Six printable cards of the AS/NZS 3000:2018 limits you check most on the job: maximum Zs, Rphe and Re, earth conductor sizes, disconnection times, verification test limits and where 30 mA RCDs are required. Free, no sign-up, no email.
Every value is read from the same transcribed tables the ElecCalc calculators use, and those tables are locked by regression tests, so a card and a calculator can never disagree. They are a quick reference, not a copy of the standard.
Print or save as PDF puts one card on each A4 page. Pocket size puts two cards on each A4 sheet: cut along the dashed line and fold each card in half to fit a shirt pocket or a meter case. In the print dialog, choose Save as PDF to keep a copy on your phone.
Card 1 · AS/NZS 3000:2018 Table 8.1
Maximum earth fault-loop impedance (Zs)
| Rating (A) | MCB Type B0.4 s | MCB Type C0.4 s | MCB Type D0.4 s | Fuse0.4 s | Fuse5 s |
|---|---|---|---|---|---|
| 6 | 9.6 | 5.1 | 3.1 | 11.5 | 15.3 |
| 10 | 5.8 | 3.1 | 1.8 | 6.4 | 9.2 |
| 16 | 3.6 | 1.9 | 1.2 | 3.1 | 5.0 |
| 20 | 2.9 | 1.5 | 0.9 | 2.1 | 3.6 |
| 25 | 2.3 | 1.2 | 0.7 | 1.6 | 2.7 |
| 32 | 1.8 | 1.0 | 0.6 | 1.3 | 2.2 |
| 40 | 1.4 | 0.8 | 0.5 | 1.0 | 1.6 |
| 50 | 1.2 | 0.6 | 0.4 | 0.7 | 1.3 |
| 63 | 0.9 | 0.5 | 0.3 | 0.6 | 0.9 |
| 80 | 0.7 | 0.4 | 0.2 | 0.4 | 0.7 |
| 100 | 0.6 | 0.3 | 0.2 | 0.3 | 0.5 |
| 125 | 0.5 | 0.2 | 0.1 | 0.2 | 0.4 |
| 160 | 0.4 | 0.2 | 0.1 | 0.2 | 0.3 |
| 200 | 0.3 | 0.2 | 0.1 | 0.1 | 0.2 |
Source: AS/NZS 3000:2018 Table 8.1. Check against the standard; have it signed off by whoever is responsible for the installation.
Use it with: Test results recorder (eleccalc.au/test-results), Circuit breaker calculator (eleccalc.au/calculator/circuit-breaker), Earthing system calculator (eleccalc.au/calculator/earthing-system).
Free from eleccalc.au/reference-cards#table-8-1
Card 2 · AS/NZS 3000:2018 Table 8.2
Maximum circuit resistance (Rphe and Re)
| Rating (A) | Active / earth (mm²) | MCB Type B, 0.4 s | MCB Type C, 0.4 s | MCB Type D, 0.4 s | Fuse, 0.4 s | Fuse, 5 s | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Rphe | Re | Rphe | Re | Rphe | Re | Rphe | Re | Rphe | Re | ||
| 6 | 1 / 1 | 6.1 | 3.1 | 3.3 | 1.6 | 2.0 | 1.0 | 7.4 | 3.7 | 9.8 | 4.9 |
| 10 | 1 / 1 | 3.7 | 1.8 | 2.0 | 1.0 | 1.2 | 0.6 | 4.1 | 2.0 | 5.9 | 2.9 |
| 10 | 1.5 / 1.5 | 3.7 | 1.8 | 2.0 | 1.0 | 1.2 | 0.6 | 4.1 | 2.0 | 5.9 | 2.9 |
| 16 | 1.5 / 1.5 | 2.3 | 1.2 | 1.2 | 0.6 | 0.7 | 0.4 | 2.0 | 1.0 | 3.2 | 1.6 |
