AS/NZS 3000:2018 + 1359

Motor Calculator

Full load current, cable sizing, breaker selection, and starter sizing for motors per AS/NZS 3000 and 1359.

Inputs

Typically 0.80 to 0.93

Typically 0.80 to 0.90

Cable & Environmental

Results

Full Load Current (FLC)

10.61

Amperes

Starting: 63.66 A

Cable Current Capacity

17 A (>= 10.61 A)

Voltage Drop (Running)

1.15 % (<= 5 %)

Voltage Drop (Starting)

6.91 % (<= 15 %)

Breaker Handles Starting Current

16 A (>= 63.66 A)

Cable Size1.5 mm²
Cable Capacity17 A
V-drop Running1.15%
V-drop Starting6.91%
Breaker16A (Curve D)
ContactorAC3 rated 12A or higher
OverloadThermal overload 8.5 to 12.2A
Show the working
Step by step derivation of the result
StepWorkingResultReference
Full Load Current (FLC)5.5 kW x 1000 / (400 V x 1.732 [3-phase] x 0.88 eff x 0.85 pf) = 10.61 A10.61 AAS/NZS 3000:2018 Cl. 1.2 & AS/NZS 1359
Starting Current10.61 A FLC x 6 (DOL multiplier) = 63.66 A63.66 AStarting method: DOL
Cable selection (copper)Table lookup: 1.5 mm2 copper clipped direct = 17 A; capacity 17 A x 1 (copper) x 1 (Ct = sqrt((75 - 40) / (75 - 40))) = 17 A >= FLC 10.61 A. Running drop 10.61 A x 14.4800 mohm/m x 30 m / 1000 / 400 V x 100 = 1.15% (limit 5%); starting drop 63.66 A same path = 6.91% (limit 15%)1.5 mm²AS/NZS 3008.1.1:2025
Circuit Breaker SelectionSmallest standard size >= FLC 10.61 A from [6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160] A = 16 A, curve D (DOL, starting current 63.66 A)16 AAS/NZS 3000:2018
Motor Contactor (AC3 duty)Smallest AC3 frame size >= FLC 10.61 A from [12, 18, 25, 32, 38, 45, 65, 90, 120, 150, 185, 220] A gives AC3 rated 12A or higherAC3 rated 12A or higherAS/NZS 3000:2018
Thermal Overload Relay10.61 A FLC x 0.8 = 8.5 A to 10.61 A FLC x 1.15 = 12.2 AThermal overload 8.5 to 12.2AAS/NZS 3000:2018 Cl. 2.2.5

Standards referenced

  • AS/NZS 3000:2018 Clause 1.2. General requirements for electrical installations
  • AS/NZS 3000:2018 Clause 2.2.5. Protection against overcurrent, thermal overload
  • AS/NZS 3000:2018 Clause 3.6. Voltage drop in consumer mains and sub-mains
  • AS/NZS 1359. Electrical equipment, Motors, generators and rotating machinery
  • AS/NZS 3008.1.1:2025 Clause 4. Current-carrying capacity of cables

Lookup values used by these calculators are indicative and awaiting validation against the current standards. Confirm against your own licensed copy before relying on a result for design.

Important: These results are indicative only. Motor circuits must be designed and verified by a qualified electrical engineer in accordance with AS/NZS 3000:2018 and AS/NZS 1359 before installation.

Motor Installation Guide for AS/NZS 3000:2018 and AS/NZS 1359

Designing a motor circuit involves more than just connecting the motor to a supply. The electrician must calculate the full load current, select an appropriate cable that handles both running current and voltage drop, choose a protective device that rides through starting inrush without nuisance tripping, and specify the correct starting method for the application. This calculator handles all of those steps from motor nameplate data. It is used whenever a new motor is being installed, an existing motor is being replaced with a different rating, or a circuit needs to be verified during commissioning or periodic inspection. The results comply with AS/NZS 3000:2018 for wiring rules and AS/NZS 1359 for motor ratings and performance characteristics.

