Earthing System Calculator
Free earthing system calculator for AS/NZS 3000 Section 5. Soil resistivity, electrode design, max earth resistance, touch and step voltage. No login.
Inputs
Typical range: 10 to 10000 Ω·m (measured on-site)
Depth for rod; length for strip/plate/ring
Center depth (typically 1 to 3 m)
▶Electrical parameters
Prospective earth fault current (from distribution)
Protective device disconnection time (typ. 0.1 to 0.4 s)
Results
Earth Resistance
77.87
Ω
Touch voltage limit (≤50V typical)
38934.79990323499 V (<= 50)
Earth resistance limit (TN-C-S)
77.86959980646998 Ω (<= 10)
Step voltage limit
20000 V (<= 75)
Earth conductor size (adequate)
4 mm² (>= 4)
Show the working
| Step | Working | Result | Reference |
|---|---|---|---|
| Single electrode resistance (rod) | R = rho / (2 x pi x L) x ln(4L/d) = 200 / (2 x pi x 2.5) x ln(4 x 2.5 / 0.0160) = 81.9680 ohm [rho 200 ohm.m, L 2.5 m, d 16 mm] | 81.9680 Ω | AS/NZS 3000:2018 Section 5.4.5.4 |
| Grid resistance (1 electrode(s) in parallel) | 1 electrode, so no parallel reduction: 81.9680 ohm | 81.9680 Ω | AS/NZS 3000:2018 Section 5.4.5.5 |
| Practical earth resistance (with spacing efficiency) | 81.9680 ohm x 0.95 efficiency factor = 77.8696 ohm | 77.8696 Ω | AS/NZS 3000:2018 5.4.5 |
| Touch voltage limit (TN-C-S, t=0.4s) | Table lookup: clearance time 0.4 s, TN-C-S, normal location = 50.0 V | 50.0 V | AS/NZS 3000:2018 Table 5.3(B) |
| Step voltage limit | 1.5 x 50.0 V touch limit = 75.0 V | 75.0 V | AS/NZS 3000:2018 Section 5.3.2 |
| Prospective touch voltage (V = I × R) | I=500 A x R=77.8696 ohm = 38934.80 V (limit 50.0 V) | 38934.80 V | AS/NZS 3000:2018 Section 5.3.2.3 |
| Step voltage (simplified) | 500 A x 200 ohm.m / (2 x 2.5 m) = 20000.00 V (limit 75.0 V) | 20000.00 V | AS/NZS 3000:2018 Section 5.3.2.3 |
| Minimum earth conductor size (adiabatic) | S = sqrt(I^2 x t) / k = sqrt(500^2 x 0.4 s) / 115 = 2.750 mm2 (copper, k = 115) | 2.750 mm² | AS/NZS 3000:2018 Appendix A |
| Earth conductor size (standard) | Next standard size at or above 2.750 mm2 from 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 = 4 mm2 | 4 mm² | Standard conductor sizes |
Standards referenced
- AS/NZS 3000:2018 Clause 5. Earthing and bonding (comprehensive earthing system requirements)
- AS/NZS 3000:2018 Clause 5.3.2.2. Indirect contact protection, touch voltage limits
- AS/NZS 3000:2018 Clause 5.3.2.3. Touch and step voltage calculations
- AS/NZS 3000:2018 Clause 5.4.5. Earth electrode resistance calculation methods
- AS/NZS 3000:2018 Clause 5.4.5.4. Formulas for various electrode types (rod, strip, plate, ring)
- AS/NZS 3000:2018 Clause Appendix A. Adiabatic equation for earth conductor sizing PLACEHOLDER
- AS/NZS 3008.1.1:2025 Clause Section 3.8. Cable selection and sizing for earth conductors
Lookup values used by these calculators are indicative and awaiting validation against the current standards. Confirm against your own licensed copy before relying on a result for design.
