AS/NZS 3000 + AS 1680

Lighting Load Calculator

Lighting circuit loads, number of circuits, and W/m² compliance per AS/NZS 3000 and AS 1680.

Inputs

80% of breaker rating recommended

Advanced options

Schedule

Lump total added to the schedule. Can be used on its own with no rows.

Premises and diversity

Sets the Appendix C load group (a) diversity and the W/m2 target. Column 2 and Column 3 premises differ.

Allowance for future luminaires, added before diversity

Supply

Low cost LED drivers often run 0.5 to 0.9

Circuit split

Sets the per circuit limit to breaker rating times this factor, capped by the max circuit load

Emergency and exit

Counted as a separate load on its own circuits, not part of the general lighting total

Density

Results

Total Load

360

Watts (1.57A)

1 circuit required

Circuit Loading

W/m² Guideline

Breaker Rating

Total Watts360 W
Total Amps1.57 A
W/m²3.6 of 20 W/m² target
Density Margin16.4 W/m² under
Per Circuit Limit10 A
Circuits Required1
Amps per Circuit1.57 A
Show the working
Step by step derivation of the result
StepWorkingResultReference
Calculate ballast-adjusted wattage for each luminaire type20 x 18 W x 1 (LED) = 360 W360 WAS/NZS 3000:2018 Table C.4
Convert total wattage to amperage360 W / 230 V = 1.57 A1.57 AAS/NZS 3000:2018 Table C.4
Determine number of circuits requiredceil(1.57 A / 10 A per circuit) = 1 circuits on 16 A breakers1 circuitsAS/NZS 3000:2018 Table C.4
Calculate amperage per circuit1.57 A / 1 circuits = 1.57 A per circuit1.57 AAS/NZS 3000:2018 Table C.4
Calculate lighting density360 W / 100 m2 = 3.6 W/m23.6 W/m²AS 1680
Compare lighting density against the target for the premises type20 W/m2 target (Office) - 3.6 W/m2 actual = 16.4 W/m2 under target16.4 W/m2AS 1680 Reference Guideline

Lookup values used by these calculators are indicative and awaiting validation against the current standards. Confirm against your own licensed copy before relying on a result for design.

Important: These results are indicative only. Lighting circuits must be designed and verified by a qualified electrical engineer in accordance with AS/NZS 3000:2018 and AS 1680 before final design.

Parameters

Every field this calculator exposes, what it means, the range it accepts, and the traps worth knowing before you rely on the answer.

Luminaire schedule, one row per type

Add one row per luminaire type. Rows are grouped by type, wattage and quantity, and each row is multiplied by a control gear factor before being summed. The label and the per row factor appear once you turn on "Per row label and control gear factor" in Advanced options.

Luminaire typeLED, fluorescent, halogen, HID or other
Selects the control gear factor applied to that row: LED 1.00, halogen 1.00, fluorescent 1.10, other 1.10 and HID 1.15. These are indicative allowances for ballast and driver losses, not values transcribed from a standard or a datasheet. If your manufacturer already quotes a circuit input wattage that includes the driver, choose LED or halogen so the factor stays at 1.00 and you do not double count the losses.
Wattagewatts per luminaire
Rated wattage of a single fitting. Accepts 1 to 10,000 watts. Gotcha: for LED fittings this should be the driver input wattage from the datasheet, not the light engine or chip wattage. A fitting sold as a 40 watt panel commonly draws 44 watts at the terminals.
Quantitywhole number
Number of identical fittings in that group. Must be a positive whole number; the form accepts 1 to 1,000. Quantities are also summed as lighting points for the points per circuit check.
Row labeltext, optional
Free text description for that row, for example "Level 2 open plan panels". It carries through to the breakdown table and into the working, so a schedule with several rows of the same type stays readable.
Control gear factor0.5 to 3, optional
Overrides the type based factor for that row only. Use it when the datasheet gives a circuit input wattage (set 1.00 so the driver loss is not counted twice), or when you know the real ballast loss for a specific fitting. Blank falls back to the type factor.