| 16 | 2.5 / 2.5 | 2.3 | 1.2 | 1.2 | 0.6 | 0.7 | 0.4 | 2.0 | 1.0 | 3.2 | 1.6 |
| 20 | 2.5 / 2.5 | 1.8 | 0.9 | 1.0 | 0.5 | 0.6 | 0.3 | 1.3 | 0.7 | 2.3 | 1.1 |
| 25 | 4 / 2.5 | 1.5 | 0.9 | 0.8 | 0.5 | 0.5 | 0.3 | 1.0 | 0.6 | 1.7 | 1.1 |
| 32 | 4 / 2.5 | 1.2 | 0.7 | 0.6 | 0.4 | 0.4 | 0.2 | 0.8 | 0.5 | 1.4 | 0.9 |
| 40 | 6 / 2.5 | 0.9 | 0.6 | 0.5 | 0.3 | 0.3 | 0.2 | 0.6 | 0.4 | 1.0 | 0.7 |
| 50 | 10 / 4 | 0.7 | 0.5 | 0.4 | 0.3 | 0.2 | 0.2 | 0.5 | 0.3 | 0.8 | 0.6 |
| 63 | 16 / 6 | 0.6 | 0.4 | 0.3 | 0.2 | 0.2 | 0.1 | 0.4 | 0.3 | 0.6 | 0.4 |
Source: AS/NZS 3000:2018 Table 8.2. Check against the standard; have it signed off by whoever is responsible for the installation.
Use it with: Test results recorder (eleccalc.au/test-results), Cable sizing calculator (eleccalc.au/calculator/cable-sizing).
Free from eleccalc.au/reference-cards#table-8-2
Card 3 · AS/NZS 3000:2018 Table 5.1
Minimum earthing conductor size
| Active conductor (mm²) | Minimum earth (mm²) |
|---|---|
| 1 | 1 |
| 1.5 | 1.5 |
| 2.5 | 2.5 |
| 4 | 2.5 |
| 6 | 2.5 |
| 10 | 4 |
| 16 | 6 |
| 25 | 6 |
| 35 | 10 |
| 50 | 16 |
| 70 | 25 |
| 95 | 25 |
| 120 | 35 |
| 150 | 50 |
| 185 | 70 |
| 240 | 95 |
| 300 | 120 |
| 400 | 120 |
| 500 | 120 |
| 630 | 120 |
Source: AS/NZS 3000:2018 Table 5.1. Check against the standard; have it signed off by whoever is responsible for the installation.
Use it with: Earth conductor calculator (eleccalc.au/calculator/earth-conductor), Cable sizing calculator (eleccalc.au/calculator/cable-sizing).
Free from eleccalc.au/reference-cards#table-5-1
Card 4 · AS/NZS 3000:2018 Clause 5.7.2
Maximum disconnection times
| Circuit | Maximum time |
|---|---|
| Final subcircuit supplying socket-outlets not exceeding 63 A, item (a)(i) | 0.4 s |
| Final subcircuit supplying hand-held Class I equipment | 0.4 s |
| Final subcircuit supplying portable equipment moved in use | 0.4 s |
| Fixed or stationary equipment, permitted only where people are not exposed to touch voltages above safe values (Appendix B4) | 5 s |
| Submain or other circuit, permitted only where people are not exposed to touch voltages above safe values (Appendix B4) | 5 s |
Source: AS/NZS 3000:2018 Clause 5.7.2. Check against the standard; have it signed off by whoever is responsible for the installation.
Use it with: Earthing system calculator (eleccalc.au/calculator/earthing-system), Circuit breaker calculator (eleccalc.au/calculator/circuit-breaker).
