither limit is exceeded for the time the fault persists.

Does the calculator handle MEN, TT, and TN-S systems?+

Yes. Select the system type in the calculator and the maximum permissible earth resistance and required electrode design will adjust accordingly. MEN (Multiple Earthed Neutral) is the standard Australian configuration; TT systems (separate consumer earth, no neutral bond) are common in rural areas without local distribution earthing; TN-S systems use a dedicated earth conductor back to the source.

SparkyToolkit · iOS

On site? Get the same calcs on your phone.

SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.

Download on theApp Store

Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.

Related calculators