Circuit fields

Supply voltagevolts
Voltage used to convert watts to amperes. Default 230. The form accepts 100 to 415 volts. One voltage applies to every luminaire and every circuit; there is no mixed voltage option.
Circuit breaker ratingamperes
Rating of the protective device on each lighting circuit, typically 10 or 16 amperes. On its own it is still just the sanity check that your max circuit load is not larger than the breaker. Set a breaker loading factor in Advanced options and it becomes the thing that actually calculates the circuit split.
Max circuit loadamperes
The design current you are prepared to put on one circuit. With no breaker loading factor set, this is what drives the circuit count. With one set, it acts as a cap on the breaker derived figure, so the per circuit limit is the smaller of the two. The form defaults to 10 amperes against a 16 ampere breaker.
Room areasquare metres, optional
Floor area served by the lighting. Leave it blank to skip the density calculation entirely. When it is filled in, the watts per square metre result appears together with the target for the premises type you chose and the margin against it. The target is no longer a fixed office number; it follows the premises type unless you override it.
Emergency lighting requiredcheckbox
Adds the AS 2293 reminder note to the results, and warns if you have ticked it without entering any emergency or exit counts. The counts themselves, not this checkbox, are what add load.

Advanced options

Everything below is optional and hidden behind the Advanced options block. Leave the whole block alone and the calculator behaves exactly as the basic form describes.

Aggregate connected loadwatts, optional
A lump connected total for lighting you have not scheduled row by row. It is added to the schedule sum and shown as its own "aggregate" row in the breakdown. You can use it on its own with no schedule rows at all, which is the quick path when you only have a total off a drawing. Gotcha: aggregate watts contribute zero lighting points, so they do not affect the points per circuit check.
Premises typenine options across Appendix C Columns 1 to 3
Drives two things. First, the AS/NZS 3000 Appendix C load group (a) lighting diversity, which differs between Column 2 premises (multiple domestic, blocks of living units) and Column 3 premises (offices, shops, hotels, hospitals, schools, industrial, warehouses). Second, the watts per square metre target the density result is judged against. Default is Office, Column 3, diversity 1.00, target 20 watts per square metre, which reproduces the old behaviour. Gotcha: the diversity values and the density targets in this list are indicative planning figures pending verification, not transcriptions from the published standard.
Diversity factor override0 to 1, optional
Replaces the premises type diversity with your own number. Use it when you have a project specific demand agreement. Blank uses the premises figure.
Spare capacitypercent, default 0
Allowance for future luminaires, applied to the connected load before diversity. 10 percent on a 2,000 watt connected load gives a 2,200 watt figure before any diversity is applied.
Power factor0.1 to 1, default 1.0
Load power factor used to convert watts to amperes. At the default of 1.0 the current is simply watts divided by volts, which is what this calculator used to assume. Cheap LED drivers commonly run 0.5 to 0.9 and the calculator warns below 0.8, because a 0.5 power factor doubles the circuit current for the same wattage.
Supply arrangementsingle phase or three phase
Single phase uses I = P / (V x pf). Three phase balanced uses I = P / (sqrt(3) x V x pf) and reports the per phase current. Use three phase with the line voltage, typically 400 volts, when a large lighting distribution board is fed as a three phase load.
Breaker loading factor0 to 1, optional
The fraction of the circuit breaker rating you will allow as continuous design current. Set 0.8 against a 16 ampere breaker and the per circuit limit becomes 12.8 amperes, capped by the max circuit load. This is what turns the circuit breaker rating from a passive comparison into the number that calculates the split, and the compliance check limit moves with it. Blank keeps the old behaviour, where max circuit load alone sets the limit.
Max points per circuitwhole number, optional
Caps the number of lighting points on one final subcircuit. The circuit count becomes the larger of the current driven figure and the points driven figure, so 40 points with a limit of 15 gives at least three circuits regardless of how low the current is. A "Points per Circuit" compliance check appears when this is set.
Emergency luminaires and watts eachcount, watts, default 3 W each
Number of emergency luminaires and the charging plus operating watts per fitting. This load is calculated separately and never enters the general lighting total or the general circuit split, because AS 2293 wants the emergency arrangement kept apart. It gets its own current and its own circuit count, and is added to the general design load only in the combined figure at the board.
Exit signs and watts eachcount, watts, default 5 W each
Same treatment as the emergency luminaire count, on a separate per unit wattage since illuminated exit signs and emergency luminaires draw different amounts.
Target densitywatts per square metre, optional
Overrides the premises type density target. Use it when a project brief or a National Construction Code Section J allowance gives you a specific number. Blank uses the premises type target.

