AS/NZS 2293.1

Emergency Lighting Calculator

Luminaire count, exit signs, spacing, and battery sizing for emergency lighting per AS/NZS 2293.1.

Inputs

Total enclosed floor area served by emergency system

Maximum travel distance from furthest point to exit

AS/NZS 2293.1 Clause 6.2.2; includes 25% aging margin

Results

Emergency Luminaires Required

50

units

Minimum illumination (floor level)

1.95 lux (Limit: 1 lux >=)

Minimum illumination (open areas)

20 lux (Limit: 0.2 lux >=)

Maximum luminaire spacing

0.8 m (Limit: 4 m <=)

Exit sign coverage

2 signs (Limit: 2 signs >=)

Battery duration capacity

17 Ah (Limit: 11.323529411764707 Ah >=)

Luminaire Count50
Exit Signs2
Total Load154.0 W
Battery Capacity17.0 Ah
Luminaire Spacing0.80 m
Floor Level Illumination1.95 lux
Open Area Illumination20.00 lux
Show the working
Step by step derivation of the result
StepWorkingResultReference
Luminaire Count Calculationmax(ceil(40 m / 4 m) = 10, ceil(500 m2 / 10 m2) = 50) = 50 = 50 units50 unitsAS/NZS 2293.1:2017 Clause 5.2.2
Exit Sign Countceil((2 exits + 0 area signs for 500 m2) x 1 [commercial]) = 2 signs2 signsAS/NZS 2293.1:2017 Clause 5.3
Total Emergency Lighting Load50 luminaires x 3 W + 2 signs x 2 W = 154.0 W154.0 WCalculation basis
Battery Capacity154.0 W / (0.85 x 24 V) = 7.55 A; 7.55 A x (90 min / 60 x 1.5 aging factor = 2.25 h) = 16.99 Ah, rounded up to 17.0 Ah17.0 AhAS/NZS 2293.1:2017 Clause 6.2.2
Luminaire Spacing40 m / 50 luminaires = 0.80 m, max allowed 4 m0.80 mAS/NZS 2293.1:2017 Clause 5.2.2
Illumination at Floor Level(50 luminaires x 30 lux) / 500 m2 x 0.65 floor factor = 1.95 lux, minimum required 1 lux1.95 luxAS/NZS 2293.1:2017 Table 3.1
Illumination in Open Areas50 luminaires x 0.4 lux per luminaire = 20.00 lux, minimum required 0.2 lux20.00 luxAS/NZS 2293.1:2017 Table 3.1

Standards referenced

  • AS/NZS 2293.1:2017 Clause 5.2.2. Minimum illumination levels and spacing requirements for escape route lighting
  • AS/NZS 2293.1:2017 Clause 5.3. Emergency exit sign requirements
  • AS/NZS 2293.1:2017 Clause 6.2.2. Battery system sizing and duration requirements
  • AS/NZS 2293.1:2017 Table Table 3.1. Minimum illumination levels for different areas

Lookup values used by these calculators are indicative and awaiting validation against the current standards. Confirm against your own licensed copy before relying on a result for design.

Important: These results are indicative only. Emergency lighting systems must be designed and verified by a qualified electrical engineer in accordance with AS/NZS 2293.1:2017 before installation. Photometric verification and product selection must be confirmed on-site.

Emergency Lighting Design Guide for AS/NZS 2293.1

Emergency lighting is a life safety system that provides illumination on escape routes when the normal mains supply fails. In Australia and New Zealand, emergency lighting design, installation, and maintenance are governed by AS/NZS 2293.1 (design and installation) and AS/NZS 2293.2 (inspection and maintenance). The standard applies to all buildings required by the Building Code of Australia (BCA) to have emergency lighting, including commercial offices, retail premises, hospitals, aged care facilities, multi-storey residential buildings, and places of public assembly. This calculator helps you estimate the number of emergency luminaires required for a given floor area, the placement of illuminated exit signs, and the battery capacity needed to maintain the required light levels for the full 90 minute duration.

