IEEE 1584:2018

Arc Flash Calculator

Free arc flash calculator for IEEE 1584:2018 incident energy, arc flash boundary, and PPE category. Built for Australian conditions. No login. No watermark.

Inputs

Line-to-line or phase-to-neutral

Maximum available short-circuit current

Time until protection operates

Distance from arc source (typically 450 mm)

Enclosed increases incident energy

Results

Incident Energy

1340.33

cal/cm²

Required PPE Category

DANGEROUS

System Voltage0.4 kV
Bolted Fault Current20 kA
Arc Duration0.5 s
Arc Current (Estimated)16.0 kA
Arc Flash Boundary15039 mm
Arc Duration (ms)500 ms

Recommended PPE

DANGEROUS — Do NOT work live. Arc flash energy exceeds safe exposure limits. Implement engineering controls (insulation, guarding, remote operation) or de-energize.

High Arc Flash Hazard

Incident energy >25 cal/cm². Avoid live work if possible. Use remote racking or other de-energized methods.

Important: These results are indicative only. Arc flash hazard analysis must be performed by a qualified electrical engineer in accordance with IEEE 1584:2018 and AS/NZS 3000:2018. All calculations must be verified and documented in hazard labels before live work.

Arc Flash Analysis for IEEE 1584:2018

Arc flash is the sudden release of thermal and radiant energy during an electrical fault. It can reach temperatures of 19,000 °C in milliseconds and produce pressure waves strong enough to throw a worker across a switch room. This calculator implements the IEEE 1584:2018 model to determine the incident energy at a defined working distance, the arc flash boundary, and the corresponding PPE category required to keep a worker survivable.

Arc flash calculation walkthrough

A typical analysis follows six steps:

  1. Bolted fault current. The prospective short-circuit current at the equipment, calculated from source impedance, transformer impedance, and cable impedances.
  2. Arc duration. The time the upstream protective device takes to clear the fault, looked up from its operating curve at the bolted fault current.
  3. Electrode configuration. VCB, VCBB, HCB, VOA, or HOA. Matches your equipment geometry.
  4. Gap between conductors. Typically 32 mm for LV switchgear, larger for MV.
  5. Working distance. 455 mm for LV per IEEE 1584 Table 9, longer for higher voltages.
  6. Solve. The calculator applies the IEEE 1584 model and returns incident energy, boundary, and PPE category.

Electrode configurations explained

  • VCB. Vertical Conductors in a Box. Most common for LV switchboards. Plasma jet directs out of the box toward the worker.
  • VCBB. Vertical Conductors in a Box with Barrier. Same as VCB but with an insulating barrier; reduces incident energy 5 to 20%.
  • HCB. Horizontal Conductors in a Box. Used when bus bars run horizontally inside enclosed switchgear.
  • VOA. Vertical Open Air. Outdoor bus bar arrangements. Lower incident energy than enclosed for the same fault current.
  • HOA. Horizontal Open Air. Outdoor horizontal conductors. Lowest incident energy of the five.

PPE category selection (NFPA 70E)

The calculated incident energy maps to one of four categories:

  • Category 1 (≤ 1.2 cal/cm²): arc-rated long- sleeve shirt + pants, safety glasses, hard hat, hearing protection, leather gloves.
  • Category 2 (1.2 to 8 cal/cm²): arc-rated shirt + pants OR coverall, arc-rated face shield with balaclava OR hood, hearing protection.
  • Category 3 (8 to 25 cal/cm²): multi-layer arc flash suit, hood, gloves; total system rating ≥ incident energy.
  • Category 4 (> 25 cal/cm²): full hazmat-style arc suit + SCBA. Consider de-energising before any work at this level.

How to reduce arc flash hazard

Three levers, in order of effectiveness:

  1. De-energise before work. Always the first option per AS/NZS 4836.
  2. Lower the arc duration by reducing upstream relay settings, within selectivity constraints. Halving arc time roughly halves incident energy.
  3. Increase working distance via remote racking, live-line tools, or insulating barriers. Incident energy falls with the square of distance.
Disclaimer: Arc flash hazard analysis must be performed by a qualified electrical engineer in accordance with IEEE 1584:2018, AS/NZS 3000:2018, and AS/NZS 4836. Hazard labels must be updated whenever upstream protection or system topology changes.
SparkyToolkit · iOS

On site? Get the same calcs on your phone.

SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.

Download on theApp Store

Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.

Related calculators