AS/NZS 3008.1.1 reference

AS/NZS 3008 table numbers: 2017 to 2025

The 2025 edition of AS/NZS 3008.1.1 renumbered its tables. If your notes, cable schedules, or a design brief reference an old table number, use this map to find the equivalent in the current edition. It covers 43 of the commonly-used current-rating, derating, and voltage-drop tables.

Scroll tables sideways to see every column.

Installation methods and limiting temperature

20172025Installation methodLocation
T1
3.1
Limiting temperature for insulated cables
T3(1)
3.5
UnenclosedAbove ground
T3(2)
3.6
Enclosed
T3(3)
3.7
Buried directBelow ground
T3(4)
3.8
Underground wiring enclosure

Current-carrying capacity

20172025InsulationMax tempArrangement
T4
3.9
Thermoplastic (V)
75°C
Single core, single-phase
T5
3.10
XLPE (X)
90°C
T6
3.11
Elastomer (R)
110°C
T7
3.12
Thermoplastic (V)
75°C
Single core, three-phase
T8
3.13
XLPE (X)
90°C
T9
3.14
Elastomer (R)
110°C
T10
3.15
Thermoplastic (V)
75°C
Multicore, single-phase
T11
3.16
XLPE (X)
90°C
T12
3.17
Elastomer (R)
110°C
T13
3.18
Thermoplastic (V)
75°C
Multicore, three-phase
T14
3.19
XLPE (X)
90°C
T15
3.20
Elastomer (R)
110°C

Grouping correction factors

Installation conditionArrangement20172025
In air or in a wiring enclosureBunched or single layer
22
3.33
In trays, racks, cleats or other supports in airSingle-core
23
3.34
Multi-core
24
3.35
Buried direct in groundSingle-core (single row / multiple row)
25(1)
3.36
3.37
Multi-core (single row / multiple row)
25(2)
3.38
3.39
Underground wiring enclosureSingle-core (single row / multiple row)
26(1)
3.40
3.41
Single or multiple core (single row / multiple row)
26(2)
3.42
3.43

Temperature, depth and soil correction factors

Correction forCondition20172025
Variations in ambient temperatureCables in air or heated concrete slabs
27(1)
3.44
In soil or underground wiring enclosures
27(2)
3.45
Depth of layingBuried direct in ground
28(1)
3.46
In underground wiring enclosures
28(2)
3.47
Soil thermal resistivity (from 1.2°C·m/W)Buried direct in ground or in a wiring enclosure
29
3.48

Voltage drop and voltage rise (Section 4)

QuantityCable arrangement20172025
ReactanceSingle-core
30
4.1(A)
Multi-core
30
4.1(B)
ResistanceSingle-core cables
34
4.5(A)
Multicore cables
35
4.7(A)
Voltage dropSingle-core laid flat, trefoil. (A) 25 to 60°C; (B) 75 to 110°C
40
4.14(A)
4.14(B)
Single-core laid flat touching, or in a wiring enclosure. (A) 25 to 60°C; (B) 75 to 110°C
41
4.15(A)
4.15(B)
Multicore. (A) and (B) both 75 to 110°C
42
4.17(A)
4.17(B)

Tables 4.17(A) and 4.17(B) are both at 75 to 110°C, unlike Tables 4.14 and 4.15 which split 25 to 60°C and 75 to 110°C.

Reference only. This maps table numbers and their subject between editions to help you navigate the standard. It does not reproduce any values from the tables. You need a current licensed copy of AS/NZS 3008.1.1:2025 for the actual figures. Numbering is transcribed from a comparison sheet; confirm against your copy of the standard before relying on it for design.

Working with these tables? Try the cable sizing and voltage drop calculators, or read the cable sizing guide.