Key concepts

  • Full load current (FLC). The current the motor draws at rated power, voltage, power factor, and efficiency. For three-phase motors: FLC = (kW x 1000) / (1.732 x V x pf x eff). This value sets the baseline for cable sizing and protection. Nameplate values should be used for power factor and efficiency where available; otherwise, 0.85 and 0.90 are reasonable defaults for general-purpose induction motors.
  • Starting current and protection coordination. During a direct-on-line start, the motor draws 5 to 7 times FLC for several seconds. The protective device must allow this transient without tripping, while still providing short-circuit and overload protection during normal running. Curve D MCBs or dedicated motor circuit breakers are designed for this characteristic. Undersized protection will nuisance-trip on every start; oversized protection may not clear an overload fast enough.
  • Cable sizing for motor circuits. The cable must be rated for the motor FLC (not starting current) per AS/NZS 3008.1.1 current carrying capacity tables. Voltage drop at FLC must stay within 5% of nominal supply from the point of supply to the motor terminals. For long cable runs, voltage drop often governs and forces a larger cable than current rating alone would require.
  • Supply authority coordination. Most Australian DNSPs set a maximum voltage dip at the point of common coupling, typically 4% for residential and 3% for commercial. Motors that cause voltage dip above this threshold during starting require supply authority approval and may need a reduced-voltage starting method even if the site electrical system can handle DOL starting.

Common scenarios

  • Installing a 5.5 kW air conditioning compressor motor. The electrician enters the motor kW, voltage (typically 400 V three-phase), and starting method (usually DOL for this size). The calculator outputs the FLC (approximately 11 A), recommends a cable size based on the run length, and suggests a curve D MCB rating. If the cable run is long (over 30 m), the calculator may upsize the cable from the current-rated minimum to meet voltage drop limits.
  • Replacing a pump motor with a larger unit on an existing circuit. Before swapping a 3.7 kW pump motor for a 5.5 kW unit, the electrician checks whether the existing cable and protective device can handle the higher FLC. The calculator determines the new FLC, checks the existing cable current rating and voltage drop, and flags whether the breaker needs to be upsized. This avoids the costly mistake of overloading an existing circuit.
  • Specifying a star-delta starter for a 15 kW motor on a light commercial supply. A 15 kW motor started DOL would draw approximately 65 to 80 A of starting current, which may exceed the DNSP voltage dip limits on a 100 A supply. The electrician enters star-delta as the starting method, and the calculator shows the reduced starting current (approximately 22 A) alongside the required contactor and overload relay ratings for the star-delta switching arrangement.

Motor starting methods

  • Direct-on-line (DOL): Highest starting current (5 to 7 times FLC). Suits small motors on robust supplies. Requires curve D breaker.
  • Star-delta: Reduces starting current to approximately 2 times FLC. Requires switching equipment; reduced torque during start.
  • Soft-starter: Electronic control allows gradual acceleration; approximately 3 times FLC. No torque loss.
  • VFD: Soft acceleration, lowest starting current (approximately 1.5 times FLC). Most efficient; speed control included.
Disclaimer: Motor starting must be coordinated with the supply authority for larger motors (typically over 7.5 kW). Verify all selections with a qualified electrical engineer.

Parameters

Every field this calculator accepts, what it means, the range it accepts, and how it feeds the result. The last four sit under Cable and Environmental but are always used.