Assumptions and limits

This is a circuit loading tool, not a lighting design tool. It tells you how much current the fittings draw and how many circuits that needs. It does not tell you whether the space will be bright enough.

What the tool assumes

  • Current defaults to watts divided by volts at a power factor of 1.0. Power factor is now an input, so if you know the driver figure, enter it and the current is recalculated properly. Left at the default, the result matches the old behaviour and understates the current on cheap drivers.
  • The circuit count is the design current divided by the per circuit limit, rounded up, and then raised further if a points per circuit limit binds. The load is still assumed to split perfectly evenly across those circuits, which is why the amperes per circuit figure always passes its own check. Real installations split by area or by switching zone and are rarely even, so check the worst loaded circuit yourself.
  • Control gear factors are flat multipliers by type unless you set a per row factor. Neither the type factor nor the per row factor varies with wattage, driver quality or dimming.
  • Every fitting is assumed to be on simultaneously at full output. The only reduction available is the Appendix C load group (a) diversity tied to the premises type, or your own override. There is no dimming allowance and no daylight or occupancy control reduction.
  • The premises type diversity values and the watts per square metre targets are indicative planning figures. They have not been checked against the current published edition of AS/NZS 3000 Appendix C or against National Construction Code Section J, and they need CPEng validation before you rely on them.
  • Emergency and exit load is a flat count multiplied by a per unit wattage. It models the normal operating draw at the board, not battery duration, charge profile or the AS 2293 classification.

What it does not do

  • No illuminance design. Lux levels, uniformity, glare, luminaire spacing, mounting height, room surface reflectance and maintenance factor are all out of scope. It will not tell you whether the design meets the AS 1680 recommendation for the task.
  • No National Construction Code Section J lighting power density compliance. The density target follows the premises type and can be overridden, but the Section J maximum for a specific class of space is often tighter again and carries its own adjustment factors, none of which are modelled here.
  • No inrush check. The capacitive inrush of many LED drivers starting together is the usual reason a lighting circuit breaker trips on switch on, and it is not modelled. It can force fewer fittings per circuit than the steady current suggests, or a curve change on the breaker.
  • No cable sizing, no voltage drop and no earth fault loop impedance. Long runs to high bay fittings need all three checked separately.
  • No emergency or exit lighting design. The emergency and exit counts give you the separate connected load and its circuit count, nothing more. AS 2293 classification, duration, spacing, coverage and battery sizing are all separate work.
  • No harmonic assessment. Large banks of electronic drivers produce third harmonic current that adds in the neutral of a three phase distribution, which is not considered here.

Treat the output as an indicative circuit loading figure. Check it against the current edition of AS/NZS 3000 and AS 1680, and have the responsible person for the installation review and sign off the final design. Nothing here is validated or certified.

Worked examples

Four examples covering a single circuit LED office, a mixed type warehouse needing several circuits, a case where the lighting density check fails, and a hotel using the advanced options end to end. Every figure comes from the same arithmetic the calculator runs.

