AS/NZS 3000 + 3008

Full Load Current Calculator

Calculate FLC for motors, transformers, heaters, and lighting with breaker recommendations per AS/NZS 3000.

Inputs

Typical: 0.85 to 1.0

Typical: 85 to 95%

Results

Full Load Current

17.82

Amperes

Equipment Typemotor
Rated Power10 kW
Voltage400 V
Phase ConfigurationThree Phase
Power Factor0.9
Efficiency90%

Recommendation: Use this FLC to select cable sizes and protection devices with appropriate safety margins.

Show the working
Step by step derivation of the result
StepWorkingResultReference
Equipment TypeDefaults for motor: PF 0.85, efficiency 90%motorAS/NZS 3000:2018
VoltageV = 400 V, used in the denominator of the FLC formula400 VAS/NZS 3000:2018 Cl. 1.5, Standard voltage
Phase ConfigurationPhase factor used in the denominator: 1.732 (sqrt(3) for three phase)Three Phase (3φ)AS/NZS 3000:2018
Power Rating10 kW x 1000 = 10000 W used in the current formula10 kWEquipment nameplate
Power FactorEntered PF = 0.9 (motor default is 0.85)0.9Equipment type default: 0.85
Efficiency90% / 100 = 0.9 used as eta90 %Equipment type default: 90%
Full Load Current (FLC)10 x 1000 / (1.732 x 400 V x 0.9 x 0.9) = 17.82 A17.82 AI = (P × 1000) / (√3 × V × PF × η)
Apparent Power10 kW / 0.9 x 0.9 = 10 kVA10 kVAS = P / (PF × η)
Phase CurrentBalanced three-phase load, so I_phase = FLC = 17.82 A17.82 AEach phase carries equal current in balanced system
Starting Current (Motor)17.82 A x 6 = 106.92 A assuming direct-on-line (DOL) starting106.92 ATypical DOL starting = 6 × FLC (varies by starting method)
Breaker SelectionStandard size lookup: 17.82 A against 6/10/16/20/25/32/40/50/63/80/100/125/160/200/250/315/400/500/630 A gives 20 A20 ANext standard breaker size ≥ FLC per AS/NZS 3000:2018
Cable Sizing (Copper, 75°C)Table lookup: FLC 17.82 A sits in the up-to-20 A band (copper, 75 degC) = 4 mm24 mm²AS/NZS 3008.1.1:2025 (simplified lookup)

Standards referenced

  • AS/NZS 3000:2018 Clause 1.5. Standard voltages for installation
  • AS/NZS 3000:2018 Clause 2.2. Protection against overcurrent
  • AS/NZS 3008.1.1:2025 Clause 4. Current-carrying capacity of cables
  • AS/NZS 1359. Electrical equipment, Motors and rotating machinery

Lookup values used by these calculators are indicative and awaiting validation against the current standards. Confirm against your own licensed copy before relying on a result for design.

Important: These results are indicative only and must be verified by a qualified electrical engineer before use in design or installation.

Parameters

Six fields drive the calculation. All six are always sent, which matters more than it sounds: the equipment type has built in default values for power factor and efficiency, but because the form always supplies its own numbers for those two fields, the defaults never take effect. Whatever you leave in the power factor and efficiency boxes is what gets used.