Motor rating (kilowatts, 0.1 to 500)
Rated mechanical output at the shaft, as printed on the nameplate. It is not the electrical input power: the efficiency and power factor fields convert one into the other. A motor marked 5.5 kilowatts draws more than 5.5 kilowatts of electrical input.
Voltage (230, 400, 415 or 690 volts)
Only these four values are accepted. For three phase it is the line to line voltage. It divides into the full load current calculation and it is also the denominator for both voltage drop percentages, running and starting.
Phase (single phase or three phase)
Decides whether the square root of 3 appears in the full load current formula. Note that it does not change the voltage drop multiplier, which is fixed at 1 in this engine for both cases. See the limits below.
Efficiency (decimal fraction, form range 0.70 to 0.95, default 0.88)
Motor efficiency at full load as a decimal, not a percentage: enter 0.88, not 88. Use the nameplate or datasheet figure where you have it. Small motors sit around 0.75 to 0.82, and modern premium efficiency motors above 7.5 kilowatts sit at 0.90 to 0.94. Efficiency divides into the current, so a low value gives a higher current.
Power factor (decimal fraction, form range 0.70 to 1.00, default 0.85)
Displacement power factor at full load, again as a decimal. Typical induction motors run 0.80 to 0.90 at full load and much lower when lightly loaded. It divides into the current in the same way as efficiency. It is used only for the current; it does not appear in the voltage drop calculation.
Starting method (direct on line, star delta, soft starter, variable frequency drive)
Sets the starting current multiplier applied to full load current: 6 for direct on line, 2 for star delta, 3 for soft starter, 1.5 for a variable frequency drive. It also selects the breaker curve, D for direct on line and C for everything else. These multipliers are fixed defaults in the engine, not motor data; the underlying module accepts an explicit multiplier but this page always sends the default for the method.
Cable length (metres, 1 to 2,000, one way)
Route length from the starter or distribution board to the motor terminals, one way. Above 100 metres the tool raises a warning to check the drop and consider a drive. It affects the voltage drop figures only; it has no effect on the breaker, contactor or overload selection.
Conductor material (copper or aluminium)
Aluminium multiplies both the current rating and the conductor resistance by 0.78. The rating reduction is right in direction; the resistance reduction is not, since aluminium resists more than copper. Treat aluminium voltage drop from this tool as unreliable and check it against manufacturer data.
Ambient temperature (degrees Celsius, 0 to 50, default 40)
The only cable derating applied. The factor is the square root of 75 minus ambient over 75 minus 40. At 40 degrees it is exactly 1.000, at 45 degrees 0.926, at 50 degrees 0.845. A motor cable in a plant room or on a hot roof should be entered above 40.
Maximum voltage drop (percent, 1 to 10 in the form, default 5)
The running voltage drop limit the selected cable must meet, and one of the two conditions in the cable selection loop. The AS/NZS 3000 figure of 5 percent covers the whole installation, so on a submain fed motor enter only the allowance left for this final run. The starting voltage drop is checked separately against a fixed 15 percent guideline that you cannot change.

Assumptions and limits

This is a first pass sizing tool for a single motor circuit. Here is exactly what it assumes and where it stops.

What it assumes

  • Full load current is derived, not read. It is the rating in watts divided by voltage, the phase factor, efficiency and power factor. Where the nameplate gives a current, use the nameplate. Real motors vary from the calculated figure.
  • Cable selection ignores starting current. The first standard size whose derated capacity is at or above full load current and whose running voltage drop is inside the limit wins. Starting current is calculated and reported, but it never pushes the cable up a size.
  • The voltage drop multiplier is fixed at 1 for both single phase and three phase. The conventional factors are 2 for single phase and the square root of 3 for three phase, so single phase drop reported here is about half of the true figure and three phase drop is about 1.7 times optimistic. Both running and starting percentages are affected. Re check the run in the voltage drop or cable sizing calculator before committing, particularly on a single phase motor.
  • Resistance only, no reactance. Values are the engine placeholder direct current resistance at 75 degrees Celsius for copper, not transcribed from a licensed copy of AS/NZS 3008.1.1. Aluminium is scaled by the same 0.78 factor as the rating, which understates its resistance.
  • One circuit, clipped direct, ambient derating only. Grouping is assumed to be 1.0. There is no installation method column, no thermal insulation, no burial correction.
  • Starting multipliers are typical values, not motor data. Real direct on line locked rotor current runs 5 to 8 times full load current depending on the design code, and the star delta figure depends on the changeover arrangement and the load inertia.
  • The breaker versus starting current check is misleading by design. It compares the breaker rating in amperes directly against the starting current, so a direct on line motor will almost always show a fail. That is not how motor protection is coordinated. A curve D device is chosen so that its instantaneous trip band, roughly 10 to 14 times rated current, sits above the inrush, and the time current curve is what decides whether it holds. Read that line as a prompt to look at the device curve, not as a defect in the design.
  • Protection and switchgear selections are generic. The breaker is the next standard size at or above full load current from 6 to 160 amperes. The contactor is the next alternating current utilisation category 3 rating at or above full load current. The overload range is 0.8 to 1.15 times full load current. None of these comes from a manufacturer range, and there is no type 1 or type 2 coordination.