Example 1. Small LED office, one circuit

A 100 square metre office with 20 recessed LED panels at 18 watts each, on 230 volts with a 16 ampere breaker and a 10 ampere design limit per circuit.

Inputs

  • Luminaires: 20 x 18 W LED
  • Supply voltage: 230 V
  • Circuit breaker rating: 16 A, max circuit load: 10 A
  • Room area: 100 square metres

Working

  1. LED control gear factor = 1.00
  2. Total watts = 18 x 20 x 1.00 = 360 W
  3. Total amperes = 360 / 230 = 1.57 A
  4. Circuits = 1.57 / 10 rounded up = 1 circuit
  5. Amperes per circuit = 1.57 / 1 = 1.57 A
  6. Density = 360 / 100 = 3.60 watts per square metre

Pass: 1.57 A per circuit is well under the 10 A design limit, the 10 A limit is under the 16 A breaker, and 3.60 watts per square metre is comfortably under the 20 watt benchmark. All three checks pass on a single circuit.

Example 2. Warehouse with mixed luminaire types

A 2,000 square metre warehouse using HID high bays for the main floor plus a few fluorescent battens over the pick face. 230 volts, 20 ampere breakers, 16 amperes design limit per circuit.

Inputs

  • Luminaires: 40 x 200 W HID, plus 6 x 36 W fluorescent
  • Supply voltage: 230 V
  • Circuit breaker rating: 20 A, max circuit load: 16 A
  • Room area: 2,000 square metres

Working

  1. HID group = 200 x 40 x 1.15 = 9,200 W
  2. Fluorescent group = 36 x 6 x 1.10 = 237.6 W
  3. Total watts = 9,200 + 237.6 = 9,437.6 W
  4. Total amperes = 9,437.6 / 230 = 41.03 A
  5. Circuits = 41.03 / 16 = 2.56, rounded up = 3 circuits
  6. Amperes per circuit = 41.03 / 3 = 13.68 A
  7. Density = 9,437.6 / 2,000 = 4.72 watts per square metre

Pass: 13.68 A per circuit sits under the 16 A design limit, the 16 A limit is under the 20 A breaker, and density is 4.72 watts per square metre. Note the control gear factors added 1,221.6 W, about 15 percent, over the raw lamp wattage.

Example 3. Halogen retrofit where lighting density fails

A small 80 square metre retail space still running halogen downlights plus some unspecified fittings. 230 volts, 16 ampere breaker, 10 ampere design limit, premises type set to Shop or retail.

Inputs

  • Luminaires: 30 x 50 W halogen, plus 10 x 100 W other
  • Supply voltage: 230 V
  • Circuit breaker rating: 16 A, max circuit load: 10 A
  • Premises type: Shop or retail (Column 3, diversity 1.00, target 25 W per square metre)
  • Room area: 80 square metres

Working

  1. Halogen group = 50 x 30 x 1.00 = 1,500 W
  2. Other group = 100 x 10 x 1.10 = 1,100 W
  3. Total watts = 1,500 + 1,100 = 2,600 W
  4. Design watts = 2,600 x 1.00 diversity = 2,600 W
  5. Total amperes = 2,600 / 230 = 11.30 A
  6. Circuits = 11.30 / 10 = 1.13, rounded up = 2 circuits
  7. Amperes per circuit = 11.30 / 2 = 5.65 A
  8. Density = 2,600 / 80 = 32.50 watts per square metre
  9. Margin = 25 target - 32.50 actual = -7.50 watts per square metre

Fail: the circuit checks pass at 5.65 A per circuit, but density of 32.50 watts per square metre is 7.50 above the retail target of 25. This is the classic case for an LED retrofit, which would cut the load by roughly three quarters and bring it back to a single circuit.

Example 4. Hotel using the advanced options end to end

A 1,800 square metre hotel floor plate. Two scheduled luminaire rows, one with a per row control gear factor, plus 10 percent spare capacity, hotel diversity, a 0.95 power factor, a breaker derived circuit limit, a 20 point per circuit rule, and emergency and exit counts kept separate.