Touch voltage approaching limit: 38934.8V (limit: 50V)
Earth resistance approaching limit: 77.87Ω (limit: 10Ω)
Parameters
Every field on the form, what it feeds, the range accepted, and which fields only apply to certain electrode types. Some fields behave in ways that are not obvious from the label, so read the notes before relying on the output.
- Soil resistivityohm metres, 10 to 10000
- The single most influential input. It appears directly in every electrode resistance formula and in the step voltage expression, so the result scales linearly with it. Measure it on site with a Wenner four-pin test if you can. Typical Australian ranges are 20 to 100 for clay, 50 to 500 for loam, 100 to 2000 for sand, 100 to 3000 for gravel, and 1000 to 10000 for rock. Measure in the driest part of the year, because resistivity can double or worse in a dry summer.
- Soil typeclay, loam, sand, rock or gravel
- Reference only. It appears in the results for context but it does not enter any formula and it does not change the resistivity value used. Selecting rock while leaving resistivity at 200 ohm metres will calculate at 200 ohm metres. Set the resistivity number yourself.
- Electrode typerod, strip, plate or ring
- Chooses the resistance formula. Rod uses resistivity divided by 2 pi times length, times the natural log of 4 times length divided by diameter. Strip uses resistivity divided by pi times length, times the natural log of 2 times length divided by width. Plate uses resistivity divided by 4 times the square root of the plate area. Ring uses resistivity divided by 4 pi times the ring radius.
- Electrode lengthmetres, 0.5 to 100
- What this means depends on the electrode type. For a rod it is the driven depth. For a strip it is the buried run length. For a plate it is one side of the plate, paired with the width field to give the area. For the ring option it is fed into the ring formula as a diameter in millimetres, so a ring entry only makes sense if you treat this field as the ring diameter in millimetres rather than metres. That is a known quirk of the current implementation, so cross-check any ring result by hand.
- Electrode diametermillimetres, 8 to 50, rod only
- The diameter of the driven rod. It sits inside a natural logarithm, so its influence is weak: doubling the rod diameter reduces resistance by well under 20 percent, whereas doubling the rod length nearly halves it. Length beats girth every time. A typical Australian copper-clad steel rod is 16 millimetres.
- Electrode widthmillimetres, 50 to 2000, strip and plate only
- For a strip it is the tape width, which also sits inside a logarithm and therefore has modest effect. For a plate it multiplies the length to give the buried area, which sits under a square root, so it matters far more there.
- Burial depthmetres, 0.5 to 10
- The depth to the centre of the electrode. It is validated and it triggers a warning below 0.5 metres about unreliable earthing in dry conditions, but it does not appear in any resistance formula. Changing it will not change the calculated resistance. In reality, depth matters a great deal because deeper soil holds moisture through summer.
- Number of electrodescount, 1 to 100
- Parallel electrodes. The calculator divides the single electrode resistance by this number and then applies a flat 0.95 practical factor. Real parallel electrodes suffer mutual interference and never achieve a straight division, especially when spaced closer than about twice their length, so treat multi-electrode results as optimistic.
- Electrode spacingmetres, not exposed on this form
- The underlying engine accepts a spacing value and has a branch that penalises closely spaced electrodes, but the web form does not send one, so that branch never runs. Parallel electrodes are modelled as a plain division by the count.
- Fault currentamps, 10 to 100000
- The prospective earth fault current that flows through the electrode. It drives three outputs: the prospective touch voltage, which is this current times the practical earth resistance, the step voltage, and the minimum earth conductor size. Be careful what you enter here. On an Australian MEN installation most fault current returns through the neutral, not through the electrode, so putting a switchboard fault level into this field will produce enormous and unrealistic touch voltages.
- Fault clearance timeseconds, 0.05 to 10
- The time the protective device takes to clear. It sets the touch voltage limit band and it appears under the square root in the conductor sizing equation. The bands used are 50 volts at 0.4 seconds and longer, 65 volts from 0.2 up to 0.4 seconds, and 80 volts from 0.1 up to 0.2 seconds. Shorter clearance times permit higher touch voltages because the body tolerates a brief shock better than a sustained one.