Equipment type
Motor, transformer, heater, lighting or general load. Unitless selection. It changes the calculation in two ways only. Choosing motor adds a starting current estimate and an extra compliance check. Choosing transformer makes the apparent power output echo your rating figure straight through as kilovolt-amperes rather than deriving it. Gotcha. The type does not change the full load current formula, and it does not override the power factor and efficiency you have typed in. Selecting heater does not silently set power factor to 1.0 for you.
Rating
The nameplate rating of the equipment, in kilowatts. Form range 0.1 to 10000, default 10. For a motor this is the mechanical shaft output, not the electrical input, which is why efficiency appears in the formula. Gotcha. The box is labelled kW but it is the only rating field on the form, so a transformer rated in kilovolt-amperes goes in here too. When you do that, set power factor to 1.0 and efficiency to 100 so the figure is not divided down a second time. See worked example 3.
Voltage
Supply voltage in volts. Form range 100 to 50000, default 400. For a three-phase selection this is the line-to-line voltage, normally 400 V nominal or 415 V as measured. For a single-phase selection it is the phase-to-neutral voltage, normally 230 V. Gotcha. The form does not change this value when you switch the phase type, so selecting single phase while 400 V is still in the box will calculate a 400 V single-phase circuit and quietly give you a current about 42 per cent too low.
Phase type
Single phase or three phase. Unitless selection. Single phase divides by voltage alone. Three phase divides by voltage multiplied by 1.7320508, the square root of three. Gotcha. The dropdown labels mention 230 V and 400 V for convenience, but the labels are cosmetic. The voltage actually used is whatever is typed in the voltage field.
Power factor
Displacement power factor at rated load. Dimensionless, form range 0.7 to 1.0, default 0.9. Typical values are 0.80 to 0.90 for a loaded induction motor, 1.0 for resistive heating, and 0.90 to 0.95 for modern LED lighting with a corrected driver. Sits in the denominator, so a lower power factor gives a higher current. Gotcha. Use the nameplate value where one exists. Motor power factor collapses at part load, so a motor running at 40 per cent of rating may sit near 0.6 rather than the 0.85 on its plate.
Efficiency
Ratio of mechanical output to electrical input, as a percentage. Form range 50 to 100, default 90. Modern IE3 motors run from about 85 per cent at 0.75 kW to about 96 per cent at 200 kW. Also sits in the denominator, so a less efficient machine draws more current for the same shaft output. Gotcha. Efficiency only belongs in the formula when the rating is a mechanical output. For heaters, lighting circuits, general loads quoted as electrical input, and transformers quoted in kilovolt-amperes, set this to 100 or the current will be overstated.

Assumptions and limits

What the tool assumes

  • A balanced, sinusoidal supply. Three-phase results assume equal current on all three lines at fundamental frequency. Harmonic current from drives, rectifiers and switching supplies is not modelled, so the real conductor loading on a distorted supply will be higher than the figure shown.
  • Steady state at rated output. The result is the current at the rating you typed in. It is not a demand figure, it carries no diversity, and it says nothing about duty cycle.
  • Motor starting current is a flat six times full load current. That is a direct on line rule of thumb. Real locked rotor current varies roughly from four to eight times depending on the motor design code, and star delta, soft starter and variable speed drive starting all give very different figures. The starting current shown is an estimate only and the tool has no input for starting method.
  • The apparent power output is not derived from the current. For non transformer types it is calculated as the rating divided by power factor and then multiplied by efficiency. That is not the same as the input kilovolt-amperes implied by the full load current result, and the two will not agree. Treat the full load current as the primary output and use the apparent power figure as a rough indication only.
  • Breaker selection is a lookup, not a design. The tool returns the next standard rating at or above the full load current from the series 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500 and 630 A. It applies no motor starting allowance, no curve selection, no discrimination study and no short circuit rating check.
  • The cable size is an indicative lookup, not a transcription of the standard. It is a simplified table built for copper conductors at a 75 degree Celsius insulation rating in a typical installation. It carries no derating for ambient temperature, grouping, installation method, insulation type or thermal insulation, and it does no voltage drop check at all, because the tool never asks for a route length. It must not be used as a cable size.

What the compliance checks actually check

Two checks always run, plus a third for motors. The first flags a full load current above 630 A, which is a practical ceiling built into this tool rather than a limit from AS/NZS 3000. The second confirms the selected breaker rating is at least the full load current, which is arithmetic on the tool's own output rather than an independent test. The third, for motors only, asks whether the selected breaker rating is at least 1.1 times the estimated starting current. Because starting current is fixed at six times full load current, that check fails for essentially every motor. It is flagging that a breaker sized on running current alone is not a motor starting study, which is true and worth knowing, but it is not evidence that the design is wrong.

What this must not be used for

  • Final cable selection. Use AS/NZS 3008.1.1 with the actual installation method, ambient temperature, grouping and route length, or use the Cable Sizing calculator which asks for all of those.
  • Motor protection design, starter selection, or overload relay settings.
  • Maximum demand. Full load current is a per circuit figure with no diversity applied. Use the Maximum Demand calculator for a switchboard.
  • Transformer inrush, through fault, or protection grading work.
  • Any load with significant harmonic content, where conductor and neutral loading need a harmonic study.
  • Evidence of compliance. This calculator is not validated or certified. Confirm every result against the equipment nameplate and the current editions of AS/NZS 3000 and AS/NZS 3008.1.1, and have it signed off by the person responsible for the installation.

Worked examples

Three examples covering a three-phase motor, a single-phase resistive load and a transformer. Every figure comes from the formulas the calculator runs, so you can reproduce them on the form above.

Example 1. Three-phase motor at design stage

A mechanical schedule calls for a 10 kW pump motor on a 400 V three-phase supply. The motor has not been purchased, so there is no nameplate. You use 0.9 power factor and 90 per cent efficiency as design assumptions.