Inputs

  • Row 1: 120 x 9 W LED, control gear factor 1.05, labelled Guest room downlights
  • Row 2: 40 x 18 W LED, labelled Corridor panels
  • Supply voltage: 230 V, single phase, power factor 0.95
  • Circuit breaker rating: 16 A, max circuit load: 16 A, breaker loading factor: 0.8
  • Max points per circuit: 20
  • Premises type: Hotel, motel or boarding house (Column 3, diversity 0.75, target 15 W per square metre)
  • Spare capacity: 10 percent, room area: 1,800 square metres
  • Emergency luminaires: 24 at 3 W, exit signs: 12 at 5 W

Working

  1. Row 1 = 120 x 9 x 1.05 = 1,134 W
  2. Row 2 = 40 x 18 x 1.00 = 720 W
  3. Connected watts = 1,134 + 720 = 1,854 W
  4. Spare capacity = 1,854 x (1 + 10 / 100) = 2,039.40 W
  5. Diversity = 2,039.40 x 0.75 = 1,529.55 W design load
  6. Total amperes = 1,529.55 / (230 x 0.95) = 7.00 A
  7. Per circuit limit = 16 x 0.8 = 12.80 A, capped by 16 A max circuit load, so 12.80 A
  8. Circuits by current = ceil(7.00 / 12.80) = 1
  9. Circuits by points = ceil(160 / 20) = 8, so 8 circuits win
  10. Amperes per circuit = 7.00 / 8 = 0.88 A
  11. Density = 1,854 / 1,800 = 1.03 watts per square metre, 13.97 under the 15 target
  12. Emergency and exit = 24 x 3 + 12 x 5 = 132 W, 0.60 A on 1 separate circuit
  13. Combined at the board = 1,529.55 + 132 = 1,661.55 W

Pass: every check passes. Note that the current would fit on a single circuit at 7.00 A, and it is the 20 point per circuit rule that forces 8 circuits. Note also that the 132 W of emergency and exit load never enters the 1,854 W general lighting total, it only appears in the combined figure at the board.

Lighting Load Guide for AS/NZS 3000 and AS 1680

Lighting load calculation determines how much electrical capacity a lighting installation requires and how that load should be distributed across circuits. This is a fundamental step in any electrical design because it drives circuit count, cable sizing, circuit breaker selection, and ultimately the contribution to the building's maximum demand. AS/NZS 3000 (Wiring Rules) sets the rules for circuit loading and outlet counts, while AS 1680 (Interior and Workplace Lighting) defines the illumination levels that the lighting system must achieve.

This calculator takes your luminaire specifications, the number of fittings, and the floor area being served, then computes the total circuit load, the number of circuits required, and the watts per square metre (W/m squared) lighting power density. It flags any circuits that exceed the maximum current rating and checks the lighting power density against typical benchmarks for the space type.

Key concepts

  • Driver input wattage, not LED chip wattage. LED luminaires consume more power at the supply terminals than the LED chips alone draw, because the driver has conversion losses (typically 85% to 95% efficient). A "40 W LED panel" might draw 44 W from the supply. Always use the driver input wattage from the manufacturer datasheet for circuit load calculations. Using the LED chip wattage will underestimate the load and can result in overloaded circuits.
  • Circuit limits under AS/NZS 3000. Lighting circuits are typically protected by a 10 A or 16 A circuit breaker. At 230 V, a 10 A circuit can supply a maximum of 2,300 W. AS/NZS 3000 also limits lighting circuits to 20 outlets (points of attachment) per circuit in some configurations. The practical limit is usually the current capacity rather than the outlet count when using modern LED luminaires.
  • Watts per square metre (lighting power density).W/m squared is the total installed lighting wattage divided by the floor area. This metric is used by the National Construction Code (NCC) Section J to set maximum allowable lighting power density for energy efficiency compliance. Typical values for modern LED installations are 5 to 8 W/m squared for offices, 8 to 12 W/m squared for retail, and 3 to 5 W/m squared for corridors and storage areas.
  • Emergency lighting contribution. Luminaires with integral emergency batteries draw a small continuous charging current (typically 2 to 5 W per fitting) on top of their normal operating wattage. This charging load must be included in the circuit load calculation. During a mains failure, these luminaires switch to battery power and the circuit load drops, but the circuit must be sized for the normal operating condition including the charge current.