- System typeTN-S, TN-C-S, TT or IT
- Selects the earth resistance limit the result is graded against: 10 ohms for TN-S, TN-C-S and TT, and 1000 ohms for IT. That is the only thing this field changes. It does not alter the touch voltage limit, the step voltage limit or the conductor size. Australian MEN installations correspond most closely to TN-C-S.
Assumptions and limits
This is a first-pass electrode sizing tool built on classical soil resistance formulas. It is deliberately pessimistic about touch and step voltage, and understanding why is essential to reading the output correctly.
What the calculator assumes
- Uniform, single-layer soil. One resistivity value for the whole volume around the electrode. Real ground is layered, and a rod that passes from dry sand into damp clay behaves nothing like the single-layer model predicts. Seasonal variation is not modelled either.
- Parallel electrodes divide cleanly. Resistance is divided by the electrode count and then multiplied by a flat 0.95 factor. There is no mutual resistance term and no spacing penalty, because the form does not collect spacing. Real arrays of closely spaced rods deliver considerably less than the ideal division.
- Touch voltage is the full electrode voltage rise. It is calculated as fault current times practical earth resistance, which is the whole ground potential rise rather than the fraction a person would actually bridge. There is no surface potential profile, no body impedance model, no allowance for footwear, and no allowance for a crushed rock surface layer. Critically, there is no credit for the MEN connection or the supply neutral return path, so for a normal Australian MEN installation this figure is far more onerous than the real hazard. Expect the touch voltage check to fail on ordinary inputs.
- Step voltage is a single simplified gradient. Fault current times resistivity, divided by twice the electrode length. It is a rough indicator, not an IEEE 80 surface potential calculation, and the limit it is compared against is simply 1.5 times the touch voltage limit.
- Touch voltage limits are banded by clearance time only. 50, 65 or 80 volts. There is no distinction between ordinary locations and special locations such as bathrooms, pools or medical areas, where lower limits apply.
- Conductor sizing is copper only. The adiabatic equation runs with a fixed material constant of 115 and no aluminium option. Use the earth conductor calculator if you need aluminium or a different constant.
- The formulas are classical, and the limits are indicative. The resistance expressions are standard textbook forms. The touch voltage bands, the resistance limits by system type and the material constant have not been transcribed from a licensed copy of AS/NZS 3000.
What this should not be used for
- Substation or high voltage earth grid design. That is the domain of IEEE Standard 80, AS 2067 and the ENA EG-0 framework, all of which model surface potential, grid geometry, split factors and decrement factors that this tool does not.
- Certifying that touch and step voltages are safe. The touch voltage output here is a worst-case ground potential rise and will read alarmingly high on realistic fault currents.
- Replacing a fall-of-potential test. Calculated resistance is a design estimate. The installed value must be measured and recorded.
- Earth fault loop impedance and automatic disconnection verification, which involve the whole loop rather than just the electrode. Use the cable sizing calculator for the loop length check.
- Lightning protection earthing to AS 1768, which has its own electrode and bonding requirements.
- Ring electrode design until the length field behaviour noted above is verified by hand.
None of this has been validated by a chartered professional engineer. Verify every result against the current edition of AS/NZS 3000 Section 5, measure the installed earth resistance on completion, and have the responsible person for the installation sign off the final design.
Worked examples
Three configurations run end to end: a single rod in average soil, an array of rods in good clay, and a horizontal strip. The arithmetic is written out so you can reproduce it.
Example 1: single 2.5 metre rod in loam, and why the touch voltage check fails
A single 16 millimetre copper-clad rod driven 2.5 metres into loam of 200 ohm metres, on a TN-C-S system, assessed against a 500 amp earth fault cleared in 0.4 seconds.
| Soil resistivity | 200 Ω·m |
|---|---|
| Electrode type | Rod |
| Electrode length | 2.5 m |
| Electrode diameter | 16 mm |
| Number of electrodes | 1 |
| Fault current | 500 A |
| Fault clearance time | 0.4 s |
| System type | TN-C-S |
Step 1. Resistivity divided by 2 pi times length: 200 divided by 15.708 equals 12.732.