Equipment type
Motor
Rating
10 kW
Voltage
400 V
Phase type
Three phase
Power factor
0.9
Efficiency
90 percent

Numerator: 10 x 1000 = 10000

Denominator: 400 x 1.7320508 = 692.82, then x 0.9 = 623.54, then x 0.90 = 561.18

Full load current: 10000 divided by 561.18 = 17.82 A

Estimated starting current: 17.82 x 6 = 106.92 A

Breaker: next standard rating at or above 17.82 A is 20 A

Indicative cable: 17.82 A falls in the band up to 20 A, giving 4 square millimetres

Reported apparent power: 10 divided by 0.9, then x 0.90 = 10.00 kilovolt-amperes

Result: 17.82 A. Below the 630 A ceiling, PASS. Breaker 20 A is at least 17.82 A, PASS. Breaker handles starting current, FAIL: 20 A is not at least 1.1 x 106.92 A = 117.6 A. That last failure is the expected outcome for any direct on line motor and is a prompt to do a proper starting study and pick a motor rated protective device, not a sign the 17.82 A figure is wrong.

Example 2. Single-phase resistive heater

A 4.8 kW single-phase bathroom heater bank runs from a 230 V final subcircuit. Resistive heating has unity power factor and turns essentially all its input into heat, so efficiency is set to 100 per cent.

Equipment type
Heater
Rating
4.8 kW
Voltage
230 V
Phase type
Single phase
Power factor
1.0
Efficiency
100 percent

Single phase drops the 1.7320508 factor, so the denominator is 230 x 1.0 x 1.00 = 230

Full load current: 4800 divided by 230 = 20.87 A

Breaker: next standard rating at or above 20.87 A is 25 A

Indicative cable: 20.87 A falls in the band up to 25 A, giving 6 square millimetres

Reported apparent power: 4.8 divided by 1.0, then x 1.00 = 4.80 kilovolt-amperes, which for a unity power factor load correctly equals the kilowatt rating

No starting current is produced, because starting current is only estimated for the motor equipment type

Result: 20.87 A. Below the 630 A ceiling, PASS. Breaker 25 A is at least 20.87 A, PASS. Both checks pass because a resistive load has no inrush to worry about.

Example 3. Transformer secondary, and the mistake to avoid

A 500 kilovolt-ampere distribution transformer has a 400 V three-phase secondary. You want the secondary full load current to check the main switch and busbar. Because the form has only a kW box, the 500 goes in there, and power factor and efficiency must both be neutralised so the figure is not divided down twice.

Equipment type
Transformer
Rating
500
Voltage
400 V
Phase type
Three phase
Power factor
1.0
Efficiency
100 percent

Denominator: 400 x 1.7320508 x 1.0 x 1.00 = 692.82

Full load current: 500000 divided by 692.82 = 721.69 A, which matches the textbook transformer result of kilovolt-amperes divided by 1.732 and the secondary voltage

Reported apparent power: 500.00 kilovolt-amperes, echoed straight through because the equipment type is transformer

Breaker: 721.69 A is above the top of the standard series, so the tool returns its largest entry, 630 A

Indicative cable: above the top band, so the tool returns its largest entry, 400 square millimetres

Result: 721.69 A. Full load current within typical range, FAIL, because 721.69 A exceeds the 630 A ceiling. Breaker rating adequate, FAIL, because the returned 630 A is less than 721.69 A. Both failures are the tool telling you it has run off the end of its own tables. A 500 kilovolt-ampere secondary needs an air circuit breaker and a busbar or multiple parallel cables designed properly, not a single lookup. Note also what happens if you leave the defaults alone: at 0.9 power factor and 90 per cent efficiency the same inputs return 890.97 A, which is 23 per cent high and simply wrong for a transformer rated in kilovolt-amperes.

Full Load Current Guide

Full Load Current (FLC) is the steady-state current drawn by an electrical load when operating at its rated output. It is the starting point for almost every downstream design decision: cable sizing, circuit breaker selection, switchboard busbar rating, and maximum demand calculations. An incorrect FLC value cascades errors through the entire design, potentially resulting in undersized cables, nuisance-tripping, or overheating. This calculator determines FLC for motors, transformers, heaters, lighting circuits, and general loads based on the rated power, supply voltage, power factor, and efficiency.

The formulas follow standard electrical engineering practice as applied in AS/NZS 3000:2018 and AS/NZS 3008.1.1. For motors, the calculator accounts for both power factor and efficiency in the denominator, which is a common source of error when calculating by hand. For transformers, it uses the apparent power (kVA) rating directly, since transformer losses are already factored into the nameplate data.