Free from eleccalc.au/reference-cards#disconnection-times
Card 5 · AS/NZS 3000:2018 Section 8, Clause 8.3
Verification test limits
| Test | Limit | Clause |
|---|---|---|
| Main earthing and bonding conductor resistance | ≤ 0.5 Ω | Cl 8.3.5.2 |
| Consumer mains insulation resistance | ≥ 1 MΩ | Cl 8.3.6.3 |
| Earth continuity (Re) | Table 8.2 Re for the device, rating and cable | Cl 8.3.5.2, Table 8.2 |
| Insulation resistance250 V is permitted where connected equipment is likely to be damaged by the 500 V test. Cl 8.3.6.3 exceptions: sheathed heating elements not less than 0.01 MΩ; RCD functional earth connections not less than 0.05 MΩ. Disconnect such equipment and test it separately. | ≥ 1 MΩ at 500 V | Cl 8.3.6.3 |
| Polarity | Pass or fail | Cl 8.3.7 |
| Correct circuit connections | Pass or fail | Cl 8.3.8 |
| Earth fault-loop impedanceRequired only where the circuit supplies socket-outlets that are not protected by an RCD of 30 mA or less. The disconnection time requirement still applies to every circuit. | Zs within Table 8.1, or Rphe within Table 8.2 | Cl 8.3.9.1 |
| RCD operation; isolates all switched polesAS/NZS 3000 Cl 8.3.10 Note 4: there is no requirement to test operating time. A recorded trip time is kept for the record only; check it against AS/NZS 3017 if you test it. | Pass or fail | Cl 8.3.10 |
Source: AS/NZS 3000:2018 Section 8, Clause 8.3. Check against the standard; have it signed off by whoever is responsible for the installation.
Use it with: Test results recorder (eleccalc.au/test-results), Earthing system calculator (eleccalc.au/calculator/earthing-system).
Free from eleccalc.au/reference-cards#test-limits
Card 6 · AS/NZS 3000:2018 Clause 2.6.3
Where 30 mA RCDs are required
| Final subcircuit | Australia, domestic or residential | Australia, non-domestic | New Zealand, residential |
|---|---|---|---|
| Socket-outlet | Required, 30 mA maximumCl 2.6.3.2.2 | Required, 30 mA maximumCl 2.6.3.2.3.3(a) | Required, 30 mA maximumCl 2.6.3.3.1(a) |
| Lighting | Required, 30 mA maximumCl 2.6.3.2.2 | Required, 30 mA maximumCl 2.6.3.2.3.3(b) | Required, 30 mA maximumCl 2.6.3.3.1(b) |
| Directly connected hand-held equipment | Required, 30 mA maximumCl 2.6.3.2.2 | Required, 30 mA maximumCl 2.6.3.2.3.3(c) | Required, 30 mA maximumCl 2.6.3.3.1(c) |
| Fixed appliance | Required, 30 mA maximumCl 2.6.3.2.2 | Should be considered, 30 mA maximumCl 2.6.3.2.3.3 Note | Not required by Clause 2.6.3Cl 2.6.3.3.1 |
- Cl 2.6.3.2.2:
- All final subcircuits in domestic and residential installations, fixed appliances included.
- Cl 2.6.3.2.3.3 Note:
- Other direct connected equipment not exceeding 32 A: 30 mA protection should be considered.
- Cl 2.6.3.2.3.3(a):
- Socket-outlet final subcircuit not exceeding 32 A.
- Cl 2.6.3.2.3.3(b):
- Lighting final subcircuit not exceeding 32 A.
- Cl 2.6.3.2.3.3(c):
- Directly connected hand-held equipment final subcircuit not exceeding 32 A.
- Cl 2.6.3.3.1:
- Residential fixed appliance circuits are not listed in Cl 2.6.3.3.1 (check other Sections, for example Cl 4.10.5 heating cables).
- Cl 2.6.3.3.1(a):
- Residential socket-outlet final subcircuit.
- Cl 2.6.3.3.1(b):
- Residential lighting final subcircuit.
- Cl 2.6.3.3.1(c):
- Residential directly connected hand-held equipment final subcircuit.
Source: AS/NZS 3000:2018 Clause 2.6.3. Check against the standard; have it signed off by whoever is responsible for the installation.
Use it with: RCD selection calculator (eleccalc.au/calculator/rcd-selection), Test results recorder (eleccalc.au/test-results).
Free from eleccalc.au/reference-cards#rcd-requirements