Step 2. The log term: 4 times 2.5 divided by 0.016 metres equals 625, and the natural log of 625 is 6.438.
Step 3. Single rod resistance: 12.732 times 6.438 equals 81.97 ohms.
Step 4. One electrode, so the grid resistance is the same 81.97 ohms. Applying the 0.95 practical factor gives 77.87 ohms.
Step 5. Touch voltage: 500 times 77.87 equals 38935 volts, against a 50 volt limit at 0.4 seconds.
Step 6. Step voltage: 500 times 200, divided by 2 times 2.5, equals 20000 volts, against a 75 volt limit.
Step 7. Earth conductor: the square root of 500 squared times 0.4 is 316.23, divided by 115 gives 2.75 square millimetres, which rounds up to 4 square millimetres.
FAIL on earth resistance, touch voltage and step voltage. 77.87 ohms is well above the 10 ohm limit for a TN-C-S system, and the voltage figures are enormous.
This is the result you get from realistic inputs, and it needs interpreting rather than acting on. A 500 amp fault does not flow through a 78 ohm electrode in the first place; at 230 volts that path would carry about 3 amps. On a real MEN installation almost all of the fault current returns through the neutral, and the electrode carries very little. What this example genuinely tells you is that a single 2.5 metre rod in 200 ohm metre soil gives roughly 78 ohms of electrode resistance, which is too high on its own and needs either more rods, deeper rods, or better soil.
Example 2: eight 6 metre rods in wet clay
A rural TT installation in clay of 20 ohm metres uses eight 16 millimetre rods driven 6 metres each. The earth fault current through the electrode is limited to 30 amps and the RCD clears in 0.4 seconds.
| Soil resistivity | 20 Ω·m |
|---|---|
| Electrode type | Rod |
| Electrode length | 6 m |
| Electrode diameter | 16 mm |
| Number of electrodes | 8 |
| Fault current | 30 A |
| Fault clearance time | 0.4 s |
| System type | TT |
Step 1. Resistivity divided by 2 pi times length: 20 divided by 37.699 equals 0.5305.
Step 2. The log term: 4 times 6 divided by 0.016 equals 1500, and the natural log of 1500 is 7.313.
Step 3. Single rod resistance: 0.5305 times 7.313 equals 3.88 ohms.
Step 4. Eight in parallel: 3.88 divided by 8 equals 0.485 ohms. Applying the 0.95 practical factor gives 0.461 ohms.
Step 5. Touch voltage: 30 times 0.461 equals 13.82 volts, against a 50 volt limit.
Step 6. Step voltage: 30 times 20, divided by 2 times 6, equals 50 volts, against a 75 volt limit.
Step 7. Earth conductor: the square root of 30 squared times 0.4 is 18.97, divided by 115 gives 0.16 square millimetres, which rounds up to the smallest standard size of 1 square millimetre. In practice a minimum size rule will govern instead.
PASS on all four checks. 0.461 ohms is comfortably inside the 10 ohm limit, touch voltage sits at 13.82 volts and step voltage at 50 volts. Note the leverage of soil quality: going from 200 to 20 ohm metres and from 2.5 to 6 metre rods took a single rod from 82 ohms to 3.88 ohms before any parallel benefit was counted.
Example 3: 20 metre buried strip, and a marginal resistance result
A 50 millimetre wide copper tape is buried in a 20 metre trench in soil of 100 ohm metres, serving a TN-S installation with a 200 amp earth fault cleared in 0.4 seconds.
| Soil resistivity | 100 Ω·m |
|---|---|
| Electrode type | Strip |
| Electrode length | 20 m |
| Electrode width | 50 mm |
| Number of electrodes | 1 |
| Fault current | 200 A |
| Fault clearance time | 0.4 s |
| System type | TN-S |
Step 1. Resistivity divided by pi times length: 100 divided by 62.832 equals 1.5915.