Key concepts

  • Minimum illumination levels. AS/NZS 2293.1 requires a minimum of 0.2 lux on the floor along the centre line of escape routes, and 1 lux at changes of direction, intersections, stairways, and within 2 metres of exit doors. These levels must be achieved at the end of the rated battery duration (90 minutes), not just at initial switch-on when lumen output is highest.
  • Maintained vs non-maintained luminaires. Maintained emergency luminaires operate continuously as part of the normal room lighting and switch to battery power during a mains failure. Non-maintained luminaires are off during normal operation and activate only when the supply fails. AS/NZS 2293.1 requires maintained luminaires in places of public entertainment such as cinemas, theatres, and concert venues.
  • Battery duration and sizing. The minimum battery duration is 90 minutes for most occupancies. The battery must be sized to deliver the required lumen output for the full duration at end-of-life capacity (typically 80 percent of initial capacity after 4 years). Central battery systems and individual self-contained luminaires are both acceptable, with different trade-offs in maintenance and reliability.
  • Exit sign requirements. Illuminated exit signs must be installed at every required exit and along escape routes so that at least one sign is visible from any point on the path of travel. Signs must comply with AS/NZS 2293.1 and the BCA for size, pictogram design (running man), colour (green and white), and mounting height. Photoluminescent signs are permitted only in specific low-risk occupancies.

Common scenarios

  1. Multi-storey office building. A 10-storey office tower with open plan floors, fire stairs, and a basement car park. Emergency luminaires are required in all corridors, stairwells, lobbies, and the car park. Exit signs are placed at each stairwell entry, lift lobby, and floor exit. The fire stairs typically require higher illumination (1 lux minimum on treads) because occupants are moving on uneven surfaces. Self-contained luminaires with individual batteries are common for office fitouts because they avoid the cost of running dedicated wiring back to a central battery room.
  2. Hospital or aged care facility. Healthcare buildings have extended duration requirements and higher illumination levels in patient care areas. Staff must be able to read medication labels and operate equipment during a power failure. Central battery systems with monitored circuits are preferred for reliability, and the testing regime under AS/NZS 2293.2 is more stringent due to the vulnerable occupant population.
  3. Retail shopping centre. Large open floor plates with high ceilings and multiple exit paths. The challenge is achieving 0.2 lux across wide open areas where luminaire spacing must account for the ceiling height and beam spread. Exit sign placement must ensure visibility above shelving and display fixtures. Places of public entertainment within the centre (such as cinemas) require maintained emergency luminaires.
Disclaimer: Final emergency lighting design must be commissioned and tested per AS/NZS 2293.2. Annual maintenance and 6-monthly testing are mandatory.

Parameters

Every field this calculator accepts, what it means, the range it accepts, and how it feeds the result. Nothing else is used: if a factor is not in this list, the calculator does not know about it.

Building type (commercial, industrial, residential, assembly)
A coarse occupancy risk category. It applies a multiplier to the exit sign count only: residential 0.8, commercial 1.0, industrial 1.2, assembly 1.5. It does not change the luminaire count, the load, or the battery size. If exit signs are turned off, this field has no effect at all.
Floor area (square metres, 10 to 50,000)
Total enclosed floor area served by the emergency lighting system. Drives the area based luminaire count at one luminaire per 10 square metres, and adds one extra exit sign per 2,000 square metres once the area passes 1,000 square metres. Areas above 50,000 square metres raise a warning to zone the system. On any large floor plate this field, not the path length, is what sets the luminaire count.
Number of exits (whole number, 1 to 20)
Count of required exits from the area. Sets the base exit sign count before the area addition and the building type multiplier, and is also the limit for the exit sign coverage check. More than 20 raises a warning to check the building layout.
Path length to exit (metres, 5 to 500)
The longest single travel distance from the furthest occupied point to an exit. This is one route, not the sum of every escape route in the building. It sets the spacing based luminaire count as the path length divided by the 4 metre maximum spacing, rounded up, and it is the numerator in the reported spacing. Above 200 metres the tool warns about intermediate signage; above 500 metres it warns that the travel distance itself needs checking.
Ceiling height (metres, 2 to 15)
Mounting height of the luminaires above the floor. It has one single effect: if the height is greater than 4.0 metres, one extra luminaire is added to the count. Exactly 4.0 metres does not trigger it. Below 2.4 metres and above 10 metres the tool raises warnings about distribution, and above 8 metres it warns about aiming, but none of those warnings change the numbers.
Emergency exit signs required (tick box)
When ticked, exit signs are counted and 2 watts per sign is added to the load. When unticked, the sign count is zero, no sign load is added, and the exit sign coverage check will report a fail whenever the number of exits is 1 or more. Untick it only when you are sizing luminaires alone and intend to ignore that check.
Battery duration (90 or 120 minutes)
Rated emergency operating time. Only these two values are accepted. Each carries a bundled factor that includes the battery ageing allowance: 90 minutes uses 1.5 and 120 minutes uses 2.0. The effective discharge time used in the sizing is therefore 2.25 hours for a 90 minute system and 4.0 hours for a 120 minute system.

Assumptions and limits

This calculator is a sizing estimator, not a lighting design. Here is exactly what it assumes and where it stops.