What it does not do

  • It sizes a single cable run at full line current. A star delta connection uses six leads with each run carrying phase current, which is a different sizing problem the tool does not handle.
  • No earth fault loop impedance, no disconnection time, no protective earthing conductor size, no prospective fault current or breaking capacity check.
  • No duty cycle, starting time, load inertia or motor thermal withstand, so it cannot tell you whether the motor accelerates before the overload operates.
  • No supply fault level and no voltage dip at the point of common coupling, which is what a distributor actually asks about for a large direct on line motor.
  • Nothing specific to variable frequency drives: no screened cable requirement, no cable length limit for the drive, no rate of voltage rise at the motor terminals, no harmonic assessment and no input side filtering.

Check every result against the current editions of AS/NZS 3000, AS/NZS 3008.1.1 and AS/NZS 1359, against the motor and device datasheets, and have the design signed off by the person responsible for the installation. Nothing here is validated or certified, and the underlying figures have not been reviewed by a chartered professional engineer.

Worked examples

Three complete runs with every intermediate figure shown, so you can check the tool against your own arithmetic.

Example 1. 5.5 kilowatt three phase motor, direct on line, 30 metres

A typical plant room motor on a 400 volt three phase supply, nameplate efficiency 0.88 and power factor 0.85, started direct on line, 30 metres of copper at 40 degrees Celsius.

Rating, voltage, phase5.5 kW, 400 V, three phase
Efficiency, power factor0.88, 0.85
Starting methodDirect on line, 6 x FLC
Cable length, ambient, drop limit30 m, 40 °C, 5 %

Working

  1. Full load current: 5,500 / (400 x 1.732 x 0.88 x 0.85) = 10.61 A.
  2. Starting current: 10.61 x 6 = 63.66 A.
  3. Temperature factor at 40 degrees: 1.000.
  4. First size tried, 1.5 mm², carries 17 A, which is at or above 10.61 A.
  5. Running drop on 1.5 mm², resistance 14.48 milliohms per metre: 10.61 x 14.48 x 30 / 1,000 = 4.61 V, which is 1.15 percent of 400 V, inside the 5 percent limit, so 1.5 mm² is selected.
  6. Starting drop: 63.66 x 14.48 x 30 / 1,000 = 27.65 V, which is 6.91 percent, inside the 15 percent guideline.
  7. Breaker: next standard size at or above 10.61 A is 16 A, curve D because the start is direct on line.
  8. Contactor: next utilisation category 3 rating at or above 10.61 A is 12 A. Overload range: 10.61 x 0.8 to 10.61 x 1.15, giving 8.5 to 12.2 A.

Result. 10.61 amperes full load, 1.5 square millimetre copper, 16 ampere curve D breaker, contactor rated at or above 12 amperes, overload set between 8.5 and 12.2 amperes. Current capacity and both voltage drop checks pass; the breaker versus starting current line reports 16 against 63.66 and shows as a fail, which is expected for a direct on line start and is what the curve D selection exists to handle. The 1.5 square millimetre result is also a good example of why this is a first pass: termination size, mechanical protection, grouping with other circuits and the real three phase drop factor all push a practical selection higher.

Example 2. 15 kilowatt three phase motor, star delta, 80 metres

A larger pump on a long run, efficiency 0.91 and power factor 0.86, started star delta so the multiplier drops to 2 and the breaker curve becomes C.

Rating, voltage, phase15 kW, 400 V, three phase
Efficiency, power factor0.91, 0.86
Starting methodStar delta, 2 x FLC
Cable length, ambient, drop limit80 m, 40 °C, 5 %

Working

  1. Full load current: 15,000 / (400 x 1.732 x 0.91 x 0.86) = 27.67 A.
  2. Starting current: 27.67 x 2 = 55.34 A.
  3. 1.5 mm² at 17 A and 2.5 mm² at 23 A are both below 27.67 A and are rejected on current.
  4. 4 mm² carries 31 A, which clears 27.67 A.
  5. Running drop on 4 mm², resistance 5.52: 27.67 x 5.52 x 80 / 1,000 = 12.22 V, which is 3.05 percent, inside 5 percent.
  6. Starting drop: 55.34 x 5.52 x 80 / 1,000 = 24.44 V, which is 6.11 percent, inside 15 percent.
  7. Breaker: 32 A, curve C because the start is not direct on line. Contactor at or above 32 A. Overload 22.1 to 31.8 A.