Step 2. The log term: 2 times 20 divided by 0.05 metres equals 800, and the natural log of 800 is 6.685.
Step 3. Strip resistance: 1.5915 times 6.685 equals 10.64 ohms.
Step 4. Applying the 0.95 practical factor gives 10.11 ohms.
Step 5. Touch voltage: 200 times 10.11 equals 2021 volts, against a 50 volt limit.
Step 6. Step voltage: 200 times 100, divided by 2 times 20, equals 500 volts, against a 75 volt limit.
Step 7. Earth conductor: the square root of 200 squared times 0.4 is 126.49, divided by 115 gives 1.10 square millimetres, which rounds up to 1.5 square millimetres.
FAIL on earth resistance by the narrowest possible margin, 10.11 ohms against a 10 ohm limit, and fail on touch and step voltage for the ground potential rise reasons described in Example 1.
The resistance result is the useful one here. Extending the trench to 25 metres drops the strip resistance to 8.80 ohms, or 8.36 ohms after the practical factor, which passes. Adding a second parallel 20 metre run instead brings it to roughly 5.05 ohms. Length is the lever: the 50 millimetre tape width sits inside a logarithm, and doubling it to 100 millimetres would only shave about 10 percent off the resistance.
Earthing System Design for AS/NZS 3000 Section 5
The earthing system bonds non-current-carrying metalwork to earth so that fault current returns through a low-impedance path and protective devices clear quickly. This calculator estimates ground resistance for common electrode types in the soil resistivity you specify, and flags touch and step voltage risks during a fault. All calculations follow AS/NZS 3000 Section 5 and the supporting equations from AS/NZS 3000 Appendix B.
How to calculate maximum earth resistance per AS/NZS 3000
AS/NZS 3000 does not specify a single maximum earth resistance value. Instead it requires the earth fault loop impedance (Zs) be low enough that the protective device disconnects within the time set in Clause 5.7.2, typically 0.4 seconds for final subcircuits supplying socket outlets rated up to 63 A, hand-held Class I equipment or portable equipment, and 5 seconds for other circuits including submains and circuits supplying fixed or stationary equipment. Table 8.1 gives the matching maximum Zs values. The calculator works backwards from these limits to determine the maximum acceptable earth resistance for your circuit.
For most Multiple Earthed Neutral (MEN) installations the effective ceiling on the consumer earth electrode resistance works out to roughly 10 to 30 Ω, but the exact figure depends on the upstream supply impedance, the protective device type and rating, and whether the circuit feeds a socket outlet or a fixed load.
Earth fault loop impedance vs earth resistance
Earth resistance (Re) is the resistance of just the electrode-to-soil path. Earth fault loop impedance (Zs) is the resistance of the entire loop: phase conductor → load → fault → earth conductor → MEN link → transformer secondary → phase conductor again. Zs is what determines whether the protective device sees enough fault current to trip in time. The calculator computes both, plus the prospective fault current Ifault.
Soil resistivity testing: Wenner method walkthrough
The Wenner four-pin method is the industry-standard soil resistivity test. Drive four equally-spaced auxiliary electrodes into the ground in a straight line, inject a known AC current between the outer pair, and measure the voltage drop between the inner pair. The apparent soil resistivity (ρ) at depth ≈ a is:
ρ = 2π × a × R
where a is the electrode spacing in metres and R is the resistance reading in ohms. Repeat at spacings of 1, 2, 4, and 8 m to characterise resistivity at progressively deeper layers. Use the harmonic mean of these readings as your design value.
Earth electrode types and when to use each
- Driven rod (1.2 to 2.4 m copper-clad steel): the default for residential and light commercial. Cheap, fast to install, effective in soils up to ≈ 200 Ω·m. Multiple rods in parallel for high-resistivity sites.
- Plate (600 × 600 mm copper or galv. steel): when ground is too rocky to drive rods. Buried at 600 mm depth minimum. Lower contact area than a rod for the same depth.