What it assumes

  • A generic LED luminaire of 3 watts and 300 lumens. There is no product selection and no photometric data. Every luminaire in the count is assumed identical. Exit signs are assumed to draw 2 watts each.
  • A 24 volt direct current battery system at 85 percent efficiency. Battery current is the total load in watts divided by 0.85 times 24 volts. Capacity is that current times the effective discharge hours, rounded up to the next half amp hour. The result is a nominal amp hour figure. There is no depth of discharge limit, no end of life capacity correction beyond the bundled ageing factor, no temperature correction, and no distinction between sealed lead acid, nickel cadmium or lithium chemistries.
  • Luminaire count is the greater of two coarse rules. Path length divided by 4 metres, or floor area divided by 10 square metres, whichever is larger, plus one if the ceiling is over 4 metres. The 10 square metre coverage figure is a rule of thumb held in the engine, not a photometric result, and on large areas it produces counts well above what a proper layout with real photometry would need.
  • Illumination outputs are proportional stand ins. Floor level lux is the luminaire count times 30, divided by the floor area, times 0.65. Open area lux is the luminaire count times 0.4. There is no luminaire intensity distribution, no room surface reflectance, no maintenance factor, no spacing to height ratio and no point by point calculation. These numbers indicate whether the count is in the right ballpark; they are not illuminance predictions.
  • Spacing is an average, not a layout. The reported spacing is the path length divided by the total luminaire count, so it falls well below 4 metres whenever the area rule dominates. It does not describe where the luminaires actually go.
  • The illumination thresholds used in the checks are indicative. The engine holds 1 lux for escape routes and 0.2 lux for open areas. These figures are held in code as indicative values, not transcribed from a licensed copy of AS/NZS 2293.1 Table 3.1. Read the current table before relying on a pass.

What it does not do

  • It does not classify the building or determine whether emergency lighting is required at all. That comes from the National Construction Code and the building classification.
  • It does not distinguish maintained from non maintained luminaires, or self contained units from a central battery system. The load and battery figures assume one pooled battery at 24 volts.
  • It does not place luminaires or signs, check exit sign viewing distances, sign size, mounting height or legend, or verify sight lines around obstructions.
  • It does not size the wiring to the luminaires, the submain, the protective devices, or the charger supply, and it does not address the monitoring or testing arrangements required by AS/NZS 2293.2.
  • It does not produce a compliance certificate and it is not a substitute for photometric software and a designed layout.

Every result should be checked against the current edition of AS/NZS 2293.1 and AS/NZS 2293.2, and signed off by the person responsible for the installation. Nothing here is validated or certified, and the underlying figures have not been reviewed by a chartered professional engineer.

Worked examples

Three complete runs through the calculator, with every intermediate figure shown, so you can check the tool against your own arithmetic.

Example 1. Open plan office floor, 90 minute duration

A single commercial office floor of 500 square metres with two required exits, a longest travel path of 40 metres, and a 3 metre ceiling. Exit signs are required and the system is a standard 90 minute duration.

Building typeCommercial
Floor area500 m²
Number of exits2
Path length to exit40 m
Ceiling height3 m
Battery duration90 min

Working

  1. Spacing rule: 40 m / 4 m = 10 luminaires.
  2. Area rule: 500 m² / 10 m² = 50 luminaires.
  3. Take the larger: 50. Ceiling is 3 m, not over 4 m, so no extra unit. Count = 50.
  4. Exit signs: 2 exits, area is not over 1,000 m² so no area addition, commercial multiplier 1.0, giving 2 signs.
  5. Load: 50 x 3 W + 2 x 2 W = 154 W.
  6. Battery current: 154 / (0.85 x 24) = 7.55 A.
  7. Discharge time: 90 / 60 x 1.5 = 2.25 h.
  8. Capacity: 7.55 x 2.25 = 16.99 Ah, rounded up to 17.0 Ah.
  9. Spacing: 40 / 50 = 0.80 m.
  10. Floor lux: 50 x 30 / 500 x 0.65 = 1.95 lux. Open area lux: 50 x 0.4 = 20.0 lux.

Result. 50 luminaires, 2 exit signs, 154 W, 17.0 Ah at 24 volts. Floor illumination 1.95 lux against a 1 lux limit, open area 20.0 lux against 0.2 lux, spacing 0.80 m against a 4 m maximum, sign coverage 2 against 2, battery 17.0 Ah against the 11.32 Ah bare duration figure. All five checks pass.

Example 2. Industrial warehouse, high bay, 120 minute duration

A 2,000 square metre warehouse with four exits, a 60 metre longest travel path and a 6 metre ceiling. Extended 120 minute duration. This example shows the high ceiling addition and the industrial sign multiplier.