Result. 27.67 amperes full load, 4 square millimetre copper, 32 ampere curve C breaker, contactor at or above 32 amperes, overload 22.1 to 31.8 amperes. Current and both voltage drop checks pass; the breaker versus starting current line again shows a fail at 32 against 55.34, for the same reason as example 1. Remember that the six lead star delta arrangement is not what has been sized here.

Example 3. 2.2 kilowatt single phase motor, direct on line, 25 metres

A small single phase motor on 230 volts, efficiency 0.80 and power factor 0.85, direct on line, 25 metres of copper. This example is the one to read alongside the voltage drop caveat in the limits.

Rating, voltage, phase2.2 kW, 230 V, single phase
Efficiency, power factor0.80, 0.85
Starting methodDirect on line, 6 x FLC
Cable length, ambient, drop limit25 m, 40 °C, 5 %

Working

  1. Full load current: 2,200 / (230 x 1 x 0.80 x 0.85) = 14.07 A.
  2. Starting current: 14.07 x 6 = 84.42 A.
  3. 1.5 mm² carries 17 A, which clears 14.07 A.
  4. Running drop as reported: 14.07 x 14.48 x 25 / 1,000 = 5.09 V, which is 2.21 percent of 230 V.
  5. Starting drop as reported: 84.42 x 14.48 x 25 / 1,000 = 30.56 V, which is 13.29 percent, just inside the 15 percent guideline.
  6. Breaker 16 A curve D, contactor at or above 18 A, overload 11.3 to 16.2 A.

Result. 14.07 amperes full load, 1.5 square millimetre copper, 16 ampere curve D breaker. Every voltage drop check passes as reported. Now apply the single phase correction: with the conventional factor of 2 the running drop is about 10.19 volts or 4.43 percent, still inside 5 percent but only just, and the starting drop is about 61.1 volts or 26.6 percent, which blows well past the 15 percent guideline. On a single phase motor that difference is the whole answer, and it is why this run should be checked in the voltage drop calculator before anyone orders cable.

Common questions

How do I calculate full load current for a three-phase motor?+

FLC equals motor kW times 1000, divided by (1.732 times line voltage times power factor times efficiency). For a 7.5 kW 400 V motor at 0.85 power factor and 0.90 efficiency, FLC equals 7500 divided by (1.732 times 400 times 0.85 times 0.90), about 14.1 A. Use the nameplate power factor and efficiency where given; otherwise default to 0.85 and 0.90 for general purpose induction motors. The calculator applies the formula automatically.

What starting method should I use for an Australian motor installation?+

Direct-on-line is the default for motors up to about 7.5 kW where the supply can handle 6 to 7 times FLC for a few seconds. Star-delta or soft-starter is typical for 7.5 to 30 kW where DOL inrush would dip the supply or trip protection. Variable frequency drives are preferred over 30 kW or whenever speed control is needed. The supply authority may dictate the method for larger motors. The calculator recommends a method based on motor size and supply impedance.

How do I size cable for a motor circuit?+

Size the cable for the motor full load current (not starting current) per AS/NZS 3008.1.1 current carrying capacity tables, then verify voltage drop at FLC stays below 5 percent of nominal. The protective device handles the starting transient via its time-current curve. For long motor runs voltage drop dominates and may dictate a cable larger than current rating alone would suggest. The calculator runs both checks.

What breaker rating do I need for a DOL-started motor?+

Use a curve D miniature circuit breaker (or motor circuit breaker) rated 1.0 to 1.25 times the motor FLC. Curve D withstands inrush up to 10 to 14 times rated current for several cycles, which is needed to ride out DOL starting. Curve C will nuisance-trip on motor inrush. For star-delta starts a curve C is acceptable because peak starting current is roughly 2 times FLC, well within the curve C envelope.

When do I need to coordinate motor starting with the supply authority?+

Most Australian distributors set a per-customer starting current limit, typically expressed as a maximum voltage dip at the point of common coupling (commonly 4 percent for residential). A 7.5 kW DOL motor in a typical residential supply can dip the local voltage by 5 percent or more, so any motor over about 5.5 kW DOL or over about 11 kW for star-delta should be checked with the local DNSP before installation.

SparkyToolkit · iOS

On site? Get the same calcs on your phone.

SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.

Download on theApp Store

Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.

Related calculators