Motor Calculator
AS/NZS 3000:2018 + AS/NZS 1359 (Australian conditions)
Inputs
Typically 0.80–0.93
Typically 0.80–0.90
▶Cable & Environmental
Results
Full Load Current (FLC)
10.61
Amperes
Starting: 63.66 A
Cable Current Capacity
17 A (>= 10.61 A)
Voltage Drop (Running)
1.15 % (<= 5 %)
Voltage Drop (Starting)
6.91 % (<= 15 %)
Breaker Handles Starting Current
16 A (>= 63.66 A)
Motor Installation Guide — AS/NZS 3000:2018 + AS/NZS 1359
Motor circuits require careful design to ensure safe operation under both running and starting conditions. This calculator determines the full load current (FLC), starting current, cable size, breaker rating, and protection devices based on motor nameplate data and the selected starting method.
Motor Starting Methods
- Direct-on-line (DOL): Highest starting current (5–7 × FLC), suitable for small motors on robust supplies. Requires curve D breaker.
- Star-delta: Reduces starting current to ~2 × FLC. Requires switching equipment and reduced torque during start.
- Soft-starter: Electronic control allows gradual acceleration, starting current ~3 × FLC. No torque loss.
- Variable Frequency Drive (VFD): Soft acceleration, lowest starting current (~1.5 × FLC). Most efficient, enables speed control.
Disclaimer: These results are indicative only. All motor circuits must be designed and verified by a qualified electrical engineer in accordance with AS/NZS 3000:2018 and AS/NZS 1359 before installation. Motor starting must be coordinated with the supply authority if the motor is large (typically >7.5 kW).