Building typeIndustrial
Floor area2,000 m²
Number of exits4
Path length to exit60 m
Ceiling height6 m
Battery duration120 min

Working

  1. Spacing rule: 60 / 4 = 15. Area rule: 2,000 / 10 = 200. Larger is 200.
  2. Ceiling 6 m is over 4 m, so add one unit. Count = 201.
  3. Exit signs: 4 exits, plus 2,000 / 2,000 = 1 area sign, giving 5, times the industrial multiplier 1.2 = 6.0, rounded up to 6 signs.
  4. Load: 201 x 3 W + 6 x 2 W = 615 W.
  5. Battery current: 615 / (0.85 x 24) = 30.15 A.
  6. Discharge time: 120 / 60 x 2.0 = 4.00 h.
  7. Capacity: 30.15 x 4.00 = 120.59 Ah, rounded up to 121.0 Ah.
  8. Spacing: 60 / 201 = 0.30 m. Floor lux: 201 x 30 / 2,000 x 0.65 = 1.96 lux.

Result. 201 luminaires, 6 exit signs, 615 W, 121.0 Ah. All five checks pass. Note that the area rule has produced 201 luminaires for a warehouse, which is roughly one unit every 10 square metres across the whole slab. A real high bay design with 6 metre mounting and wide beam optics would use a fraction of that. Treat this as an upper bound and confirm with a photometric layout.

Example 3. Assembly hall, ceiling exactly at the 4 metre boundary

A 1,200 square metre function hall with three exits, a 45 metre path and a 4.0 metre ceiling, on 90 minute duration. This one shows the assembly multiplier of 1.5 and the fact that a ceiling of exactly 4.0 metres does not trigger the extra luminaire.

Building typeAssembly
Floor area1,200 m²
Number of exits3
Path length to exit45 m
Ceiling height4.0 m
Battery duration90 min

Working

  1. Spacing rule: 45 / 4 = 11.25, rounded up to 12. Area rule: 1,200 / 10 = 120. Larger is 120.
  2. Ceiling is 4.0 m, which is not greater than 4.0 m, so no extra unit. Count = 120.
  3. Exit signs: 3 exits, plus 1,200 / 2,000 rounded up = 1, giving 4, times the assembly multiplier 1.5 = 6 signs.
  4. Load: 120 x 3 W + 6 x 2 W = 372 W.
  5. Battery current: 372 / (0.85 x 24) = 18.24 A. Discharge time 2.25 h.
  6. Capacity: 18.24 x 2.25 = 41.03 Ah, rounded up to 41.5 Ah.
  7. Spacing: 45 / 120 = 0.38 m. Floor lux: 120 x 30 / 1,200 x 0.65 = 1.95 lux.

Result. 120 luminaires, 6 exit signs, 372 W, 41.5 Ah. All five checks pass. Raise the ceiling to 4.1 metres and the count becomes 121, the load 375 W and the battery 41.5 Ah. Switch the building type to commercial and the sign count drops from 6 to 4.

Common questions

How many emergency luminaires does AS/NZS 2293.1 require?+

AS/NZS 2293.1 specifies minimum illumination levels (0.2 lux on the floor of escape routes, 1 lux at changes of direction and exits) rather than a fixed number of luminaires. The number required depends on the building layout, ceiling height, luminaire output, and spacing. The calculator estimates the count based on floor area and luminaire specifications.

How long must emergency lighting operate after a power failure?+

AS/NZS 2293.1 requires a minimum of 90 minutes of emergency lighting operation from the battery or central power supply. Some high-risk occupancies may require longer duration. The battery must be sized to deliver the required illumination for the full duration at end-of-life capacity.

What is the difference between maintained and non-maintained emergency lighting?+

Maintained emergency luminaires operate continuously (as normal room lighting) and switch to battery power during a mains failure. Non-maintained luminaires are off during normal operation and switch on only during a power failure. Maintained luminaires are required in places of public entertainment per AS/NZS 2293.1.

How often must emergency lighting be tested?+

AS/NZS 2293.2 requires monthly function tests (switch to battery for a few seconds to verify operation) and six-monthly duration tests (run on battery for the full rated duration to verify capacity). Results must be recorded in a logbook and made available to the authority having jurisdiction.

Do exit signs count as emergency lighting?+

Exit signs provide directional guidance but are separate from emergency illumination. Both are required per AS/NZS 2293.1. Exit signs must be illuminated (internally lit or photoluminescent) and visible from any point on the escape route. The calculator covers both exit signs and emergency luminaires.

SparkyToolkit · iOS

On site? Get the same calcs on your phone.

SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.

Download on theApp Store

Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.

Related calculators