Key concepts

  • Three-phase FLC formula. For three-phase loads: FLC = P / (1.732 x V x PF x efficiency). The 1.732 factor (square root of 3) accounts for the phase relationship in a balanced three-phase system. For resistive loads like heaters, PF is 1.0 and efficiency is 1.0, simplifying the calculation.
  • Power factor (PF). The ratio of real power (kW) to apparent power (kVA). Induction motors typically operate at 0.80 to 0.90 PF at full load. A lower power factor means the motor draws more current for the same mechanical output. PF varies with load; it drops significantly at light loads, which is why oversized motors waste energy.
  • Efficiency. The percentage of electrical input power converted to useful mechanical output. Modern IE3 motors range from 85% (small, 0.75 kW) to 96% (large, 200 kW). Efficiency appears in the denominator, so a less efficient motor draws more current for the same output power.
  • Nameplate current vs calculated FLC. Motor nameplates list the rated current at full load conditions. This should match the calculated FLC closely. If the nameplate is available, always use it for cable and protection sizing. The calculator is most useful when the nameplate is not available (design stage), when comparing equipment options, or when verifying nameplate data.

Common scenarios

  1. Sizing a motor circuit at design stage. A mechanical engineer specifies a 15 kW pump motor at 400 V three-phase, but the motor has not been purchased yet and no nameplate data is available. Using default values of 0.85 PF and 0.90 efficiency, the calculator returns an FLC of approximately 28.4 A. The electrical designer uses this to select a 32 A circuit breaker and 6 mm squared cable (with derating checks via the Cable Sizing calculator).
  2. Checking transformer secondary current. A 500 kVA three-phase transformer with a 400 V secondary needs busbar and cable sizing on the LV side. FLC = 500,000 / (1.732 x 400) = 722 A. This current determines the minimum busbar cross-section, the main switch rating, and the cable size from the transformer to the main switchboard.
  3. Maximum demand calculation for a switchboard.An electrician needs the FLC of each circuit to build a maximum demand schedule for a commercial fit-out. The loads include a 15 kW three-phase oven (resistive, FLC = 21.7 A), a 7.5 kW exhaust fan motor (FLC = 14.2 A at 0.85 PF, 0.90 efficiency), and 4.8 kW of LED lighting (single-phase, FLC = 20.9 A per phase). The calculator provides each FLC value for the demand schedule.
Disclaimer: This calculator is provided as a guide only. Full load current values must be verified against equipment nameplates and the current edition of AS/NZS 3000 and AS/NZS 3008.1.1 by a qualified electrical engineer.

Common questions

How do I calculate full load current for a three-phase motor?+

FLC = P / (1.732 times V times cos(phi) times efficiency). For a 7.5 kW 400 V motor at 0.85 power factor and 0.90 efficiency: FLC = 7500 / (1.732 times 400 times 0.85 times 0.90) = 14.1 A. Use the nameplate values where available; otherwise default to 0.85 PF and 0.90 efficiency.

What is the difference between FLC and nameplate current?+

Full load current (FLC) is the current at rated power output. Nameplate current is the same value printed on the motor nameplate. Some motors list the rated current at the service factor (e.g. 1.15 times rated), which is higher than FLC. Always clarify which value is shown and use the FLC for cable and protection sizing.

How do I calculate FLC for a single-phase load?+

For single-phase: FLC = P / (V times cos(phi)). For a 2.4 kW single-phase heater at unity power factor: FLC = 2400 / 230 = 10.4 A. For a motor, include efficiency in the denominator: FLC = P / (V times cos(phi) times efficiency).

Why is FLC important for cable sizing?+

The cable must carry the full load current continuously without exceeding its temperature rating. The cable current carrying capacity (Iz) after derating must be greater than or equal to the FLC. FLC also determines the circuit breaker rating and the earth fault loop impedance check.

How do I calculate FLC for a transformer?+

For a three-phase transformer: FLC = kVA times 1000 / (1.732 times V). For a 500 kVA transformer at 400 V secondary: FLC = 500000 / (1.732 times 400) = 722 A. For single-phase: FLC = kVA times 1000 / V.

SparkyToolkit · iOS

On site? Get the same calcs on your phone.

SparkyToolkit gives you offline calculators, AI standards lookup, and on-site drawing tools, all built by the same team behind ElecCalc.

Download on theApp Store

Building something else? EmergencyAPI gives developers real-time AU emergency feeds (fires, floods, warnings) as GeoJSON.

Related calculators