Common scenarios

  • Open plan office fit-out. A 500 m squared open plan office requires approximately 400 lux at desk height per AS 1680.1. Using 36 W LED panels at 130 lumens per watt, the designer needs roughly 42 luminaires (total 1,512 W, or about 3.0 W/m squared). This fits comfortably on a single 10 A circuit, but for maintenance flexibility and to avoid a total blackout from one tripped breaker, it is standard practice to split the load across two or three circuits covering different zones of the floor plate.
  • Warehouse or industrial shed. A 2,000 m squared warehouse with 8 m mounting height needs high bay luminaires producing enough lumens to achieve 200 lux at floor level. Using 200 W LED high bays, the designer might specify 40 fittings (total 8,000 W, or 4.0 W/m squared). At 230 V, this is approximately 34.8 A total, requiring a minimum of three 16 A circuits or four 10 A circuits. Cable runs to high bays are long, so voltage drop must be checked alongside the load calculation.
  • Retail tenancy with feature lighting. A retail fit-out combines general ambient lighting (recessed downlights or panels), accent lighting (track spots on displays), and decorative feature lighting (pendant fixtures, LED strip). Each type has different wattages and control requirements. The lighting load calculation must account for all three categories, and circuits are often separated by lighting type so that accent and feature lighting can be switched or dimmed independently from the general lighting.
Disclaimer: Lighting power density limits in the National Construction Code can be more restrictive than AS/NZS 3000 alone. Verify with a qualified electrical designer.

Common questions

How do I calculate lighting load for a circuit?+

Sum the wattage of all luminaires on the circuit, including any control gear losses. For LED luminaires, use the driver input wattage (not the LED chip wattage). Add 10 percent for future luminaire additions if the circuit serves an area likely to be reconfigured. Divide total watts by voltage to get the circuit current.

What is the maximum number of luminaires per lighting circuit?+

AS/NZS 3000 does not set a fixed maximum number of luminaires per circuit. The limit is the circuit breaker rating (typically 10 A or 16 A for lighting) and the cable current carrying capacity. At 230 V on a 10 A circuit, the maximum load is 2300 W. Divide by the wattage per luminaire to get the maximum count.

How do I calculate watts per square metre for lighting design?+

Watts per square metre (W/m squared) equals total installed lighting wattage divided by the floor area. AS 1680 provides recommended illumination levels (lux) for different space types, which can be converted to W/m squared using the luminaire efficacy (lumens per watt). Typical office lighting is 8 to 12 W/m squared with modern LED luminaires.

Do LED drivers affect the lighting circuit load calculation?+

Yes. LED drivers draw more power from the supply than the LED chips consume, due to driver efficiency losses (typically 85 to 95 percent efficient). Always use the driver input wattage for circuit load calculations. Some LED drivers also have a poor power factor (0.5 to 0.7), which increases the apparent current on the circuit.

How does emergency lighting affect the lighting load calculation?+

Emergency luminaires with integral batteries draw a small charging current (typically 2 to 5 W per luminaire) in addition to their operating wattage during normal operation. This charging current must be included in the circuit load calculation. During a mains failure, the emergency luminaires switch to battery and the circuit load drops to zero.

SparkyToolkit · iOS

On site? Get the same calcs on your phone.

SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.

Download on theApp Store

Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.

Related calculators