- Mesh / grid: at substations and large industrial sites. Provides equipotential bonding across a large area, critical for limiting touch and step voltages during a fault.
- Ring earth (buried bare conductor around the building): common for lightning protection and high- resistivity sites. Often combined with rods at corners.
Touch and step voltage: where the requirements actually come from
When fault current flows through the earth electrode, the soil around it sits at an elevated potential. Touch voltage is what a person feels between an exposed metal part (e.g. a switchboard frame) and the ground 1 m away, limited to 50 V AC under fault for installations accessible to ordinary persons. Step voltage is what a person feels between their two feet (1 m apart) standing on the ground near the electrode. The calculator flags either if it exceeds the safe limit for the disconnection time of the upstream protective device.
Common questions
What is the maximum earth resistance allowed by AS/NZS 3000?+
AS/NZS 3000 does not set a single fixed maximum earth resistance. Instead it requires that the earth fault loop impedance be low enough that the protective device disconnects within the times in Clause 5.7.2 (0.4 s for final subcircuits supplying socket outlets rated up to 63 A, hand-held Class I equipment, or portable equipment, and 5 s for other circuits including submains and final subcircuits supplying fixed or stationary equipment). Table 8.1 lists the corresponding maximum Zs values for common MCBs and fuses. For most residential MEN systems this works out to an earth electrode resistance under about 30 ohms, but the actual ceiling depends on the supply system, protective device, and circuit configuration.
How do I test soil resistivity on site?+
The most common method is the Wenner four-electrode test. Drive four equally-spaced rods into the ground in a straight line, inject a known current between the outer two, and measure the voltage between the inner two. Soil resistivity (ρ) in Ω·m equals 2π × a × R, where a is the electrode spacing in metres and R is the measured resistance in ohms. Repeat at multiple spacings (1 m, 2 m, 4 m, 8 m) to characterise resistivity at different depths. Australian sandy and rocky soils typically range from 100 to 1000 Ω·m; clay and damp soils 10 to 100 Ω·m.
What is the difference between earth fault loop impedance and earth resistance?+
Earth resistance (Re) is the resistance of just the earth electrode-to-mass-of-earth path, measured in ohms. Earth fault loop impedance (Zs) is the total impedance of the entire fault loop, including phase conductor, earth conductor, transformer winding, supply earth, and the earth electrode all in series. Zs is what determines whether a fault current is high enough to trip the protective device. AS/NZS 3000 disconnection times are based on Zs, not Re alone.
Which earth electrode type should I use?+
Driven rods (1.2 to 2.4 m copper-clad steel) are the default for most residential and light commercial sites: cheap, fast to install, and effective in soils up to about 200 Ω·m. Plates are useful when ground is too rocky to drive rods. Earthing meshes (grids of buried bare conductors) are used at substations and large industrial sites where the touch and step voltage requirements demand a large equipotential area. Ring earths surround buildings; they are common for lightning protection and in installations with high soil resistivity.
How do touch and step voltage hazards arise?+
During an earth fault, current flowing through the soil creates a voltage gradient around the earth electrode. Touch voltage is the difference between an exposed conductive part (e.g. a metal switchboard frame) and a person's feet 1 m away, typically limited to 50 V AC under fault. Step voltage is the difference between two points on the ground 1 m apart, where a person's feet might be, typically limited to higher levels but still hazardous. AS/NZS 3000 Section 5 requires the earthing system be designed so neither limit is exceeded for the time the fault persists.
Does the calculator handle MEN, TT, and TN-S systems?+
Yes. Select the system type in the calculator and the maximum permissible earth resistance and required electrode design will adjust accordingly. MEN (Multiple Earthed Neutral) is the standard Australian configuration; TT systems (separate consumer earth, no neutral bond) are common in rural areas without local distribution earthing; TN-S systems use a dedicated earth conductor back to the source.
On site? Get the same calcs on your phone.
SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.
Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.
Related calculators